View larger
PT-IQ-1X2-EX-24DC-UT 2801512 PHOENIX CONTACT Surge protection device
PT-IQ-1X2-EX-24DC-UT
2801512
PHOENIX CONTACT
1 Pcs.
Automation > Combined arrester for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact surge protection device (part number PT-IQ-1X2-EX-24DC-UT) offers advanced, multi-stage overvoltage protection with continuous condition monitoring for industrial signal cables. These modular surge arresters are deployed in control cabinets to protect sensitive I/O cards from damaging voltage spikes. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2801512
- Packing unit: 1 pc
- Catalog page: Page 129 (C-4-2017)
- GTIN: 4046356801225
- Weight per Piece (excluding packing): 107.400 g
- Custom tariff number: 85363010
- Country of origin: DE (Germany)
- Height: 91.1 mm
- Width: 17.7 mm
- Depth: 77.5 mm (incl. DIN rail 7.5 mm)
- Horizontal pitch: 1 Div.
- Ambient temperature (operation): -40 °C ... 70 °C
- Ambient temperature (storage/transport): -40 °C ... 85 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
- Degree of protection: IP20
- Housing material: PA 6.6
More info
▲Key Commercial Data
| Orderkey | 2801512 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 129 (C-4-2017) |
| GTIN | 4046356801225 |
| Weight per Piece (excluding packing) | 107.400 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 70 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Degree of protection | IP20 |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Direction of action | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 24 V DC |
| Maximum continuous voltage UC | 30 V DC |
| 21 V AC | |
| Rated current | 350 mA |
| Operating effective current ICat UC | ≤ 5 µA (per system) |
| Residual current IPE | ≤ 100 nA (per system) |
| Nominal discharge current In(8/20) µs (line-line) | 10 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 10 kA |
| Pulse discharge current Iimp(10/350) µs | 2 kA |
| Total discharge current Itotal(8/20) µs | 20 kA |
| Voltage protection level Up(line-line) | ≤ 60 V (C1 - 1 kV/500 A) |
| ≤ 110 V (C2 - 10 kV / 5 kA) | |
| ≤ 140 V (C2 - 10 kA) | |
| ≤ 50 V (C3 - 25 A) | |
| ≤ 55 V (C3 - 100 A) | |
| Voltage protection level Up(line-earth) | ≤ 1.3 kV (C2 - 10 kV / 5 kA) |
| ≤ 1.5 kV (C2 - 10 kA) | |
| ≤ 1.3 kV (C3 - 100 A) | |
| Response time tA(line-line) | ≤ 1 ns |
| Response time tA(line-earth) | ≤ 100 ns |
| Input attenuation aE, sym. | typ. 0.3 dB (≤ 300 kHz / 150 Ω) |
| Cut-off frequency fg (3 dB), sym. in 150 Ohm system | typ. 1.1 MHz |
| Capacity (line-earth) | typ. 2 nF |
| Resistance in series | 1.2 Ω ±5 % |
| Surge protection fault message | Optical, multi-stage |
| Max. required back-up fuse | 350 mA (F) |
| Impulse durability (line-line) | C1 - 1 kV/500 A |
| C2 - 10 kA | |
| C3 - 100 A | |
| Impulse durability (line-earth) | C2 - 10 kA |
| D1 - 2 kA | |
| Pulse reset time (line-line) | ≤ 30 ms |
| Pulse reset time (line-earth) | ≤ 30 ms |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M3 |
| Tightening torque | 0.5 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Standards and Regulations
| Standards/specifications | EN 61643-21/A2 2013 |
|---|---|
| IEC 61643-21/A2 2012 | |
| EN 61000-6-2 2005 | |
| EN 61000-6-3 A1:2011 |
General
| Maximum inner capacitance Ci | negligible |
|---|---|
| Max. internal inductance Li | negligible |
| Max. input current Ii | 350 mA |
| Max. input voltage Ui | 30 V DC |
| max. input power Pi | 1.2 W |
| Insulation voltage to ground | > 500 V AC |
| Standards/specifications | EN 60079-0 2012 |
| EN 60079-11 2012 | |
| EN 60079-15 2010 | |
| IEC 60079-0 2012 | |
| IEC 60079-11 2012 | |
| IEC 60079-15 2010 | |
| Ambient temperature (operation) | -40 °C ... 50 °C (T6) |
| -40 °C ... 70 °C (T4) |