Request QuoteProduct Overview
Engineered for electrical defense, the Phoenix Contact LIT 4X1-24 surge protection device limits transient overvoltages to protect sensitive instrumentation and control loops. These modular units are commonly integrated into multi-channel industrial setups to maintain operational continuity and shield hardware from voltage spikes. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 24 V
More info
▲Key Commercial Data
| Orderkey | 2804649 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 117 (C-4-2017) |
| GTIN | 4046356428286 |
| Weight per Piece (excluding packing) | 63.740 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 80 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | anthracite grey RAL 7016 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, one-piece |
| Direction of action | Line-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 36 V DC |
| 25 V AC | |
| Rated current | 350 mA (40° C) |
| Operating effective current ICat UC | ≤ 2 µA |
| Residual current IPE | ≤ 8 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 500 A |
| 2 kA (in total) | |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| 20 kA (in total) | |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 50 A |
| 200 A (in total) | |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 60 V |
| Residual voltage at In(line-earth) | ≤ 50 V |
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 60 V |
| Voltage protection level Up(line-earth) | ≤ 60 V (C1 - 500 V / 250 A) |
| ≤ 95 V (C2 - 10 kV / 5 kA) | |
| ≤ 55 V (C3 - 10 A) | |
| ≤ 55 V (C3 - 50 A) | |
| ≤ 250 V (D1 - 500 A) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (1 MHz / 50 Ω) |
| typ. 0.2 dB (350 kHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system | typ. 6 MHz |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 2 MHz |
| Capacity | ≤ 1.3 nF (per channel) |
| Resistance in series | 3.3 Ω ±20 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 315 mA (T) |
| Impulse durability (line-earth) | C1 - 500 V / 250 A |
| C2 - 10 kV/5 kA | |
| C3 - 50 A | |
| D1 - 500 A | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |