View larger
PT 2X1-VF-230AC 2805460 PHOENIX CONTACT Surge protection device
PT 2X1-VF-230AC
2805460
PHOENIX CONTACT
1 Pcs.
Automation > Surge protection device for data networks/MCR-technology
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Designed for industrial installations, the Phoenix Contact PT 2X1-VF-230AC surge protection device provides critical defense against electrical disturbances, transient overvoltages, and line-conducted interference. These units are typically integrated into power distribution loops to protect sensitive downstream loads from premature failure.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Nominal voltage DC (EF008799): 230 V
More info
▲Key Commercial Data
| Orderkey | 2805460 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 114 (C-4-2017) |
| GTIN | 4046356460989 |
| Weight per Piece (excluding packing) | 71.780 g |
| Custom tariff number | 85363010 |
| Country of origin | DE (Germany) |
Dimensions
| Height | 44.8 mm |
|---|---|
| Width | 17.5 mm |
| Depth | 51.7 mm |
| Horizontal pitch | 1 Div. |
| Complete module height | 90 mm |
| Complete module width | 17.7 mm |
| Complete module depth | 65.5 mm |
General
| Housing material | PA 6.6 |
|---|---|
| Flammability rating according to UL 94 | V-0 |
| Color | black |
| Mounting type | DIN rail: 35 mm |
| Type | DIN rail module, two-section, divisible |
| Number of positions | 2 |
| Direction of action | Line-Line & Line-Earth Ground |
Protective circuit
| IEC test classification | C1 |
|---|---|
| C2 | |
| C3 | |
| D1 | |
| Nominal voltage UN | 230 V AC |
| Maximum continuous voltage UC | 250 V AC |
| Rated current | 6 A |
| Operating effective current ICat UC | ≤ 2 µA |
| Residual current IPE | ≤ 2 µA (at UN) |
| Nominal discharge current In(8/20) µs | 3 kA |
| Nominal discharge current In(8/20) µs (line-earth) | 3 kA |
| Pulse discharge current Iimp(10/350) µs | 500 A |
| Total discharge current Itotal(8/20) µs | 8 kA |
| Total discharge current Itotal(10/350) µs | 1 kA |
| Max. discharge current Imax(8/20) µs | 8 kA |
| Max. discharge current Imax(8/20) µs maximum (line-earth) | 8 kA |
| Nominal pulse current Ian (10/1000) µs (line-earth) | 100 A |
| Output voltage limitation at 1 kV/µs (line-earth) static | ≤ 1.4 kV |
| Residual voltage at In(line-line) | ≤ 2 kV |
| Residual voltage at In(line-earth) | ≤ 1 kV |
| Residual voltage with Ian (10/1000) µs (line-line) | ≤ 1.4 kV |
| Residual voltage with Ian (10/1000) µs (line-earth) | ≤ 700 V |
| Energy absorption | 150 J |
| Voltage protection level Up(line-line) | ≤ 2.5 kV (C2 - 4 kV / 2 kA) |
| ≤ 1.8 kV (C3 - 100 A) | |
| ≤ 2.6 kV (D1 - 500 A) | |
| Voltage protection level Up(line-earth) | ≤ 1.1 kV (C1 - 500 A) |
| ≤ 1.5 kV (C2 - 4 kV / 2 kA) | |
| ≤ 1.6 kV (C3 - 100 A) | |
| ≤ 1.8 kV (D1 - 500 A) | |
| Response time tA | ≤ 100 ns |
| Capacity (line-line) | typ. 4.5 pF |
| Capacity (line-earth) | typ. 9 pF |
| Resistance in series | 0 Ω |
| Surge protection fault message | optical |
| Max. required back-up fuse | 6 A (gL / gG) |
| Impulse durability (line-earth) | C2 - 4 kV/2 kA |
| C3 - 100 A | |
| D1 - 500 A |
Connection data
| Connection method | Screw connection |
|---|---|
| Connection method IN | Screw terminal blocks |
| Connection method OUT | Screw terminal blocks |
| Screw thread | M3 |
| Tightening torque | 0.8 Nm |
| Stripping length | 8 mm |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section solid | 0.2 mm² ... 4 mm² |
| Conductor cross section AWG | 24 ... 12 |
Remote indication contact
| Switching function | N/C contact |
|---|---|
| Maximum operating voltage Umax.AC | 250 V AC |
| Max. operating current Imax | 1 A |
Standards and Regulations
| Standards/regulations | DIN EN 61643-21 |
|---|---|
| Standards/specifications | DIN EN 61643-21 2002 |