View larger
SOL-SC-2ST-0-DC-6MPPT-1000EQSE 1318523 PHOENIX CONTACT String box for photovoltaic installations up to 1000 ..
SOL-SC-2ST-0-DC-6MPPT-1000EQSE
1318523
PHOENIX CONTACT
1 Pcs.
Automation > Photovoltaic DC Stringbox
Industry Solutions (IS)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
SOL-SC-2ST-0-DC-6MPPT-1000EQSE 1318523 PHOENIX CONTACT String box for photovoltaic installations up to 1000 assemblies safely consolidate multiple DC string inputs from solar arrays while providing essential overvoltage protection. These robust industrial junction boxes ensure structured cable management and safeguard system integrity against environmental electrical disturbances. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Product type: String combiner box (SCB)
- Insulation characteristics Protection class: II
- General MPP voltage U N: max. 1000 V DC
- Non-load voltage U OC: max. 1100 V DC
- Current per string I max: max. 20 A
- Total current MPP tracker: max. 40 A
- Surge protection EN type: T1
- IEC test classification: T1
- Protection level U p: ≤ 3.5 kV
- Total discharge current I total (10/350) µs: 5 kA
- Total discharge current I total (8/20) µs: 40 kA
- Short-circuit current rating I SCPV: 40 A
- Number of inputs: Strings: 2 (per MPP tracker)
- Number of supported MPP trackers: 6
- DC Number of outputs: MPP tracker: 6
- Number of outputs: ±: 2 (per MPP tracker)
More info
▲| Product type | String combiner box (SCB) |
| Insulation characteristics | |
| Protection class | II |
| General | |
| MPP voltage UN | max. 1000 V DC |
| Non-load voltage UOC | max. 1100 V DC |
| Current per string Imax | max. 20 A |
| Total current MPP tracker | max. 40 A |
| Surge protection | |
| EN type | T1 |
| IEC test classification | T1 |
| Protection level Up | ≤ 3.5 kV |
| Total discharge current Itotal(10/350) µs | 5 kA |
| Total discharge current Itotal(8/20) µs | 40 kA |
| Short-circuit current rating ISCPV | 40 A |
| Number of inputs: Strings | 2 (per MPP tracker) |
| Number of supported MPP trackers | 6 |
| DC | |
| Number of outputs: MPP tracker | 6 |
| Number of outputs: ± | 2 (per MPP tracker) |
| DC input | |
| Type of cable entry | Cable gland |
| Connection method | Push-in connection |
| Cable cross section | 4 mm² ... 6 mm² |
| External cable diameter | 5 mm ... 7 mm |
| Protective bonding and protective grounding conductor | |
| Type of cable entry | Cable gland |
| Connection method | Push-in connection |
| Cable cross section | 2x 16 mm² |
| External cable diameter | 2x 6 mm ... 13 mm |
| DC output | |
| Type of cable entry | Cable gland |
| Connection method | Push-in connection |
| Cable cross section | 4 mm² ... 6 mm² |
| External cable diameter | 5 mm ... 7 mm |
| Housing | |
| Width | 400 mm |
| Height | 400 mm |
| Depth | 200 mm |
| Material Housing | Polyester fiberglass reinforced |
| Material Cover/door | Polyester fiberglass reinforced |
| Ambient conditions | |
| Degree of protection | IP65 |
| Ambient temperature (operation) | -20 °C ... 50 °C |
| Standard designation | Low-voltage switchgear and controlgear assemblies - Part 2: Power switchgear and controlgear assemblies |
| Standards/specifications | EN 61439-2 |