View larger
PLC-SC-EIK 1-SVN 24P/P 2982663 PHOENIX CONTACT Solid-state relay module
PLC-SC-EIK 1-SVN 24P/P
2982663
PHOENIX CONTACT
1 Pcs.
Automation > Optocoupler
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The Phoenix Contact PLC-SC-EIK 1-SVN 24P/P 2982663 PHOENIX CONTACT Solid-state relay module functions as a solid-state relay module designed for fast, wear-free switching of control signals in industrial automation systems. This category of component interfaces low-power controller outputs with higher-load field devices, providing galvanic isolation and reliable logic-level translation without mechanical wear. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Input voltage (EF003840): 19.2 V
- Type of voltage (input voltage) (EF003033): DC
- Rated operation current Ie (EF001443): 0.05 A
- Type of digital output (EF003601): Electronic
- With LED indication (EF005950): Yes
More info
▲Key Commercial Data
| Orderkey | 2982663 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 420 (C-5-2017) |
| GTIN | 4046356147330 |
| Weight per Piece (excluding packing) | 35.540 g |
| Custom tariff number | 85364190 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -25 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Degree of protection | IP20 |
Input data
| Designation | Device supply |
|---|---|
| Nominal input voltage UN | 24 V DC |
| Input voltage range in reference to UN | 0.8 ... 1.2 |
| Input voltage range | 19.2 V DC ... 28.8 V DC |
| Typical input current at UN | approx. 14 mA |
| Max. current consumption | approx. 70 mA (at 50 mA output current) |
| Operating voltage display | Green LED |
| Type of protection | Reverse polarity protection |
| Surge protection | |
| Protective circuit/component | Polarity protection diode |
| Suppressor diode | |
| Designation | Control circuit |
| Nominal input voltage UN | 8.2 V DC ±10 % |
| Type of protection | Surge protection |
| Protective circuit/component | Suppressor diode |
| Non-load voltage | 8.2 V DC ±10 % |
| Switching point | ≥ 2.1 mA (In conductive state) |
| ≤ 1.2 mA (In blocking state) | |
| 6.3 mA ... 10 mA (in the event of a short-circuit) | |
| 0 mA ... 0.35 mA (In the event of a wire break) | |
| Switching hysteresis | approx. 0.2 mA |
| Internal resistance | approx. 1 kΩ |
| Cable length | < 30 m |
| Power dissipation for nominal condition | 0.34 W |
Output data
| Designation | Signal output |
|---|---|
| Output nominal voltage | ≤ 100 mV (In conductive state) |
| UVN- UR;in blocking state | |
| Limiting continuous current | 50 mA |
| Transmission frequency | approx. 350 Hz |
| Voltage drop at max. limiting continuous current | ≤ 1.5 V (UR) |
| Status display | Green LED |
| Indication | Red LED |
| Type of protection | Surge protection |
| Protective circuit/component | Suppressor diode |
| Designation | Alarm output |
| Output nominal voltage | UVN- URes |
| Limiting continuous current | 50 mA |
| Voltage drop at max. limiting continuous current | ≤ 2 V (URest) |
| Indication | Red LED |
| Type of protection | Surge protection |
| Protective circuit/component | Suppressor diode |
Connection data 1
| Connection name | Input side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 12 |
Connection data 2
| Connection name | Output side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Conductor cross section solid | 0.14 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.14 mm² ... 2.5 mm² |
| Conductor cross section AWG | 26 ... 12 |
General
| Mounting position | any |
|---|---|
| Assembly instructions | In rows with zero spacing |
| Operating mode | 100% operating factor |
| Flammability rating according to UL 94 | V0 |
| Designation | Air clearances and creepage distances |
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Degree of pollution | 2 |
| Overvoltage category | I |
Standards and Regulations
| Designation | Air clearances and creepage distances |
|---|---|
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Rated insulation voltage | 50 V DC |
| Rated surge voltage | 0.4 kV |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | I |
| Flammability rating according to UL 94 | V0 |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |