View larger
VAL-MS 385/80/1+1-FM 2921284 PHOENIX CONTACT Type 2 surge arrester
VAL-MS 385/80/1+1-FM
2921284
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Built by Phoenix Contact under part number 2921284, this type 2 surge arrester acts as a robust defense mechanism against indirect lightning strikes and switching overvoltages in electrical distribution networks. Surge protective devices of this class are standard additions to industrial switchboards to ensure continuous plant operation and safeguard connected electronics.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- System configuration DC: No
- System configuration IT: No
- System configuration TN: No
- System configuration TN-C: No
- System configuration TN-C-S: No
- System configuration TN-S: No
- System configuration TT: Yes
- System configuration other: No
- Nominal discharge surge current (8/20): 40 kA
- Max. discharge surge current (8/20): 80 kA
- Max. continuous voltage AC: 385 V
- Voltage protection level: 2 kV
- Voltage protection level L-N: 2 kV
- Voltage protection level N-PE: 1.7 kV
- Short-circuit breaking capacity (Isccr): 25 kA
- Integrated backup fuse: Yes
More info
▲Key Commercial Data
| Orderkey | 2921284 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 49 (C-6-2013) |
| GTIN | 4046356280006 |
| Weight per Piece (excluding packing) | 330.900 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TT |
| TN-C | |
| TN-S | |
| Mode of protection | L-N |
| L-PE | |
| N-PE | |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| PBT | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 240 V AC (TN-S) |
|---|---|
| 240 V AC (TT) | |
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous operating voltage UC(L-N) | 385 V AC |
| Maximum continuous voltage UC(N-PE) | 264 V AC |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 5 µA |
| Standby power consumption PC | ≤ 231 mVA |
| Nominal discharge current In(8/20) µs | 40 kA |
| Maximum discharge current Imax(8/20) µs | 80 kA |
| Impulse discharge current (10/350) µs (L-N), charge | 1.25 As |
| Impulse discharge current (10/350) µs (L-N), specific energy | 1.56 kJ/Ω |
| Impulse discharge current (10/350) µs (L-N), peak current value Iimp | 2.5 kA |
| Impulse discharge current (10/350) µs (L-PE), charge | 1.25 As |
| Impulse discharge current (10/350) µs (L-PE), specific energy | 1.56 kJ/Ω |
| Impulse discharge current (10/350) µs (L-PE), peak current value Iimp | 2.5 kA |
| Impulse discharge current (10/350) µs (N-PE), charge | 5 As |
| Impulse discharge current (10/350) µs (N-PE), specific energy | 25 kJ/Ω |
| Impulse discharge current (10/350) µs (N-PE), peak current value Iimp | 10 kA |
| Total discharge current Itotal(8/20) µs | 80 kA |
| Total discharge current Itotal(10/350) µs | 5 kA |
| Follow current interrupt rating Ifi(N-PE) | 100 A |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up(L-N) | ≤ 2 kV |
| Voltage protection level Up(L-PE) | ≤ 2 kV |
| Voltage protection level Up(N-PE) | ≤ 1.7 kV |
| Residual voltage Ures(L-N) | ≤ 2 kV (at In) |
| ≤ 1.3 kV (at 10 kA) | |
| ≤ 1.2 kV (at 5 kA) | |
| ≤ 1.15 kV (at 3 kA) | |
| Residual voltage Ures(L-PE) | ≤ 2 kV (at In) |
| ≤ 1.5 kV (at 10 kA) | |
| ≤ 1.4 kV (at 5 kA) | |
| ≤ 1.3 kV (at 3 kA) | |
| Residual voltage Ures(N-PE) | ≤ 0.6 kV (at In) |
| ≤ 0.5 kV (at 10 kA) | |
| ≤ 0.5 kV (at 5 kA) | |
| ≤ 0.4 kV (at 3 kA) | |
| TOV behavior at UT(L-N) | 480 V AC (5 s / withstand mode) |
| 457 V AC (120 min / withstand mode) | |
| TOV behavior at UT(N-PE) | 1200 V AC (200 ms / withstand mode) |
| Response time tA(L-N) | ≤ 25 ns |
| Response time tA(L-PE) | ≤ 100 ns |
| Response time tA(N-PE) | ≤ 100 ns |
| Max. backup fuse with V-type through wiring | 80 A (gG - 16 mm²) |
| Max. backup fuse with branch wiring | 250 A (gG) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC |
| 30 V DC | |
| Operating current | 5 mA AC ... 1.5 A AC |
| 1 A DC | |
| Connection method | Plug-in/screw connection via COMBICON |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 3 Nm (1,5 mm² ... 16 mm²) |
| 4.5 Nm (25 mm² ... 35 mm²) | |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 16 mm² |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-N) | 385 V AC |
| Maximum continuous operating voltage MCOV (L-G) | 385 V AC |
| Maximum continuous operating voltage MCOV (N-G) | 264 V AC |
| Nom. voltage | 240 V AC |
| Mode of protection | L-N |
| L-G | |
| N-G | |
| Power distribution system | Single phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-N) | 2710 V |
| Measured limiting voltage MLV (L-G) | 3730 V |
| Measured limiting voltage MLV (N-G) | 2590 V |
| Nominal discharge current In(L-N) | 20 kA |
| Nominal discharge current In(L-G) | 20 kA |
| Nominal discharge current In(N-G) | 20 kA |
UL indicator/remote signaling
| Operating voltage | 125 V AC |
|---|---|
| Operating current | 1 A AC |
| Tightening torque | 4 lbf-in. |
| Conductor cross section AWG | 30 ... 14 |