The Phoenix Contact CT 10-2PE/FS-24 2807955 is a surge protection plug that provides dependable defense for sensitive signal wiring against transient overvoltages. Modular suppression elements like this are frequently deployed within industrial terminal strips to maintain uninterrupted communication across automated networks. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 24 V
More info
▲Key Commercial Data
| Orderkey | 2807955 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 106 (C-6-2013) |
| GTIN | 4017918104740 |
| Weight per Piece (excluding packing) | 125.150 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
General
| Housing material | PBT |
|---|---|
| Flammability rating according to UL 94 | V0 |
| Color | black |
| Standards for cearances and creepage distances | VDE 0110-1 |
| IEC 60664-1 | |
| Mounting type | On CT-TERMIBLOCK and LSA-PLUS disconnect strip |
| Type | LSA-PLUS module |
| Direction of action | Line-Line & Line-Earth Ground |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.00 |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 40 V DC |
| 28 V AC | |
| Nominal current IN | 1.5 A (75 °C) |
| Operating effective current ICat UC | ≤ 5 µA (a-b) |
| Residual current IPE | ≤ 1 µA (per path) |
| Nominal discharge current In(8/20) µs (line-line) | 119 A (25 °C) |
| Nominal discharge current In(8/20) µs (line-earth) | 5 kA |
| Total surge current (8/20) µs | 10 kA |
| Max. discharge current Imax(8/20) µs maximum (line-line) | 119 A (25 °C) |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 5 kA |
| Nominal pulse current Ian (10/1000) µs (line-line) | 23 A (25 °C) |
| Output voltage limitation at 1 kV/µs (line-line) spike | ≤ 70 V |
| Output voltage limitation at 1 kV/µs (line-earth) spike | ≤ 650 V |
| Output voltage limitation at 1 kV/µs (line-line) static | ≤ 60 V |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 650 V |
| Residual voltage at In(line-line) | ≤ 85 V |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 65 V |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | 0.1 dB (Typ. up to 2 MHz / 50 Ω) |
| 0.1 dB (Typ. up to 1 MHz / 150 Ω) | |
| 0.1 dB (Typ. up to 400 kHz / 600 Ω) | |
| Input attenuation aE, asym. | |
| Cut-off frequency fg (3 dB), sym. in 50 Ohm system | 10 MHz (typ.) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | 4 MHz (typ.) |
| Cut-off frequency fg (3 dB), sym. in 600 Ohm system | 1 MHz (typ.) |
| Capacity (line-line) | 1.1 nF (f=1 MHz / VR= 0 V) |
| Capacity (line-earth) | 1 pF |
| Resistance in series | |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C3 - 100 A | |
| D1 - 2.5 kA |
Connection data
| Connection method | can be plugged into COMTRAB-TERMIBLOCK and LSA-PLUS disconnect and switching strips |
|---|---|
| Connection method IN | COMTRAB plug-in system |
| Connection method OUT | COMTRAB plug-in system |