View larger
VAL-MS 75 VF ST 2805318 PHOENIX CONTACT Type 2 surge protection plug
VAL-MS 75 VF ST
2805318
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact VAL-MS 75 VF ST Type 2 surge protection plug provides robust defense for industrial power architectures by limiting transient voltage surges across electrical networks. These modular protective elements install easily into dedicated base assemblies to safeguard sensitive downstream controllers and machinery from electrical disruptions. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 2805318
- Packing unit: 10 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 62 (C-4-2017)
- GTIN: 4046356430869
- Weight per Piece (excluding packing): 31.520 g
- Custom tariff number: 85363030
- Country of origin: DE (Germany)
- Height: 52.4 mm
- Width: 17.5 mm
- Depth: 55.3 mm
- Horizontal pitch: 1 Div.
- Degree of protection: IP20
- Ambient temperature (operation): -40 °C ... 80 °C
- Ambient temperature (storage/transport): -40 °C ... 80 °C
- Altitude: ≤ 2000 m (amsl (above mean sea level))
More info
▲Key Commercial Data
| Orderkey | 2805318 |
|---|---|
| Packing unit | 10 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 62 (C-4-2017) |
| GTIN | 4046356430869 |
| Weight per Piece (excluding packing) | 31.520 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g |
| Vibration (operation) | 5g |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| Mode of protection | L-PE |
| L-L | |
| Mounting type | on base element |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 1 |
| Surge protection fault message | optical |
Additional descriptions
| Note | The values specified for the L-L protective path are only valid in connection with VAL-MS/2+0-BE/FM/S2 |
|---|
Protective circuit
| Nominal voltage UN | 5 V AC ... 48 V AC |
|---|---|
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 75 V AC |
| 100 V DC | |
| Residual current IPE | ≤ 5 µA |
| Standby power consumption PC | ≤ 1 mVA |
| Nominal discharge current In(8/20) µs | 10 kA |
| Maximum discharge current Imax(8/20) µs | 20 kA |
| Short-circuit current rating ISCCR | 10 kA |
| Voltage protection level Up | ≤ 1.4 kV |
| Voltage protection level Up(L-L) | ≤ 1.8 kV |
| Residual voltage Ures | ≤ 0.45 kV (at In) |
| ≤ 0.35 kV (at 5 kA) | |
| ≤ 0.3 kV (at 3 kA) | |
| Residual voltage Ures(L-L) | ≤ 0.9 kV (at In) |
| ≤ 0.7 kV (at 5 kA) | |
| ≤ 0.6 kV (at 3 kA) | |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.4 kV |
| Response time tA | ≤ 100 ns |
| Max. backup fuse with branch wiring | 63 A (gG) |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-N) | 75 V AC |
| Maximum continuous operating voltage MCOV (L+) - (L-) | 100 V DC |
| Nom. voltage | 48 V AC |
| Nominal voltage | 60 V DC |
| Mode of protection | L-N |
| (L+) - (L-) | |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 1760 V |
| Measured limiting voltage MLV (L+) - (L-) | 1760 V |
| Nominal discharge current In(L-N) | 10 kA |
| Nominal discharge current In(L+) - (L-) | 10 kA |