View larger
PT-IQ-5-HF+F-12DC-PT 2801295 PHOENIX CONTACT Surge protection device
PT-IQ-5-HF+F-12DC-PT
2801295
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Offering advanced defense for automated systems, this PT-IQ-5-HF+F-12DC-PT 2801295 PHOENIX CONTACT surge protection device protects sensitive electronic hardware from destructive power surges. These sophisticated suppression units are widely deployed in modern industrial control architectures to ensure uninterrupted signal processing and high system availability.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage AC (EF008798): 12 V
More info
▲Key Commercial Data
| Orderkey | 2801295 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 147 (C-4-2017) |
| GTIN | 4046356766753 |
| Weight per Piece (excluding packing) | 122.000 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Transmission speed | 90 Mpbs |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 12 V DC |
| Maximum continuous voltage UC | 15 V DC |
| 10 V AC | |
| Rated current | 600 mA (40 °C) |
| Operating effective current ICat UC | ≤ 100 µA (per path) |
| Residual current IPE | ≤ 10 µA (per path) |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Nominal discharge current In(8/20) µs (core-signal ground) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Voltage protection level Up(line-line) | ≤ 90 V (C1 - 1 kV/500 A) |
| ≤ 40 V (C3 - 25 A) | |
| ≤ 40 V (C3 - 50 A) | |
| ≤ 145 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Up(line-earth) | ≤ 730 V (C1 - 1 kV/500 A) |
| ≤ 900 V (C2 - 10 kV / 5 kA) | |
| ≤ 900 V (C3 - 25 A) | |
| ≤ 900 V (C3 - 50 A) | |
| Voltage protection level Up(line-signalground) | ≤ 90 V (C1 - 1 kV/500 A) |
| ≤ 40 V (C3 - 25 A) | |
| ≤ 40 V (C3 - 50 A) | |
| ≤ 145 V (C2 - 10 kV / 5 kA) | |
| Voltage protection level Upstatic (line-line) | ≤ 55 V (C1 - 1 kV/500 A) |
| Voltage protection level Upstatic (line-signalground) | ≤ 55 V (C1 - 1 kV/500 A) |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA (line-signalground) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 10 MHz/150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 60 MHz |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system | typ. 60 MHz |
| Capacity (line-line) | typ. 30 pF |
| Capacity (line-signalground) | typ. 30 pF |
| Resistance in series | 1.2 Ω ±5 % |
| Surge protection fault message | Optical, multi-stage |
| Max. required back-up fuse | 600 mA (FF) |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 25 A | |
| C3 - 50 A | |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 25 A | |
| C3 - 50 A | |
| D1 - 2.5 kA | |
| Impulse durability (line-signalground) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 25 A | |
| C3 - 50 A | |
| Pulse reset time (line-line) | ≤ 15 ms |
| Pulse reset time (line-earth) | ≤ 15 ms |
| Pulse reset time (line-signalground) | ≤ 15 ms |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 10 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + A1:2008 + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 | |
| EN 61000-6-2 2005 | |
| EN 61000-6-3 2007 + A1:2011 |