View larger
CT 10-2PE/FSR-24 2807968 PHOENIX CONTACT Surge protection plug
CT 10-2PE/FSR-24
2807968
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for high-density signal distribution systems, the Phoenix Contact CT 10-2PE/FSR-24 2807968 PHOENIX CONTACT Surge protection plug diverts destructive electrical transients away from sensitive automation electronics. Industrial control engineers install specialized surge protection plugs within patch panels and marshalling racks to secure delicate communication networks.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 24 V
More info
▲Key Commercial Data
| Orderkey | 2807968 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 107 (C-6-2013) |
| GTIN | 4017918104757 |
| Weight per Piece (excluding packing) | 127.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V0 |
| Color | black |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Type | LSA-PLUS module |
| Direction of action | Line-Line & Line-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 40 V DC |
| 28 V AC | |
| Rated current | 200 mA (25 °C) |
| Operating effective current ICat UC | ≤ 5 µA (a-b) |
| Residual current IPE | ≤ 1 µA (per path) |
| Nominal discharge current In(8/20) µs (line-line) | 5 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 5 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 5 kA |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 95 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 650 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 60 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 650 V |
| Residual voltage at In(line-line) | ≤ 55 V |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | 1.5 dB (Typ. up to 2 MHz / 50 Ω) |
| 0.6 dB (Typ. up to 1 MHz / 150 Ω) | |
| 0.2 dB (Typ. up to 100 kHz / 600 Ω) | |
| Input attenuation aE, asym. | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | 7 MHz (typ.) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | 4 MHz (typ.) |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system | 900 kHz (typ.) |
| Capacity (line-line) | 1.1 nF (f=1 MHz / VR= 0 V) |
| Capacity (line-earth) | 1 pF (typ.) |
| Resistance in series | 10 Ω ±10 % |
| Surge protection fault message | none |
| Max. required back-up fuse | 200 mA |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C3 - 100 A | |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C3 - 100 A | |
| D1 - 2.5 kA |
Connection data
| Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
|---|---|
| Connection method IN | COMTRAB plug-in system |
| Connection method OUT | COMTRAB plug-in system |