PHOENIX CONTACT PT-IQ-1X2-48DC-PT PT-IQ-1X2-48DC-PT 2801257 PHOENIX CONTACT Surge protection device View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PT-IQ-1X2-48DC-PT 2801257 PHOENIX CONTACT Surge protection device

PT-IQ-1X2-48DC-PT

2801257

PHOENIX CONTACT

1 Pcs.

Surge protection device Surge protection, consisting of plug-in protection and base element, with multi-level diagnostic and status indication integrated into a module for a circ. of 2-wire signal free of potential.

Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact PT-IQ-1X2-48DC-PT 2801257 is a surge protection device built to safeguard industrial data and signal circuits from high-energy electrical disturbances. These units are commonly installed in control cabinets to ensure continuous protection and real-time status monitoring for sensitive automation assets. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Nominal voltage DC (EF008799): 48 V

More info

▲

Key Commercial Data

Orderkey2801257
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 96 (C-4-2017)
GTIN4046356766401
Weight per Piece (excluding packing)110.000 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height109.3 mm
Width17.7 mm
Depth77.5 mm (incl. DIN rail 7.5 mm)
Horizontal pitch1 Div.

Ambient conditions

Ambient temperature (operation)-40 °C ... 70 °C
Ambient temperature (storage/transport)-40 °C ... 85 °C
Altitude≤ 4000 m (amsl (above mean sea level))
Degree of protectionIP20

General

Housing materialPA 6.6
Flammability rating according to UL 94V-0
Colorjet black RAL 9005
Mounting typeDIN rail: 35 mm
TypeDIN rail module, two-section, divisible
Direction of actionLine-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground

Additional descriptions

NoteRemote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector.

Protective circuit

IEC test classificationC1
C2
C3
D1
Nominal voltage UN48 V DC
Maximum continuous voltage UC53 V DC
37 V AC
Rated current300 mA
Operating effective current ICat UC≤ 5 µA (in the signal circuit)
Residual current IPE≤ 2 µA (per signal circuit)
Nominal discharge current In(8/20) µs (line-line)10 kA
Nominal discharge current In(8/20) µs (line-earth)10 kA
Pulse discharge current Iimp(10/350) µs (line-earth)2.5 kA
Total discharge current Itotal(8/20) µs20 kA
Voltage protection level Up(line-line)≤ 100 V (C1 - 1 kV/500 A)
≤ 150 V (C2 - 10 kV / 5 kA)
≤ 90 V (C3 - 25 A)
≤ 95 V (C3 - 100 A)
Voltage protection level Up(line-earth)≤ 600 V (C1 - 1 kV/500 A)
≤ 750 V (C2 - 10 kV / 5 kA)
≤ 700 V (C3 - 25 A)
≤ 800 V (C3 - 100 A)
Voltage protection level Upstatic (line-earth)≤ 60 V (C2 - 10 kV / 5 kA)
≤ 40 V (C3 - 25 A)
≤ 100 V (C3 - 100 A)
Response time tA(line-line)≤ 1 ns
Response time tA(line-earth)≤ 100 ns
Input attenuation aE, sym.typ. 0.3 dB (≤ 450 kHz/150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ohm systemtyp. 1.9 MHz
Capacity (line-line)typ. 1.5 nF
Resistance in series1.2 Ω ±5 %
Surge protection fault messageOptical, multi-stage
Max. required back-up fuse315 mA (FF)
Impulse durability (line-line)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C2 - 10 kA
C3 - 100 A
Impulse durability (line-earth)C1 - 1 kV/500 A
C2 - 10 kV/5 kA
C2 - 10 kA
C3 - 100 A
D1 - 2.5 kA
Pulse reset time (line-line)≤ 300 ms
Pulse reset time (line-earth)≤ 4000 ms

Connection data

Connection methodPush-in connection
Stripping length10 mm
Conductor cross section flexible0.2 mm² ... 2.5 mm²
Conductor cross section solid0.2 mm² ... 4 mm²
Conductor cross section AWG24 ... 12

Connection, equipotential bonding

Connection methodDIN rail NS35

Standards and Regulations

Standards/specificationsIEC 61643-21 2000 + A1:2008 + A2:2012
EN 61643-21 2001 + A1:2009 + A2:2013
EN 61000-6-2 2005
EN 61000-6-3 2007 + A1:2011

Classifications


Product Datasheet