View larger
PT-IQ-4X1+F-24DC-UT 2800983 PHOENIX CONTACT Surge protection device
PT-IQ-4X1+F-24DC-UT
2800983
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PT-IQ-4X1+F-24DC-UT is a multi-stage surge protection device designed for sophisticated MCR technology installations requiring visual fault diagnostics. Industrial facilities use modular signal surge barriers to protect sensitive measurement electronics from sudden voltage spikes and transient anomalies. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Surge protection for MCR technology
- Product family: PLUGTRAB IQ
- IEC test classification: C1
- Type: DIN rail module, two-section, divisible
- Surge protection fault message: Optical, multi-stage
- Data management status Article revision: 08
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal voltage U N: 24 V DC
- Connection method: Screw connection
- Screw thread: M3
- Tightening torque: 0.5 Nm
- Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
- Conductor cross section rigid: 0.2 mm² ... 4 mm²
- Conductor cross section AWG: 24 ... 12
- Width: 17.7 mm
More info
▲| General | |
| Note | Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector. |
| Product type | Surge protection for MCR technology |
| Product family | PLUGTRAB IQ |
| IEC test classification | C1 |
| C2 | |
| C3 | |
| D1 | |
| Type | DIN rail module, two-section, divisible |
| Surge protection fault message | Optical, multi-stage |
| Data management status | |
| Article revision | 08 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal voltage UN | 24 V DC |
| Connection method | Screw connection |
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section rigid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
| Dimensional drawing | |
| Width | 17.7 mm |
| Height | 91.1 mm |
| Depth | 77.5 mm (incl. DIN rail 7.5 mm) |
| Horizontal pitch | 1 Div. |
| Color | black (RAL 9005) |
| black (RAL 9005) | |
| Flammability rating according to UL 94 | V-0 |
| Housing material | PA 6.6 |
| Mechanical data | |
| Open side panel | No |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 700 mA (50 °C) |
| Operating effective current ICat UC | ≤ 1 mA (per path) |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (line-ground) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Voltage protection level Up(line-earth) | ≤ 800 V (C1 - 1 kV / 500 A) |
| ≤ 950 V (C2 - 10 kV / 5 kA) | |
| ≤ 650 V (C2 - 10 kA) | |
| ≤ 780 V (C3 - 25 A) | |
| Voltage protection level Up(line-signalground) | ≤ 75 V (C1 - 1 kV / 500 A) |
| ≤ 135 V (C2 - 10 kV / 5 kA) | |
| ≤ 180 V (C2 - 10 kA) | |
| ≤ 55 V (C3 - 25 A) | |
| ≤ 60 V (C3 - 50 A) | |
| Voltage protection level Upstatic (line-earth) | ≤ 80 V (C2 - 10 kV / 5 kA) |
| ≤ 230 V (C2 - 10 kA) | |
| Response time tA(line-earth) | ≤ 100 ns |
| Response time tA(line-signalground) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 300 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), asym. (signal ground) in 150 Ω system | typ. 1.1 MHz |
| Capacity (Core-Earth) | typ. 2 nF |
| Resistance per path | 1.2 Ω ±5 % |
| Surge protection fault message | Optical, multi-stage |
| Max. required back-up fuse | 800 mA (FF) |
| Impulse durability (line-earth) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C2 - 10 kA | |
| C3 - 50 A | |
| D1 - 2.5 kA | |
| Impulse durability (line-signalground) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C2 - 10 kA | |
| C3 - 50 A | |
| D1 - 2,5 kA | |
| Pulse reset time (line-earth) | ≤ 30 ms |
| Pulse reset time (line-signalground) | ≤ 350 ms |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 70 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl) |
| Standards/specifications | IEC 61643-21 |
| Note | 2000 + A1:2008, modified |
| Standards/specifications | EN 61643-21 |
| Note | 2001 + A1:2009 |
| Standards/specifications | EN 61000-6-3 |
| Note | 2007 + A1:2011 |
| Standards/specifications | EN 61000-6-2 |
| Note | 2005 |
| Mounting type | DIN rail: 35 mm |