PACT RCP-4000A-UIRO-PT-D140 2906235 PHOENIX CONTACT Current transformer
PACT RCP-4000A-UIRO-PT-D140
2906235
PHOENIX CONTACT
1 Pcs.
Automation > Current transformer
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
The PACT RCP-4000A-UIRO-PT-D140 2906235 Phoenix Contact current transformer utilizes flexible coil technology to measure AC currents in space-constrained installations. Such transducers provide adjustable output signals to integrate seamlessly into existing control system architectures. Technical specifications and ordering data are shown below.
- Orderkey: 2906235
- Packing unit: 1 pc
- Note: Made to Order (non-returnable)
- Catalog page: Page 237 (C-5-2017)
- GTIN: 4055626048338
- Weight per Piece (excluding packing): 398.700 g
- Custom tariff number: 85437090
- Country of origin: DE (Germany)
- Nominal supply voltage: 24 V DC
- Nominal supply voltage range: 9.6 V DC ... 30 V DC
- Power consumption: ≤ 1 W (at I OUT = 20 mA, 9.6 V DC, 600 Ω load)
- Frequency measuring range: 40 Hz ... 20000 Hz
- Position error: < 1 %
- Linearity error: 0.1 %
- Measuring ranges (current): 100 A 250 A 400 A 630 A 1000 A 1500 A 2000 A 4000 A
- Configurable/programmable: Via DIP switches
Specific pricing, availability and lead time are confirmed per enquiry through an RFQ.
More info
▲Key Commercial Data
| Orderkey | 2906235 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 237 (C-5-2017) |
| GTIN | 4055626048338 |
| Weight per Piece (excluding packing) | 398.700 g |
| Custom tariff number | 85437090 |
| Country of origin | DE (Germany) |
Measuring transducer supply
| Nominal supply voltage | 24 V DC |
|---|---|
| Nominal supply voltage range | 9.6 V DC ... 30 V DC |
| Power consumption | ≤ 1 W (at IOUT= 20 mA, 9.6 V DC, 600 Ω load) |
Measuring coil input data
| Frequency measuring range | 40 Hz ... 20000 Hz |
|---|---|
| Position error | < 1 % |
| Linearity error | 0.1 % |
Measuring transducer input data
| Measuring ranges (current) | 100 A 250 A 400 A 630 A 1000 A 1500 A 2000 A 4000 A |
|---|---|
| Configurable/programmable | Via DIP switches |
Measuring coil signal output
| Output signal (at 50 Hz) | 100 mV (no load, at 1,000 A) |
|---|---|
| Output voltage (in no-load operation) | VOUT= M * dI/dt |
| Output voltage (sinusoidal, in no-load operation) | 100 mV (VOUT= 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A)) |
Measuring transducer signal output
| Current output signal | 0 mA ... 20 mA (via DIP switch) |
|---|---|
| 4 mA ... 20 mA (via DIP switch) | |
| 0 mA ... 10 mA (via DIP switch) | |
| 2 mA ... 10 mA (via DIP switch) | |
| 0 mA ... 21 mA (can be set via software) | |
| Voltage output signal | 0 V ... 10 V (via DIP switch) |
| 2 V ... 10 V (via DIP switch) | |
| 0 V ... 5 V (via DIP switch) | |
| 1 V ... 5 V (via DIP switch) | |
| 0 V ... 10.5 V (can be set via software) | |
| Load/output load current output | ≤ 600 Ω (20 mA) |
General data, measuring coil
| Length of measuring coil | 450 mm |
|---|---|
| Diameter of measuring coil | 8.3 mm ±0.2 mm |
| Length of signal cable | 3000 mm |
| Conductor structure signal line | 2x 0.22 mm (Signal (tinned)) |
| 1x 0.22 mm (Shielding (tinned)) | |
| Coil material | Elastollan |
| Housing material | PC |
| Insulation | double insulation |
| Rated insulation voltage | 1000 V AC (rms CAT III) |
| 600 V AC (rms CAT IV) | |
| Test voltage | 10.45 kV (DC / 1 min.) |
| Basic accuracy | |
| UL, USA/Canada | UL 61010 Recognized |
General data for measuring transducer
| Maximum transmission error | ≤ 0.5 % (From the range end value) |
|---|---|
| Frequency range | 16 Hz ... 1000 Hz |
| Housing material | PBT |
| Test voltage | 3 kV (50 Hz, 1 min.) |
| UL, USA/Canada | UL 508 Listed |
General data
| Standards/regulations | IEC 61010-1 |
|---|---|
| IEC 61010-2-032 | |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Typical measuring error | < 1 % |
Connection data
| Connection name | Measuring transducer side |
|---|---|
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Connection method | Push-in connection |
| Stripping length | 10 mm |
Ambient conditions
| Ambient temperature (operation) | -30 °C ... 80 °C (Measuring coil) |
|---|---|
| -40 °C ... 70 °C (Measuring transducer) | |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C (Measuring coil) |
| -40 °C ... 85 °C (Measuring transducer) | |
| Maximum altitude | > 4000 m |
| Measuring coil degree of protection | IP67 (not assessed by UL) |
| Measuring transducer degree of protection | IP20 |
Standards and Regulations
| Electromagnetic compatibility | Conformance with EMC Directive 2004/108/EC |
|---|---|
| Noise emission | EN 61000-6-4 |
| Standards/regulations | IEC 61010-1 |
| IEC 61010-2-032 | |
| Rated insulation voltage | 300 V |
| Degree of pollution | 2 |
| Overvoltage category | II |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Conformance | CE-compliant |