View larger
CSMA-LAMBDA/4-2.0-BS-SET 2800491 PHOENIX CONTACT Surge protection device
CSMA-LAMBDA/4-2.0-BS-SET
2800491
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact CSMA-LAMBDA/4-2.0-BS-SET surge protection device is designed to protect coaxial signal paths, antenna feeds, and high-frequency communication lines from high-energy surges and lightning strikes. These specialized components preserve signal integrity while diverting harmful electrical transients safely to ground. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2800491
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 179 (C-4-2017)
- GTIN: 4046356556149
- Weight per Piece (excluding packing): 300.450 g
- Custom tariff number: 85366910
- Country of origin: DE (Germany)
- Height: 25 mm
- Width: 46.5 mm
- Depth: 70 mm
- Ambient temperature (operation): -40 °C ... 70 °C
- Ambient temperature (storage/transport): -40 °C ... 70 °C
- Degree of protection: IP55
- Housing material: HPb59-1
- Color: nickel
More info
▲Key Commercial Data
| Orderkey | 2800491 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 179 (C-4-2017) |
| GTIN | 4046356556149 |
| Weight per Piece (excluding packing) | 300.450 g |
| Custom tariff number | 85366910 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Degree of protection | IP55 |
General
| Housing material | HPb59-1 |
|---|---|
| Color | nickel |
| Mounting type | Connection-specific intermediate plugging |
| Type | Attachment plug |
| Number of positions | 2 |
| Direction of action | Line-Shield/Earth Ground |
Protective circuit
| IEC test classification | C2 |
|---|---|
| C3 | |
| D1 | |
| VDE requirement class | C2 |
| C3 | |
| D1 | |
| Rated current | 2 A (25 °C) |
| Nominal discharge current In(8/20) µs (line-earth) | 6 kA |
| Nominal discharge current In(8/20) µs (line-shield) | 6 kA |
| Total discharge current Itotal(8/20) µs | 6 kA |
| Max. discharge current Imax(8/20) µs | 6 kA |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 1 V |
| Output voltage limitation at 1 kV/µs (line-shield) static | ≤ 1 V |
| Residual voltage at In(line-earth) | ≤ 20 V |
| Residual voltage at In(line-shield) | ≤ 20 V |
| Voltage protection level Up(line-earth) | ≤ 5 V (C1 - 1 kV/500 A) |
| ≤ 25 V (C2 - 10 kV / 5 kA) | |
| ≤ 15 V (6 kV / 3 kA) | |
| Input attenuation aE, asym. | typ. 1 dB (0.8 GHz ... 2.25 GHz) |
| Frequency range | 0.8 GHz ... 2.25 GHz |
| Standing wave ratio SWR in a 50 Ω system | ≤ 1.2 (0.8 GHz ... 2.25 GHz) |
| ≤ 1.1 (1.7 GHz ... 2.1 GHz) | |
| Permissible HF power Pmaxat VSWR = xx (50 ohm system) | ≤ 110 W (VSWR = 1.0) |
| Surge protection fault message | none |
| Impulse durability (line-earth) | C2 - 10 kV/5 kA |
| D1 - 1 kA | |
| Impulse durability (line-shield) | C2 - 10 kV/5 kA |
| D1 - 1 kA |
Connection data
| Connection method | SMA connector |
|---|---|
| Connection method IN | SMA connector, female connector |
| Connection method OUT | SMA connector, male connector |
Standards and Regulations
| Standards/regulations | IEC 61643-21 |
|---|---|
| Standards/specifications | IEC 61643-21/A1 2008 |
| EN 61643-21/A1 2009 |