View larger
S-PT-4-EX-24DC-1/2" 2800037 PHOENIX CONTACT Surge protection device
S-PT-4-EX-24DC-1/2"
2800037
PHOENIX CONTACT
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for field instrumentation, the S-PT-4-EX-24DC-1/2" 2800037 PHOENIX CONTACT Surge protection device by Phoenix Contact is a screw-in surge protection module. These devices are typically mounted directly onto field transmitters and sensors to protect delicate electronic measurement loops from induced lightning surges. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Surge protection for MCR technology
- Product family: SURGETRAB
- IEC test classification: C1
- Type: Screw-in module
- Number of positions: 4
- Data management status Article revision: 08
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal voltage U N: 24 V DC
- Connection method: Individual wires
- Maximum inner capacitance C i: 1.65 nF
- Max. internal inductance L i: 1 µH
- Max. input current I i: 500 mA (T4 / ≤ 75 °C)
- Max. input voltage U i: 36 V DC
- max. input power P i: 3.00 W
- Insulation voltage to ground: 500 V AC
More info
▲| Product type | Surge protection for MCR technology |
| Product family | SURGETRAB |
| IEC test classification | C1 |
| C2 | |
| C3 | |
| D1 | |
| Type | Screw-in module |
| Number of positions | 4 |
| Data management status | |
| Article revision | 08 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 24 V DC |
| Connection method | Individual wires |
| Maximum inner capacitance Ci | 1.65 nF |
| Max. internal inductance Li | 1 µH |
| Max. input current Ii | 500 mA (T4 / ≤ 75 °C) |
| 500 mA (T5 / ≤ 75 °C) | |
| 500 mA (T6 / ≤ 60 °C) | |
| Max. input voltage Ui | 36 V DC |
| max. input power Pi | 3.00 W |
| Insulation voltage to ground | 500 V AC |
| Ambient temperature (operation) | -40 °C ... 75 °C (T4) |
| -40 °C ... 75 °C (T5) | |
| -40 °C ... 60 °C (T6) | |
| Operating temperature range | -40 °C ... 100 °C (T4) |
| -40 °C ... 75 °C (T5) | |
| -40 °C ... 60 °C (T6) | |
| Max. surface temperature | 135 °C (T4) |
| 100 °C (T5) | |
| 85 °C (T6) |
| Dimensional drawing | |
| Width | 28 mm |
| Height | 28 mm |
| Depth | 79 mm |
| Color | Steel/stainless steel color |
| Housing material | Stainless steel 1.4404 |
| ASTM 316L |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Line & Line-Earth Ground |
| Maximum continuous voltage UC | 36 V DC |
| 25 V AC | |
| Operating effective current ICat UC | ≤ 5 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-line) | 260 A |
| Nominal discharge current In(8/20) µs (line-ground) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 1 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Total discharge current Itotal(10/350) µs | 2 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 50 A |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 130 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 1.1 kV |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 60 V |
| Voltage protection level Up(line-line) | ≤ 65 V (C3 - 10 A) |
| Voltage protection level Up(line-earth) | ≤ 1.1 kV (C3 - 100 A) |
| ≤ 1.1 kV (C1 - 1 kV / 500 A) | |
| ≤ 1.2 kV (C2 - 10 kV / 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.1 dB (30 MHz / 50 Ω) |
| typ. 0.1 dB (6 MHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ω system | typ. 70 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ω system | typ. 70 MHz |
| Capacity (Core-Core) | typ. 20 pF |
| Capacity (Core-Earth) | typ. 5 pF |
| Surge protection fault message | none |
| Impulse durability (line-line) | C3 - 25 A |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A | |
| D1 - 1 kA | |
| Alternating current carrying capacity (line-earth) | 10 A - 1 s |
| Ambient conditions | |
| Degree of protection | IP67 |
| Ambient temperature (operation) | -40 °C ... 80 °C (non-Ex) |
| Altitude | ≤ 2000 m (amsl) |
| Conformity/Approvals | |
| ATEX | II 1 G Ex ia IIC T4...T6 |
| II 2 G Ex d IIC T4...T6 | |
| II 1 D Ex iaD 20 IP6x T85 °C...135 °C | |
| II 2 D Ex tD A21 IP6x T85 °C...135 °C | |
| IECEx | Ga Ex ia IIC T4...T6 |
| Ex d IIC T4...T6 | |
| Ex iaD IP6x T85 °C...135 °C | |
| Ex tD A21 IP6x T85 °C...135 °C | |
| Air clearances and creepage distances | |
| Standards/regulations | IEC 60664-1 / IEC 60079-11 |
| Standards/specifications | EN 61643-21 |
| Note | A2:2013 |
| Standards/specifications | EN 60079-0 |
| Note | 2018 |
| Standards/specifications | EN 60079-1 |
| Note | 2007 |
| Standards/specifications | EN 60079-11 |
| Note | 2012 |
| Standards/specifications | EN 60079-31 |
| Note | 2009 |
| Standards/specifications | IEC 60079-0 |
| Note | 2017 |
| Standards/specifications | IEC 60079-1 |
| Note | 2007 |
| Standards/specifications | IEC 60079-11 |
| Note | 2011 |
| Standards/specifications | IEC 60079-31 |
| Note | 2008 |
| Mounting type | 1/2" NPT |