View larger
F-MS 12 2817987 PHOENIX CONTACT Type 2 surge arrester
F-MS 12
2817987
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Built to divert high-energy electrical impulses, the F-MS 12 2817987 PHOENIX CONTACT Type 2 surge arrester delivers dependable overvoltage protection for industrial power networks. Surge arresters of this classification are critical for preventing electrical faults from damaging sensitive automation assets. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- System configuration DC (EF009926): No
- System configuration IT (EF009927): No
- System configuration TN (EF009928): Yes
- System configuration TN-C (EF009929): No
- System configuration TN-C-S (EF009933): No
- System configuration TN-S (EF009930): No
- System configuration TT (EF009931): No
- System configuration other (EF009932): No
- Nominal discharge surge current (8/20) (EF004214): 20 kA
- Max. discharge surge current (8/20) (EF012274): 40 kA
- Max. continuous voltage AC (EF004198): 260 V
- Voltage protection level L-N (EF004236): 1.5 kV
- Integrated backup fuse (EF008797): Yes
- Leakage-current free (EF016002): No
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
- Signalling at the device (EF004241): Optic
More info
▲Key Commercial Data
| Orderkey | 2817987 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 55 (C-4-2017) |
| GTIN | 4017918163662 |
| Weight per Piece (excluding packing) | 106.100 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN |
| TT | |
| Mode of protection | N-PE |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| PBT | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 1 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 240/415 V AC (TN - only N-PE) |
|---|---|
| 240/415 V AC (TT - only N-PE) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 260 V AC |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 5 µA |
| Standby power consumption PC | ≤ 1.5 mVA |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Follow current interrupt rating Ifi | 100 A |
| Voltage protection level Up | ≤ 1.5 kV |
| Residual voltage Ures | ≤ 0.4 kV (at In) |
| ≤ 0.25 kV (at 10 kA) | |
| ≤ 0.15 kV (at 5 kA) | |
| ≤ 0.1 kV (at 3 kA) | |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
| TOV behavior at UT | 1200 V AC (200 ms / withstand mode) |
| Response time tA | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 80 A (gG) |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 3 Nm (1,5 mm² ... 16 mm²) |
| 4.5 Nm (25 mm² ... 35 mm²) | |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 16 mm² |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (N-G) | 260 V AC |
| Mode of protection | N-G |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (N-G) | 1490 V |
| Nominal discharge current In(N-G) | 20 kA |