Request QuoteProduct Overview
Phoenix Contact part SAC-5P- 2,0-28X/M12FS SH OD is a specialized sensor/actuator cable utilized for connecting industrial field devices, instruments, and automation hardware. These cables ensure protected signal exchange and power distribution in demanding plant floor environments.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 5
- Type of electrical connection, box-sided (EF005524): M12
- Type of plug-in contact, box-sided (EF008386): Female (bus)
- Positioning cable feed, box-sided (EF005927): Straight
- Cable length (EF000536): 2 m
- Halogen free (EF000025): Yes
- With LED indication (EF005950): No
- Screened (EF000881): Yes
- Cable type (EF000081): Multi-core
- Vulcanize (EF004115): No
- Material contact body (EF008248): CuSn
- Rated current In (EF008250): 4 A
- Rated voltage (EF000228): 48 V
- Degree of protection (IP) (EF005474): IP65
More info
▲Key Commercial Data
| Orderkey | 1407266 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 156 (C-4-2013) |
| GTIN | 4046356773843 |
| Weight per Piece (excluding packing) | 190.900 g |
| Custom tariff number | 85444290 |
| Country of origin | PL (Poland) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 105 °C (Plug / socket) |
|---|---|
| -40 °C ... 85 °C (On sudden changes in temperature (according to IEC 60512-11-4)) | |
| Degree of protection | IP65 |
| IP67 | |
| IP68 | |
| IP69K |
General
| Rated current at 40°C | 4 A |
|---|---|
| Rated voltage | 48 V AC |
| 60 V DC | |
| Number of positions | 5 |
| Insulation resistance | ≥ 100 MΩ |
| Coding | A - standard |
| Standards/regulations | M12 connector IEC 61076-2-101 |
| Status display | No |
| Protective circuit/component | unwired |
| Degree of pollution | 3 |
| Insertion/withdrawal cycles | ≥ 100 |
| Torque | 0.4 Nm (M12 connector) |
Material
| Flammability rating according to UL 94 | V0 |
|---|---|
| Contact material | CuSn |
| Contact surface material | Ni/Au |
| Contact carrier material | PP |
| Material of grip body | PP |
| Material, knurls | Stainless steel |
| Sealing material | FPM |
Standards and Regulations
| Standard designation | M12 connector |
|---|---|
| Standards/regulations | IEC 61076-2-101 |
| Flammability rating according to UL 94 | V0 |
Cable
| Cable type | PE-X black |
|---|---|
| Cable type (abbreviation) | 28X |
| Cable abbreviation | Li2X2X-C-V1-2X |
| Conductor cross section | 5x 0.5 mm² |
| AWG signal line | 20 |
| Conductor structure signal line | 28x 0.15 mm |
| Core diameter including insulation | 1.6 mm ±0.5 mm |
| Thickness, insulation | approx. 0.3 mm (Core insulation) |
| Wire colors | Brown, white, blue, black, gray |
| Overall twist | 5 wires around filler to the core |
| Length of twist, overall twist | 68 mm |
| Shielding | Braided copper wires |
| Optical shield covering | 85 % |
| External sheath, color | black-gray RAL 7021 |
| Inner sheath thickness | approx. 0.5 mm |
| Outer sheath thickness | approx. 0.7 mm |
| External cable diameter D | 7.25 mm ±0,3 mm |
| Minimum bending radius, fixed installation | 5 x D |
| Minimum bending radius, flexible installation | 10 x D |
| Number of bending cycles | 1000000 |
| Minimum bending radius, drag chain applications | 10 x D |
| Traversing path | 10 m |
| Traversing rate | 3 m/s |
| Acceleration | 10 m/s² |
| Cable weight | 85 kg/km |
| Outer sheath, material | PE-X |
| Material, inner sheath | PE-X |
| Material, filler | PP yarn |
| Material conductor insulation | PE-X |
| Conductor material | Bare Cu litz wires |
| Insulation resistance | ≥ 100 MΩ*km (at 20 °C) |
| Conductor resistance | ≤ 39 Ω/m (at 20 °C) |
| Working capacitance | ≤ 110 pF (core-core) |
| ≤ 200 pF (core-shield) | |
| Nominal voltage, cable | ≤ 300 V AC |
| Test voltage, cable | ≥ 3000 V AC (Spark test) |
| Test voltage Core/Shield | ≥ 1000 V AC (for 10 s) |
| Special properties | Inductance approx. 0.48 mH/km |
| Irradiated | |
| Flame resistance | According to DIN EN 60332-1-2 |
| according to DIN EN 50266-2-5 | |
| Halogen-free | in accordance with DIN VDE 0472 part 815 |
| in accordance with DIN EN 50267-2-1 | |
| Resistance to oil | According to DIN EN 60811-2-1, 168 h at 100°C |
| According to DIN EN 50306 | |
| Other resistance | Resistance to fuels according to IEC 60811, 168 h at 70°C |
| UV resistant according to DIN VDE 0276-605 | |
| UV resistant in accordance with DIN EN ISO 4892-2-A (750 h) | |
| Ambient temperature (operation) | -40 °C ... 105 °C (cable, fixed installation) |
| -15 °C ... 105 °C (cable, flexible installation) | |
| 20 °C ±5 °C (cable, drag chain applications) |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |