Request QuoteProduct Overview
Phoenix Contact DT-UFB-IB-RB0 surge protection device is engineered to protect industrial fieldbus networks and automation nodes from high-energy transient disturbances. By stabilizing line potentials, it ensures reliable data exchange across harsh factory floor environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2800056
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 159 (C-4-2017)
- GTIN: 4046356462723
- Weight per Piece (excluding packing): 436.000 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 110 mm
- Width: 25 mm
- Depth: 63 mm
- Ambient temperature (operation): -40 °C ... 85 °C
- Degree of protection: IP20
- Housing material: Zinc die-cast
- Color: silver/black
- Standards for cearances and creepage distances: IEC 60664-1
More info
▲Key Commercial Data
| Orderkey | 2800056 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 159 (C-4-2017) |
| GTIN | 4046356462723 |
| Weight per Piece (excluding packing) | 436.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | Zinc die-cast |
|---|---|
| Color | silver/black |
| Standards for cearances and creepage distances | IEC 60664-1 |
| VDE 0110-1 | |
| Mounting type | Connection-specific attachment plug and DIN rail, 35 mm |
| Type | Attachment plug for DIN rail mounting |
| Number of positions | 5 |
| Direction of action | Line-Line & Line-Ground/Shield |
Protective circuit
| IEC test classification | B2 |
|---|---|
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| VDE requirement class | B2 |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| Maximum continuous voltage UC | 5.8 V DC |
| Rated current | ≤ 180 mA (25 °C) |
| Operating effective current ICat UC | ≤ 1 µA |
| Residual current IPE | ≤ 5 µA |
| Nominal discharge current In(8/20) µs (line-line) | ≤ 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | ≤ 5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 15 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 700 V |
| Output voltage limitation at 1 kV/µs (line-signalground) static | ≤ 15 V |
| Residual voltage at In(line-line) | ≤ 25 V |
| Residual voltage at In(line-earth) | ≤ 55 V |
| Residual voltage at In(line-signalground) | ≤ 25 V |
| Voltage protection level Up(line-line) | ≤ 16 V (B2 - 100 A) |
| ≤ 20 V (C1 - 500 A) | |
| ≤ 60 V (C2 - 1 kA) | |
| ≤ 60 V (C2 - 5 kA) | |
| Voltage protection level Up(line-earth) | ≤ 700 V (B2 - 100 A) |
| ≤ 700 V (C1 - 500 A) | |
| ≤ 700 V (C2 - 5 kA) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.5 dB (≤ 5 MHz / 150 Ω) |
| typ. 0.6 dB (≤ 10 MHz / 100/150 Ω) | |
| Cut-off frequency fg (3 dB), sym. in 100 Ohm system | ≥ 100 MHz |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | ≥ 100 MHz |
| Capacity (line-line) | typ. 20 pF |
| Resistance in series | typ. 7 Ω |
| Surge protection fault message | none |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| B2 - 4 kV/100 A | |
| Impulse durability (line-earth) | B2 - 4 kV/100 A |
| C1 - 1 kV/500 A | |
| C2 - 10 kV/5 kA | |
| D1 - 1 kA |
Connection data
| Connection method | D-SUB-9 |
|---|---|
| Connection method IN | D-SUB-9 socket |
| Connection method OUT | D-SUB-9 connector |
| Connection technology | Remote bus output |
Standards and Regulations
| Standards/regulations | IEC 61643-21 |
|---|---|
| DIN EN 61643-21 | |
| Standards/specifications | DIN EN 61643-21 2002 |
| IEC 61643-21 2000 |