View larger
UGSK/S 0305080 PHOENIX CONTACT Slide-type terminal block
UGSK/S
0305080
PHOENIX CONTACT
50 Pcs.
Automation > Feed-through terminal block
Modular TBs
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact UGSK/S slide-type terminal block provides specialized disconnection functionality for measurement and testing circuits in industrial control panels. Technicians rely on slide disconnect terminals to safely isolate specific signal paths during routine diagnostic procedures without rewiring.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 0305080
- Packing unit: 50 pc
- Catalog page: Page 481 (C-1-2017)
- GTIN: 4017918000745
- Weight per Piece (excluding packing): 26.080 g
- Custom tariff number: 85369010
- Country of origin: DE (Germany)
- Number of levels: 1
- Number of connections: 2
- Nominal cross section: 6 mm²
- Color: gray
- Insulating material: PA
- Flammability rating according to UL 94: V2
- Rated surge voltage: 6 kV
- Degree of pollution: 3
- Overvoltage category: III
More info
▲Key Commercial Data
| Orderkey | 0305080 |
|---|---|
| Packing unit | 50 pc |
| Catalog page | Page 481 (C-1-2017) |
| GTIN | 4017918000745 |
| Weight per Piece (excluding packing) | 26.080 g |
| Custom tariff number | 85369010 |
| Country of origin | DE (Germany) |
General
| Number of levels | 1 |
|---|---|
| Number of connections | 2 |
| Nominal cross section | 6 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V2 |
| Rated surge voltage | 6 kV |
| Degree of pollution | 3 |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 1.31 W |
| Connection in acc. with standard | IEC 60947-7-1 |
| Nominal current IN | 41 A |
| Maximum load current | 57 A (with 10 mm² conductor cross section) |
| Nominal voltage UN | 500 V |
| Open side panel | Yes |
| Shock protection test specification | IEC 60529:2001-02 |
| Back of the hand protection | guaranteed |
| Finger protection | guaranteed |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 7.3 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 1.89 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of bending test | Test passed |
| Bending test rotation speed | 10 rpm |
| Bending test turns | 135 |
| Bending test conductor cross section/weight | 0.5 mm² / 0.3 kg |
| 6 mm2/ 1.4 kg | |
| 10 mm² / 2 kg | |
| Tensile test result | Test passed |
| Conductor cross section tensile test | 0.5 mm² |
| Tractive force setpoint | 20 N |
| Conductor cross section tensile test | 6 mm² |
| Tractive force setpoint | 80 N |
| Conductor cross section tensile test | 10 mm² |
| Tractive force setpoint | 90 N |
| Result of tight fit on support | Test passed |
| Tight fit on carrier | NS 32/NS 35 |
| Setpoint | 5 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 3.2 mV |
| Temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 6 mm² |
| Short-time current | 0.72 kA |
| Conductor cross section short circuit testing | 10 mm² |
| Short-time current | 1.2 kA |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Relative insulation material temperature index (Elec., UL 746 B) | 125 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Static insulating material application in cold | -40 °C |
Connection data
| Conductor cross section solid min. | 0.5 mm² |
|---|---|
| Conductor cross section solid max. | 10 mm² |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 6 mm² |
| Conductor cross section AWG min. | 20 |
| Conductor cross section AWG max. | 8 |
| Conductor cross section flexible, with ferrule without plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule without plastic sleeve max. | 6 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve min. | 0.5 mm² |
| Conductor cross section flexible, with ferrule with plastic sleeve max. | 4 mm² |
| 2 conductors with same cross section, solid min. | 0.5 mm² |
| 2 conductors with same cross section, solid max. | 1.5 mm² |
| 2 conductors with same cross section, stranded min. | 0.5 mm² |
| 2 conductors with same cross section, stranded max. | 4 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, ferrules without plastic sleeve, max. | 4 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, min. | 0.5 mm² |
| 2 conductors with same cross section, stranded, TWIN ferrules with plastic sleeve, max. | 4 mm² |
| Connection method | Screw connection |
| Stripping length | 11 mm |
| Screw thread | M4 |
| Tightening torque, min | 1.5 Nm |
| Tightening torque max | 1.8 Nm |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| IEC 60947-7-1 | |
| Flammability rating according to UL 94 | V2 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |