The Phoenix Contact PT-IQ-3-PB-PT is an advanced surge protection device engineered to safeguard sensitive PROFIBUS and communication networks from damaging electrical transients. Modern control systems incorporate dedicated data line surge suppressors to maintain data integrity and prevent communication dropouts in harsh industrial environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 5 V
More info
▲Key Commercial Data
| Orderkey | 2801286 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 153 (C-4-2017) |
| GTIN | 4046356766678 |
| Weight per Piece (excluding packing) | 109.700 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Transmission speed | 90 Mpbs |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 5 V DC |
| Maximum continuous voltage UC | 6 V DC |
| 4 V AC | |
| Rated current | 600 mA (40 °C) |
| Operating effective current ICat UC | ≤ 800 µA (per path) |
| Residual current IPE | ≤ 800 µA (per path) |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-line) | 2.5 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Voltage protection level Up(line-line) | ≤ 90 V (C1 - 1 kV/500 A) |
| ≤ 140 V (C2 - 10 kV / 5 kA) | |
| ≤ 30 V (C3 - 25 A) | |
| ≤ 30 V (C3 - 50 A) | |
| Voltage protection level Up(line-earth) | ≤ 90 V (C1 - 1 kV/500 A) |
| ≤ 140 V (C2 - 10 kV / 5 kA) | |
| ≤ 30 V (C3 - 25 A) | |
| ≤ 30 V (C3 - 50 A) | |
| Voltage protection level Upstatic (line-line) | ≤ 45 V (C1 - 1 kV/500 A) |
| Voltage protection level Upstatic (line-earth) | ≤ 45 V (C1 - 1 kV/500 A) |
| Response time tA (line-signalground) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 60 MHz |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system | typ. 60 MHz |
| Capacity (line-line) | typ. 30 pF |
| Capacity (line-signalground) | typ. 30 pF |
| Resistance in series | 1.2 Ω ±5 % |
| Surge protection fault message | Optical, multi-stage |
| Max. required back-up fuse | 600 mA (FF) |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C3 - 50 A | |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C3 - 50 A | |
| D1 - 2.5 kA | |
| Pulse reset time (line-line) | ≤ 10 ms |
| Pulse reset time (line-earth) | ≤ 10 ms |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 10 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + A1:2008 + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 | |
| EN 61000-6-2 2007 + A1:2011 | |
| EN 61000-6-3 2005 |