View larger
VAL-MS 230/2+0-FM 2800102 PHOENIX CONTACT Type 2 surge arrester
VAL-MS 230/2+0-FM
2800102
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Safeguard critical automation components from unexpected electrical surges using the VAL-MS 230/2+0-FM 2800102 PHOENIX CONTACT Type 2 surge arrester. Surge suppression modules are universally deployed in low-voltage distribution switchboards to divert destructive transient voltage spikes to ground. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- System configuration DC (EF009926): No
- System configuration IT (EF009927): No
- System configuration TN (EF009928): No
- System configuration TN-C (EF009929): Yes
- System configuration TN-C-S (EF009933): No
- System configuration TN-S (EF009930): No
- System configuration TT (EF009931): No
- System configuration other (EF009932): No
- Nominal discharge surge current (8/20) (EF004214): 20 kA
- Max. discharge surge current (8/20) (EF012274): 40 kA
- Max. continuous voltage AC (EF004198): 275 V
- Voltage protection level L-N (EF004236): 1.35 kV
- Short-circuit breaking capacity (Isccr) (EF012627): 25 kA
- Integrated backup fuse (EF008797): Yes
- Leakage-current free (EF016002): No
- Mounting method (EF000003): DIN rail (top hat rail) 35 mm
More info
▲Key Commercial Data
| Orderkey | 2800102 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 41 (C-6-2015) |
| GTIN | 4046356499675 |
| Weight per Piece (excluding packing) | 257.500 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 (only when all terminal points are used) |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 2000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
| Shock (operation) | 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) |
| Vibration (operation) | 5g (10 ... 500 Hz / 2.5 h / X, Y, Z) |
General
| IEC test classification | II |
|---|---|
| T2 | |
| EN type | T2 |
| IEC power supply system | TN-C |
| Mode of protection | L-PEN |
| Mounting type | DIN rail: 35 mm |
| Color | jet black RAL 9005 |
| Housing material | PA 6.6 |
| PBT | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | DIN rail module, two-section, divisible |
| Surge protection fault message | Optical, remote indicator contact |
Protective circuit
| Nominal voltage UN | 240/415 V AC (TN-C) |
|---|---|
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 275 V AC |
| Rated load current IL | 80 A |
| Residual current IPE | ≤ 0.9 mA |
| Standby power consumption PC | ≤ 240 mVA |
| Nominal discharge current In(8/20) µs | 20 kA |
| Maximum discharge current Imax(8/20) µs | 40 kA |
| Short-circuit current rating ISCCR | 25 kA |
| Voltage protection level Up | ≤ 1.35 kV |
| Residual voltage Ures | ≤ 1.35 kV (at In) |
| ≤ 1.1 kV (at 10 kA) | |
| ≤ 1 kV (at 5 kA) | |
| ≤ 0.9 kV (at 3 kA) | |
| TOV behavior at UT | 335 V AC (5 s / withstand mode) |
| Response time tA | ≤ 25 ns |
| Max. backup fuse with V-type through wiring | 80 A (gG) |
| Max. backup fuse with branch wiring | 125 A (gG) |
Indicator/remote signaling
| Switching function | PDT contact |
|---|---|
| Operating voltage | 5 V AC ... 250 V AC |
| 30 V DC | |
| Operating current | 5 mA AC ... 1.5 A AC |
| 1 A DC | |
| Connection method | Plug-in/screw connection via COMBICON |
| Screw thread | M2 |
| Tightening torque | 0.25 Nm |
| Stripping length | 7 mm |
| Conductor cross section flexible | 0.14 mm² ... 1.5 mm² |
| Conductor cross section solid | 0.14 mm² ... 1.5 mm² |
| Conductor cross section AWG | 28 ... 16 |
Connection data
| Connection method | Screw connection |
|---|---|
| Screw thread | M5 |
| Tightening torque | 3 Nm (1,5 mm² ... 16 mm²) |
| 4.5 Nm (25 mm² ... 35 mm²) | |
| Stripping length | 16 mm |
| Conductor cross section flexible | 1.5 mm² ... 25 mm² |
| Conductor cross section solid | 1.5 mm² ... 35 mm² |
| Conductor cross section AWG | 15 ... 2 |
| Connection method | Fork-type cable lug |
| Conductor cross section flexible | 1.5 mm² ... 16 mm² |
UL specifications
| SPD Type | 4CA |
|---|---|
| Maximum continuous operating voltage MCOV (L-L) | 550 V AC |
| Maximum continuous operating voltage MCOV (L-N) | 275 V AC |
| Nom. voltage | 230 V AC |
| Mode of protection | L-L |
| L-N | |
| Power distribution system | Split phase |
| Nominal frequency | 50/60 Hz |
| Measured limiting voltage MLV (L-L) | 2720 V |
| Measured limiting voltage MLV (L-N) | 1910 V |
| Nominal discharge current In(L-L) | 20 kA |
| Nominal discharge current In(L-N) | 20 kA |
UL indicator/remote signaling
| Operating voltage | 125 V AC |
|---|---|
| Operating current | 1 A AC |
| Tightening torque | 4 lbf-in. |
| Conductor cross section AWG | 30 ... 14 |