View larger
LIT 1X2-24 2804610 PHOENIX CONTACT Surge protection device
LIT 1X2-24
2804610
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact Surge protection device part number LIT 1X2-24 is a slimline suppression module deployed within industrial measurement and control loops to prevent high-voltage surges from damaging connected automation instrumentation.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2804610
- Packing unit: 10 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 100 (C-4-2017)
- GTIN: 4046356428330
- Weight per Piece (excluding packing): 53.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 93.1 mm
- Width: 6.2 mm
- Depth: 102.5 mm (incl. DIN rail 7.5 mm)
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: PBT
More info
▲Key Commercial Data
| Orderkey | 2804610 |
|---|---|
| Packing unit | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 100 (C-4-2017) |
| GTIN | 4046356428330 |
| Weight per Piece (excluding packing) | 53.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 80 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | anthracite grey RAL 7016 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, one-piece |
| Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 36 V DC |
| 25 V AC | |
| Rated current | 350 mA (40° C) |
| Operating effective current ICat UC | ≤ 2 µA |
| Residual current IPE | ≤ 2 µA |
| Nominal discharge current In(8/20) µs (line-line) | 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 500 A |
| 1 kA (in total) | |
| Total discharge current Itotal(8/20) µs | 10 kA |
| 20 kA (1x) | |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 10 kA |
| 20 kA (in total) | |
| Nominal pulse current Ian (10/1000) µs (line-line) | 50 A |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 50 A |
| 100 A (in total) | |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 60 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 650 V |
| Residual voltage at In(line-line) | ≤ 70 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 50 V |
| Voltage protection level Up(line-line) | ≤ 70 V (C2 - 10 kV / 5 kA) |
| ≤ 50 V (C3 - 10 A) | |
| ≤ 55 V (C3 - 50 A) | |
| Voltage protection level Up(line-earth) | ≤ 650 V (C1 - 500 V / 250 A) |
| ≤ 700 V (C2 - 10 kV / 5 kA) | |
| ≤ 650 V (C3 - 10 A) | |
| ≤ 700 V (C3 - 50 A) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.7 dB (1 MHz / 50 Ω) |
| typ. 0.3 dB (350 kHz / 150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | typ. 6 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 2 MHz |
| Capacity | ≤ 1.3 nF (per channel) |
| Resistance in series | 3.3 Ω ±20 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 315 mA (T) |
| Impulse durability (line-line) | C2 - 10 kV/5 kA |
| C3 - 50 A | |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C3 - 50 A | |
| D1 - 500 A | |
| Alternating current carrying capacity (line-earth) | 5 A - 1 s |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
Standards and Regulations
| Standards/specifications | EN 61643-21 A2:2013 |
|---|---|
| EN 60079-0 2012 | |
| EN 60079-11 2012 | |
| EN 60079-26 2007 | |
| IEC 60079-0 2011 | |
| IEC 60079-11 2011 | |
| IEC 60079-26 2006 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |