PHOENIX CONTACT VAL-MS 1000DC-PV/2+V VAL-MS 1000DC-PV/2+V 2800628 PHOENIX CONTACT Surge arrester for 2-pos. isolated 1000 V DC voltage systems, f.. View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-MS 1000DC-PV/2+V 2800628 PHOENIX CONTACT Surge arrester for 2-pos. isolated 1000 V DC voltage systems, f..

VAL-MS 1000DC-PV/2+V

2800628

PHOENIX CONTACT

1 Pcs.

Surge arrester for 2-pos. isolated 1000 V DC voltage systems, for DIN rail mounting, 3-pos. base element, three plug-in temperature-monitored protective elements, status message on each plug. Surge protection device for isolated and grounded 2-pole photovoltaic 1000 V DC direct current systems, for rail mounting, 3-pole base element, three plug-in protection elements with temperature control, status message on each male connector.

Automation > Surge protection device for power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Phoenix Contact VAL-MS 1000DC-PV/2+V surge arresters are specialized components engineered to protect isolated direct current photovoltaic power generation systems from atmospheric surges. These units absorb voltage spikes inherent in large-scale solar power infrastructures to safeguard inverters and arrays.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • System configuration DC (EF009926): Yes
  • System configuration IT (EF009927): No
  • Category type 2 (EF004230): Yes

More info

▲

Dimensions

Height90 mm
Width53.4 mm
Depth65.5 mm
Horizontal pitch3 Div.

Ambient conditions

Degree of protectionIP20 (only when all terminal points are used)
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)60g (Half sine/11 ms/3x XYZ)
Vibration (operation)7.5g (5-500 Hz/2.5 h/XYZ)

General

Standards/specificationsEN 50539-11 2013
IEC test classificationPV T2
PV T2
Number of portsOne
SPD failure behaviorOCM (Open-circuit mode)
Connection configurationY configuration
SPD designVoltage-limiting type
Installation locationInside
AccessibilityAccessible
Installation location of the disconnect deviceInternal
Mounting typeDIN rail: 35 mm
Colorjet black RAL 9005
Housing materialPA 6.6-FR
PBT-FR
Pollution degree2
Distance between live and grounded parts8 mm
Flammability rating according to UL 94V-0
TypeDIN rail module, two-section, divisible
Surge protection fault messageoptical

Additional descriptions

NoteThe device is intended for touch proof installation in a housing. Ensure that there is a gap of at least 8 mm between the active and grounded parts in the connection area.

Protective circuit DC voltage side (DC)

Maximum continuous operating voltage UCPV1170 V DC
Open circuit voltage UOCSTC≤ 970 V DC
Short-circuit current rating ISCPV1000 A
Continuous operating current ICPV< 20 µA
Rated load current IL80 A
Residual current IPE≤ 20 µA DC
≤ 250 µA AC
Standby power consumption PC≤ 25 mVA
Nominal discharge current In(8/20) µs (L+) - (L-)15 kA
Nominal discharge current In(8/20) µs (L+) - PE15 kA
Nominal discharge current In(8/20) µs (L-) - PE15 kA
Maximum discharge current Imax(8/20) µs (L+) - (L-)40 kA
Maximum discharge current Imax(8/20) µs (L+) - PE40 kA
Maximum discharge current Imax(8/20) µs (L-) - PE40 kA
Total discharge current ITotal(8/20) µs40 kA
Voltage protection level Up(L+) - (L-)≤ 3.7 kV
Voltage protection level Up(L+) - PE≤ 3.7 kV
Voltage protection level Up(L-) - PE≤ 3.7 kV
Residual voltage Ures(L+) - (L-)≤ 3.7 kV (at In)
≤ 3.1 kV (at 5 kA)
≤ 3.5 kV (at 10 kA)
≤ 4 kV (at 20 kA)
≤ 4.6 kV (at 30 kA)
≤ 5 kV (at 40 kA)
Residual voltage Ures(L+) - PE≤ 3.7 kV (at In)
≤ 3.1 kV (at 5 kA)
≤ 3.5 kV (at 10 kA)
≤ 4 kV (at 20 kA)
≤ 4.6 kV (at 30 kA)
≤ 5 kV (at 40 kA)
Residual voltage Ures(L-) - PE≤ 3.7 kV (at In)
≤ 3.1 kV (at 5 kA)
≤ 3.5 kV (at 10 kA)
≤ 4 kV (at 20 kA)
≤ 4.6 kV (at 30 kA)
≤ 5 kV (at 40 kA)
Response time tA(L+) - (L-)≤ 25 ns
Response time tA(L+) - PE≤ 25 ns
Response time tA(L-) -PE≤ 25 ns
Insulation resistance Riso> 5 GΩ (at 500 V DC)

Connection data

Connection methodScrew connection
Conductor cross section flexible min.1.5 mm²
Conductor cross section flexible max.25 mm²
Conductor cross section solid min.1.5 mm²
Conductor cross section solid max.35 mm²
Conductor cross section AWG15 ... 2
10 ... 2 (UL)
Screw threadM5
Tightening torque4.5 Nm
30 lbf-in. (UL)
Stripping length16 mm
Connection methodBiconnect terminal blocks
Conductor cross section flexible min.1.5 mm²
Conductor cross section flexible max.16 mm²
Screw threadM5

UL specifications

SPD Type4 (for Type 2 photovoltaic applications)
Maximum continuous operating voltage MCOV (L+) - (L-)1170 V DC
Maximum continuous operating voltage MCOV (L+) - G1170 V DC
Maximum continuous operating voltage MCOV (L-) - G1170 V DC
Nom. voltage970 V AC
Mode of protection(L+) - (L-)
(L+) - G
(L-) - G
Power distribution system1
Voltage protection rating VPR (L+) - (L-)2.5 kV
Voltage protection rating VPR (L+) - G2.5 kV
Voltage protection rating VPR (L-) -G2.5 kV
Nominal discharge current In(L+) - (L-)10 kA
Nominal discharge current In(L+) - G10 kA
Nominal discharge current In(L-) - G10 kA

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.