Shielding low-voltage instrumentation from harmful electrical disturbances, the Phoenix Contact LIT 4-12 2804704 PHOENIX CONTACT Surge protection device is a staple component in industrial automation hardware. Specialized surge barriers protect delicate electronics from voltage surges that can otherwise cause catastrophic system failure.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 12 V
More info
▲Key Commercial Data
| Orderkey | 2804704 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 123 (C-4-2017) |
| GTIN | 4046356462204 |
| Weight per Piece (excluding packing) | 61.870 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 80 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | anthracite grey RAL 7016 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, one-piece |
| Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 12 V DC |
| Maximum continuous voltage UC | 18 V DC |
| 13 V AC | |
| Rated current | 500 mA (40 °C) |
| Operating effective current ICat UC | ≤ 2 µA |
| Residual current IPE | ≤ 4 µA |
| Nominal discharge current In(8/20) µs (line-line) | 350 A |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 500 A |
| 2 kA (in total) | |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 350 A |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| 20 kA (in total) | |
| Nominal pulse current Ian (10/1000) µs (line-line) | 70 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 50 A |
| 200 A (in total) | |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 50 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 650 V |
| Residual voltage at In(line-line) | ≤ 50 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 50 V |
| Voltage protection level Up(line-line) | ≤ 50 V (C1 - 500 V / 250 A) |
| ≤ 35 V (C3 - 10 A) | |
| ≤ 40 V (C3 - 70 A) | |
| Voltage protection level Up(line-earth) | ≤ 650 V (C1 - 500 V / 250 A) |
| ≤ 650 V (C2 - 10 kV / 5 kA) | |
| ≤ 650 V (C3 - 10 A) | |
| ≤ 700 V (C3 - 50 A) | |
| ≤ 700 V (D1 - 500 A) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (1.5 MHz/50 Ω) |
| typ. 0.3 dB (500 kHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 5 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1.7 MHz |
| Capacity | ≤ 1.5 nF (per path) |
| Resistance in series | 0 Ω |
| Surge protection fault message | none |
| Max. required back-up fuse | 500 mA (T) |
| Impulse durability (line-line) | C1 - 500 V / 250 A |
| C3 - 70 A | |
| Impulse durability (line-earth) | C1 - 500 V / 250 A |
| C2 - 10 kV/5 kA | |
| C3 - 50 A | |
| D1 - 500 A | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection method IN | PLUGTRAB plug-in system |
| Connection method OUT | PLUGTRAB plug-in system |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Standards and Regulations
| Standards/specifications | EN 61643-21 A2:2013 |
|---|---|
| EN 60079-0 2012 | |
| EN 60079-11 2012 | |
| EN 60079-26 2007 | |
| IEC 60079-0 2011 | |
| IEC 60079-11 2011 | |
| IEC 60079-26 2006 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|