VAL-MS 230 ST 2798844 PHOENIX CONTACT Type 2 surge protection plug modules offer dependable secondary defense against voltage spikes within standard low-voltage power distribution networks. Industrial electrical systems integrate these replaceable plug elements to protect machinery and control instruments from switching overvoltages. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: Replacement plug
- Product family: VALVETRAB MS
- IEC test classification: II
- EN type: T2
- IEC power supply system: TN
- Type: DIN rail module, two-section, divisible
- Number of positions: 1
- Surge protection fault message: optical
- Data management status Article revision: 27
- Insulation characteristics Overvoltage category: III
- Pollution degree: 2
- Nominal frequency f N: 50 Hz (60 Hz)
- Connection method: pluggable
- Width: 17.5 mm
- Height: 52.4 mm
- Depth: 55.3 mm
More info
▲| Product type | Replacement plug |
| Product family | VALVETRAB MS |
| IEC test classification | II |
| T2 | |
| EN type | T2 |
| IEC power supply system | TN |
| TT | |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 1 |
| Surge protection fault message | optical |
| Arrester can be tested with CHECKMASTER from software version: | From SW rev. 1.10 |
| Data management status | |
| Article revision | 27 |
| Insulation characteristics | |
| Overvoltage category | III |
| Pollution degree | 2 |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Connection method | pluggable |
| Dimensional drawing | |
| Width | 17.5 mm |
| Height | 52.4 mm |
| Depth | 55.3 mm |
| Horizontal pitch | 1 Div. |
| Color | black (RAL 9005) |
| Flammability rating according to UL 94 | V-0 |
| CTI value of material | 600 |
| Insulating material | PA 6.6 |
| Material group | I |
| Housing material | PA 6.6 |
| Mode of protection | L-N |
| L-PEN | |
| Direction of action | 1L-N/PE |
| Nominal voltage UN | 240/415 V AC (TN) |
| 240/415 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 275 V AC |
| Residual current IPE | ≤ 0.45 mA |
| Standby power consumption PC | ≤ 120 mVA |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 1.35 kV |
| Residual voltage Ures | ≤ 1.35 kV (at In) |
| ≤ 1.1 kV (at 10 kA) | |
| ≤ 1 kV (at 5 kA) | |
| ≤ 0.9 kV (at 3 kA) | |
| TOV behavior at UT | 335 V AC (5 s / withstand mode) |
| 440 V AC (120 min / safe failure mode) | |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with branch wiring | 125 A (gG) |
| Ambient conditions | |
| Degree of protection | IP20 |
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
| UL specifications | |
| Maximum continuous operating voltage MCOV (L-N) | 275 V AC |
| Nominal discharge current In(L-N) | 20 kA |
| Mode of protection | L-N |
| Nominal voltage | 230 V AC |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 1910 V |
| SPD Type | 4CA |
| Standards/specifications | IEC 61643-11 |
| Note | 2011 |
| Standards/specifications | EN 61643-11 |
| Note | 2012 |