The Phoenix Contact PT-IQ-2X1+F-24DC-PT surge protection device offers advanced transient voltage defense with integrated signal monitoring capabilities. Such devices are standard in industrial automation systems requiring continuous circuit protection. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 24 V
More info
▲Key Commercial Data
| Orderkey | 2801248 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 111 (C-4-2017) |
| GTIN | 4046356766319 |
| Weight per Piece (excluding packing) | 111.300 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | jet black RAL 9005 |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Additional descriptions
| Note | Remote signaling as well as the power supply of the DIN rail connector are established by snapping the module into place on the DIN rail connector. |
|---|
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 1000 mA (40 °C) |
| Operating effective current ICat UC | ≤ 1 mA (per path) |
| Residual current IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Nominal discharge current In(8/20) µs (core-signal ground) | 10 kA |
| Pulse discharge current Iimp(10/350) µs (line-earth) | 2.5 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Voltage protection level Up(line-earth) | ≤ 800 V (C1 - 1 kV/500 A) |
| ≤ 950 V (C2 - 10 kV / 5 kA) | |
| ≤ 780 V (C3 - 25 A) | |
| ≤ 950 V (C3 - 50 A) | |
| Voltage protection level Up(line-signalground) | ≤ 75 V (C1 - 1 kV/500 A) |
| ≤ 135 V (C2 - 10 kV / 5 kA) | |
| ≤ 55 V (C3 - 25 A) | |
| ≤ 60 V (C3 - 50 A) | |
| Voltage protection level Upstatic (line-earth) | ≤ 90 V (C3 - 25 A) |
| ≤ 90 V (C3 - 50 A) | |
| Response time tA (line-signalground) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, asym. | typ. 0.3 dB (≤ 300 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), asym. (GND) in 150 Ohm system | typ. 1.1 MHz |
| Capacity (line-signalground) | typ. 2 nF |
| Resistance in series | 1.2 Ω ±5 % |
| Surge protection fault message | Optical, multi-stage |
| Max. required back-up fuse | 1 A (FF) |
| Impulse durability (line-earth) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 50 A | |
| D1 - 2.5 kA | |
| Impulse durability (line-signalground) | C1 - 1 kV/500 A |
| C2 - 10 kV/5 kA | |
| C2 - 10 kA | |
| C3 - 50 A | |
| D1 - 2,5 kA | |
| Pulse reset time (line-earth) | ≤ 30 ms |
| Pulse reset time (line-signalground) | ≤ 350 ms |
Connection data
| Connection method | Push-in connection |
|---|---|
| Stripping length | 10 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | IEC 61643-21 2000 + A1:2008 + A2:2012 |
|---|---|
| EN 61643-21 2001 + A1:2009 + A2:2013 | |
| EN 61000-6-3 2007 + A1:2011 | |
| EN 61000-6-2 2005 |