The Phoenix Contact DT-UFB-IB-RBI is a specialized surge protection device designed to limit transient overvoltages and protect sensitive data transmission equipment. Such protective components are commonly integrated into industrial networking infrastructures and communication lines to prevent electrical disturbances from propagating through automation systems. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2800055
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 159 (C-4-2017)
- GTIN: 4046356462716
- Weight per Piece (excluding packing): 436.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 110 mm
- Width: 25 mm
- Depth: 63 mm
- Ambient temperature (operation): -40 °C ... 85 °C
- Degree of protection: IP20
- Housing material: Zinc die-cast
- Color: silver/black
- Standards for cearances and creepage distances: IEC 60664-1
More info
▲Key Commercial Data
| Orderkey | 2800055 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 159 (C-4-2017) |
| GTIN | 4046356462716 |
| Weight per Piece (excluding packing) | 436.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | Zinc die-cast |
|---|---|
| Color | silver/black |
| Standards for cearances and creepage distances | IEC 60664-1 |
| VDE 0110-1 | |
| Mounting type | Connection-specific attachment plug and DIN rail, 35 mm |
| Type | Attachment plug for DIN rail mounting |
| Number of positions | 5 |
| Direction of action | Line-Line & Line-Ground/Shield |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | B2 |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Maximum continuous voltage UC | 5.8 V DC |
| Rated current | ≤ 180 mA (25 °C) |
| Operating effective current ICat UC | ≤ 1 µA |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (line-line) | ≤ 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | ≤ 5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 15 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 15 V |
| Residual voltage at In(line-line) | ≤ 25 V |
| Residual voltage at In(line-earth) | ≤ 55 V |
| Residual voltage at In(line-signalground) | ≤ 25 V |
| Voltage protection level Up(line-line) | ≤ 16 V (B2 - 100 A) |
| ≤ 20 V (C1 - 500 A) | |
| ≤ 20 V (C2 - 1 kA) | |
| ≤ 60 V (C2 - 5 kA) | |
| Voltage protection level Up(line-earth) | ≤ 700 V (B2 - 100 A) |
| ≤ 700 V (C1 - 500 A) | |
| ≤ 700 V (C2 - 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 5 MHz / 150 Ω) |
| typ. 0.6 dB (≤ 10 MHz / 100/150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | ≥ 100 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | ≥ 100 MHz |
| Capacity (line-line) | typ. 20 pF |
| Resistance in series | typ. 7 Ω |
| Surge protection fault message | none |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| B2 - 4 kV/100 A | |
| Impulse durability (line-earth) | B2 - 4 kV/100 A |
| C1 - 1 kV/500 A | |
| C2 - 10 kV/5 kA | |
| D1 - 1 kA |
Connection data
| Connection method | D-SUB-9 |
|---|---|
| Connection method IN | D-SUB-9 plug |
| Connection method OUT | D-SUB-9 socket |
| Connection technology | Remote bus input |
Standards and Regulations
| Standards/regulations | IEC 61643-21 |
|---|---|
| DIN EN 61643-21 | |
| Standards/specifications | DIN EN 61643-21 2002 |
| IEC 61643-21 2000 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |