View larger
PT-IQ-4X1-48DC-UT 2801219 PHOENIX CONTACT Surge protection device
PT-IQ-4X1-48DC-UT
2801219
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PT-IQ-4X1-48DC-UT 2801219 is a surge protection device engineered to shield multi-channel signal loops against lightning-induced surges and switching overvoltages. Facilities rely on these advanced protective modules to prevent catastrophic failures in critical measurement and control equipment. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 48 V
More info
▲Key Commercial Data
| Orderkey | 2801219 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 111 (C-4-2017) |
| GTIN | 4046356745093 |
| Weight per Piece (excluding packing) | 125.900 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Additional descriptions
| Note | Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector. |
|---|
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 48 V DC |
| Maximum continuous voltage UC | 53 V DC |
| 37 V AC | |
| Rated current | 300 mA |
| Operating effective current ICat UC | ≤ 6 µA (per path) |
| Residual current IPE | ≤ 6 µA (per path) |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Voltage protection level Up(line-earth) | ≤ 105 V (C1 - 1 kV/500 A) |
| ≤ 160 V (C2 - 10 kV / 5 kA) | |
| ≤ 90 V (C3 - 25 A) | |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 530 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system | typ. 1.9 MHz |
| Capacity (line-signalground) | typ. 1.5 nF |
| Resistance in series | 1.2 Ω ±5 % |
| Surge protection fault message | Optical, multi-stage |
| Max. required back-up fuse | 315 mA (FF) |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 25 A | |
| D1 - 2.5 kA | |
| Pulse reset time (line-earth) | ≤ 1500 ms |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + A1:2008, modified |
|---|---|
| EN 61643-21 2001 + A1:2009 | |
| EN 61000-6-3 2007 + A1:2011 | |
| EN 61000-6-2 2005 |