PHOENIX CONTACT PSR-SPP-24UC/ESA2/4X1/1X2/B PSR-SPP- 24UC/ESA2/4X1/1X2/B 2963954 PHOENIX CONTACT Safety relays View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PSR-SPP- 24UC/ESA2/4X1/1X2/B 2963954 PHOENIX CONTACT Safety relays

PSR-SPP-24UC/ESA2/4X1/1X2/B

2963954

PHOENIX CONTACT

1 Pcs.

Safety relays Safety relay for emergency stop and safety door up to SIL 1, category 1, PL c, depending on the application up to SIL 3, category 4, PL e, single-channel operation, 4 enabling circuits, US = 24 V DC, plug-in push-in terminal block

Automation > Device for monitoring of safety-related circuits
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Safety relays serve as the primary logic and switching elements in industrial safety circuits, ensuring machines stop predictably when safety boundaries are breached. The Phoenix Contact PSR-SPP-24UC/ESA2/4X1/1X2/B uses spring clamp connections and includes a dedicated feedback circuit for monitoring external contactors.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Model (EF000010): Basic device
  • Suitable for rail mounting (EF003972): Yes
  • With detachable clamps (EF003340): Yes
  • Type of electric connection (EF003961): Spring clamp connection
  • Suitable for monitoring of position switches (EF007270): Yes
  • Suitable for monitoring of valves (EF007272): No
  • Suitable for monitoring of tactile sensors (EF007271): No
  • Suitable for monitoring of magnetic switches (EF007266): Yes
  • Suitable for monitoring of proximity switches (EF007267): No
  • With start input (EF003342): No
  • With muting function (EF004057): No
  • With feedback circuit (EF003343): Yes
  • Release-delay (EF001129): 0.1 s
  • With approval for BG BIA (EF004145): No
  • With approval according to UL (EF001783): No
  • Width (EF000008): 22.5 mm

More info

▲

Key Commercial Data

Orderkey2963954
Packing unit1 pc
Catalog pagePage 260 (C-6-2017)
GTIN4017918904821
Weight per Piece (excluding packing)194.380 g
Custom tariff number85371098
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width22.5 mm
Height112 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 65 °C (observe derating)
Ambient temperature (storage/transport)-40 °C ... 70 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitude≤ 2000 m (Above sea level)

Input data

Rated control circuit supply voltage US24 V AC/DC -15 % / +10 %
Rated control supply current IStyp. 140 mA AC
typ. 65 mA DC
Power consumption at UStyp. 3.36 W (AC)
typ. 1.56 W (DC)
Inrush current2 A (Δt = 10 ms at Us)
< 40 mA (with Us/Ixto S34)
Current consumption< 50 mA (with Us/Ixto S12)
0 mA (with Us/Ixto S34)
Voltage at input/start and feedback circuit24 V DC -15 % / +10 %
Typical response time< 65 ms (automatic start)
< 40 ms (manual start)
Typ. starting time with Us< 65 ms (when controlled via A1)
Typical release time< 45 ms (when controlled via S12)
< 200 ms (when controlled via A1)
Recovery time< 1 s
Operating voltage display1 x green LED
Status display2 x green LEDs
Protective circuitSurge protection Suppressor diode
Protection against polarity reversal for rated control circuit supply voltage
Maximum switching frequency1 Hz
Max. permissible overall conductor resistanceapprox. 22 Ω (Input and start circuits at US)
Filter time2 ms (at A1 in the event of voltage dips at Us)
max. 1.5 ms (at S12; test pulse width)
7.5 ms (at S12; test pulse rate)
Test pulse rate = 5 x Test pulse width

Output data

Contact type4 enabling current paths
1 signaling current path
Contact materialAgSnO2
Maximum switching voltage250 V AC/DC (Observe the load curve)
Minimum switching voltage5 V AC/DC
Limiting continuous current6 A (N/O contact, pay attention to the derating)
6 A (N/C contact)
Maximum inrush current20 A (Δt  100 ms)
Inrush current, minimum10 mA
Sq. Total current72 A2(observe derating)
Interrupting rating (ohmic load) max.144 W (24 V DC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
110 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load)42 W (24 V DC, τ = 40 ms)
42 W (48 V DC, τ = 40 ms)
42 W (110 V DC, τ = 40 ms)
42 W (220 V DC, τ = 40 ms)
Switching capacity min.50 mW
Mechanical service life10x 106cycles
Switching capacity (360/h cycles)4 A (24 V DC)
4 A (230 V AC)
Output fuse10 A gL/gG (N/O contact)
6 A gL/gG (N/C contact)

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight194.38 g
Mounting positionvertical or horizontal
Mounting typeDIN rail mounting
Assembly instructionsSee derating curve
Degree of protectionIP20
IP54
Min. degree of protection of inst. locationIP54
Housing materialPBT
Housing coloryellow

Connection data

Connection methodSpring-cage connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.1.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.1.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.16
Stripping length8 mm

Safety-related characteristic data

Stop category0
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)1 (up to SIL 3 depending on the application)
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)1 (up to SIL 3 depending on the application)
DesignationEN ISO 13849
Performance level (PL)c (up to PL e depending on the application)
Category1 (up to Cat. 4 depending on the application)
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)1 (up to SILCL 3 depending on the application)

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178/VDE 0160
Rated insulation voltage250 V AC
Rated surge voltage/insulationBasic insulation 4 kV:
between all current paths and housing
Safe isolation, reinforced insulation 6 kV:
between A1/A2 and 13/14, 23/24, 33/34, 43/44
between S11/S12/S33/S34 and 13/14, 23/24, 33/34, 43/44
between 51/52 and 13/14, 23/24, 33/34, 43/44
Degree of pollution2
Overvoltage categoryIII
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g
ConformanceCE-compliant

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.