PHOENIX CONTACT DT-LAN-CAT.6+ DT-LAN-CAT.6+ 2881007 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

DT-LAN-CAT.6+ 2881007 PHOENIX CONTACT Surge protection device

DT-LAN-CAT.6+

2881007

PHOENIX CONTACT

1 Pcs.

Surge protection device Surge protection according to EA class (CAT6A), for Gigabit Ethernet (up to 10 GBit/s), Token Ring, FDDI/CDDI, ISDN, DS1. Suitable for Power over Ethernet (PoE++ / 4PPoE) "Mode A" and "Mode B". RJ45 intermediate connector with separate grounding conductor and grounding interlocking foot for NS 35 rail.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact DT-LAN-CAT.6+ surge protection device is engineered to protect Ethernet and network hardware up to Category 6 performance standards from transient surges. Network surge protectors are widely installed in commercial and industrial IT cabling infrastructures to prevent lightning-induced damage to active network switches. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2881007
  • Packing unit: 1 pc
  • Catalog page: Page 142 (C-4-2017)
  • GTIN: 4046356151900
  • Weight per Piece (excluding packing): 314.100 g
  • Custom tariff number: 85363010
  • Country of origin: DE (Germany)
  • Height: 102 mm
  • Width: 25 mm
  • Depth: 63.5 mm
  • Ambient temperature (operation): -40 °C ... 70 °C
  • Ambient temperature (storage/transport): -40 °C ... 70 °C
  • Degree of protection: IP20
  • Housing material: Zinc die-cast
  • Color: silver/black
  • Mounting type: Connection-specific attachment plug and DIN rail, 35 mm

More info

▲

Key Commercial Data

Orderkey2881007
Packing unit1 pc
Catalog pagePage 142 (C-4-2017)
GTIN4046356151900
Weight per Piece (excluding packing)314.100 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height102 mm
Width25 mm
Depth63.5 mm

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 70 °C
Degree of protectionIP20

General

Housing materialZinc die-cast
Colorsilver/black
Mounting typeConnection-specific attachment plug and DIN rail, 35 mm
TypeAttachment plug for DIN rail mounting
Number of positions8
Direction of actionLine-Line & Line-Ground/Shield

Protective circuit

IEC test classificationB2
C1
C2
C3
D1
Maximum continuous voltage UC(wire-wire)≤ 3.3 V DC (± 60 V DC/PoE+)
Rated current≤ 1.5 A (25 °C)
Operating effective current ICat UC≤ 1 µA
Residual current IPE≤ 400 µA
Nominal discharge current In(8/20) µs (line-line)100 A
Nominal discharge current In(8/20) µs (line-earth)2 kA (per signal pair)
Total discharge current Itotal(8/20) µs10 kA
Nominal pulse current Ian (10/700) µs (line-line)≤ 40 A
Nominal pulse current Ian (10/700) µs (line-earth)≤ 160 A
Output voltage limitation at 1 kV/µs (line-line) spike≤ 85 V (PoE)
Output voltage limitation at 1 kV/µs (line-earth) spike≤ 700 V
Output voltage limitation at 1 kV/µs (line-line) static≤ 9 V
Output voltage limitation at 1 kV/µs (line-earth) static≤ 700 V
Residual voltage at In(line-line)≤ 15 V
≤ 100 V (PoE)
Voltage protection level Up(line-line)≤ 9 V (B2 - 1 kV / 25 A)
≤ 100 V (B2 - 1 kV / 25 A - PoE)
≤ 12 V (C3 - 20 A)
Voltage protection level Up(line-earth)≤ 900 V (B2 - 4 kV / 100 A)
≤ 700 V (C2 - 4 kV / 2 kA)
≤ 1 kV (C3 - 80 A)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.≤ 1 dB (up to100 MHz/direct measuring)
≤ 1 dB (up to 250 MHz/direct measuring)
≤ 3 dB (up to 500 MHz/direct measuring)
Near-end crosstalk attenuation≥ 35 dB (250 MHz/100 Ω/link)
≥ 45 dB (100 MHz / 100 Ω / Link)
≥ 27 dB (500 MHz / 100 Ω / Link)
≥ 39 dB (250 MHz/100 Ω/direct measuring)
Capacity (line-line)typ. 12 pF (f= 1 MHz / VR= 0 V)
Capacity (line-earth)typ. 2 pF (f= 1 MHz / VR= 0 V)
Surge protection fault messagenone
Impulse durability (line-line)B2 - 1 kV / 25 A
C3 - 20 A
Impulse durability (line-earth)B2 - 4 kV/100 A
C2 - 4 kV/2 kA
C3 - 80 A
D1 - 1 kA

Connection data

Connection methodRJ45

Connection, equipotential bonding

Connection methodDIN rail NS35

Standards and Regulations

Standards/specificationsIEC 61643-21 2002
EN 50173-1 2002
ISO/IEC 11801-Am.1 2006

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet