PT-IQ-5-HF-12DC-PT 2801293 PHOENIX CONTACT Surge protection device
PT-IQ-5-HF-12DC-PT
2801293
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PT-IQ-5-HF-12DC-PT 2801293 is a surge protection device configured to mitigate transient electrical disturbances in high-frequency data and signal applications. Facilities rely on this protective technology to maintain data integrity and prevent hardware damage in automated industrial environments. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 12 V
More info
▲Key Commercial Data
| Orderkey | 2801293 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 146 (C-4-2017) |
| GTIN | 4046356766746 |
| Weight per Piece (excluding packing) | 121.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Standards for cearances and creepage distances | IEC 60664-1 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Transmission speed | 90 Mpbs |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 12 V DC |
| Maximum continuous voltage UC | 15 V DC |
| 10 V AC | |
| Rated current | 600 mA (40 °C) |
| Operating effective current ICat UC | ≤ 100 µA (per path) |
| Residual current IPE | ≤ 100 µA (per path) |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Voltage protection level Up(line-line) | ≤ 90 V (C1 - 1 kV/500 A) |
| ≤ 40 V (C3 - 25 A) | |
| ≤ 40 V (C3 - 50 A) | |
| ≤ 145 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Up(line-earth) | ≤ 90 V (C1 - 1 kV/500 A) |
| ≤ 145 V (C2 - 10 kV / 5 kA) | |
| ≤ 40 V (C3 - 25 A) | |
| ≤ 40 V (C3 - 50 A) | |
| Voltage protection level Upstatic (line-line) | ≤ 55 V (C1 - 1 kV/500 A) |
| Voltage protection level Upstatic (line-earth) | ≤ 55 V (C1 - 1 kV/500 A) |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 1 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 60 MHz |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system | typ. 60 MHz |
| Capacity (line-line) | typ. 30 pF |
| Capacity (line-signalground) | typ. 30 pF |
| Resistance in series | 1.2 Ω ±5 % |
| Surge protection fault message | Optical, multi-stage |
| Max. required back-up fuse | 600 mA (FF) |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 25 A | |
| C3 - 50 A | |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 25 A | |
| C3 - 50 A | |
| D1 - 2.5 kA | |
| Impulse durability (line-signalground) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 25 A | |
| C3 - 50 A | |
| Pulse reset time (line-line) | ≤ 15 ms |
| Pulse reset time (line-signalground) | ≤ 15 ms |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 10 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + A1:2008 + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 | |
| EN 61000-6-2 2005 | |
| EN 61000-6-3 2007 + A1:2011 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |