PSR-SPP- 24UC/ESA2/4X1/1X2/B 2963954 PHOENIX CONTACT Safety relays
PSR-SPP-24UC/ESA2/4X1/1X2/B
2963954
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Safety relays serve as the primary logic and switching elements in industrial safety circuits, ensuring machines stop predictably when safety boundaries are breached. The Phoenix Contact PSR-SPP-24UC/ESA2/4X1/1X2/B uses spring clamp connections and includes a dedicated feedback circuit for monitoring external contactors.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Model (EF000010): Basic device
- Suitable for rail mounting (EF003972): Yes
- With detachable clamps (EF003340): Yes
- Type of electric connection (EF003961): Spring clamp connection
- Suitable for monitoring of position switches (EF007270): Yes
- Suitable for monitoring of valves (EF007272): No
- Suitable for monitoring of tactile sensors (EF007271): No
- Suitable for monitoring of magnetic switches (EF007266): Yes
- Suitable for monitoring of proximity switches (EF007267): No
- With start input (EF003342): No
- With muting function (EF004057): No
- With feedback circuit (EF003343): Yes
- Release-delay (EF001129): 0.1 s
- With approval for BG BIA (EF004145): No
- With approval according to UL (EF001783): No
- Width (EF000008): 22.5 mm
More info
▲Key Commercial Data
| Orderkey | 2963954 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 260 (C-6-2017) |
| GTIN | 4017918904821 |
| Weight per Piece (excluding packing) | 194.380 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 65 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
Input data
| Rated control circuit supply voltage US | 24 V AC/DC -15 % / +10 % |
|---|---|
| Rated control supply current IS | typ. 140 mA AC |
| typ. 65 mA DC | |
| Power consumption at US | typ. 3.36 W (AC) |
| typ. 1.56 W (DC) | |
| Inrush current | 2 A (Δt = 10 ms at Us) |
| < 40 mA (with Us/Ixto S34) | |
| Current consumption | < 50 mA (with Us/Ixto S12) |
| 0 mA (with Us/Ixto S34) | |
| Voltage at input/start and feedback circuit | 24 V DC -15 % / +10 % |
| Typical response time | < 65 ms (automatic start) |
| < 40 ms (manual start) | |
| Typ. starting time with Us | < 65 ms (when controlled via A1) |
| Typical release time | < 45 ms (when controlled via S12) |
| < 200 ms (when controlled via A1) | |
| Recovery time | < 1 s |
| Operating voltage display | 1 x green LED |
| Status display | 2 x green LEDs |
| Protective circuit | Surge protection Suppressor diode |
| Protection against polarity reversal for rated control circuit supply voltage | |
| Maximum switching frequency | 1 Hz |
| Max. permissible overall conductor resistance | approx. 22 Ω (Input and start circuits at US) |
| Filter time | 2 ms (at A1 in the event of voltage dips at Us) |
| max. 1.5 ms (at S12; test pulse width) | |
| 7.5 ms (at S12; test pulse rate) | |
| Test pulse rate = 5 x Test pulse width |
Output data
| Contact type | 4 enabling current paths |
|---|---|
| 1 signaling current path | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 250 V AC/DC (Observe the load curve) |
| Minimum switching voltage | 5 V AC/DC |
| Limiting continuous current | 6 A (N/O contact, pay attention to the derating) |
| 6 A (N/C contact) | |
| Maximum inrush current | 20 A (Δt 100 ms) |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2(observe derating) |
| Interrupting rating (ohmic load) max. | 144 W (24 V DC, τ = 0 ms) |
| 288 W (48 V DC, τ = 0 ms) | |
| 110 W (110 V DC, τ = 0 ms) | |
| 88 W (220 V DC, τ = 0 ms) | |
| 1500 VA (250 V AC, τ = 0 ms) | |
| Maximum interrupting rating (inductive load) | 42 W (24 V DC, τ = 40 ms) |
| 42 W (48 V DC, τ = 40 ms) | |
| 42 W (110 V DC, τ = 40 ms) | |
| 42 W (220 V DC, τ = 40 ms) | |
| Switching capacity min. | 50 mW |
| Mechanical service life | 10x 106cycles |
| Switching capacity (360/h cycles) | 4 A (24 V DC) |
| 4 A (230 V AC) | |
| Output fuse | 10 A gL/gG (N/O contact) |
| 6 A gL/gG (N/C contact) |
General
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 194.38 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Assembly instructions | See derating curve |
| Degree of protection | IP20 |
| IP54 | |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | yellow |
Connection data
| Connection method | Spring-cage connection |
|---|---|
| pluggable | Yes |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 1.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 1.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 16 |
| Stripping length | 8 mm |
Safety-related characteristic data
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 - High demand |
| Safety Integrity Level (SIL) | 1 (up to SIL 3 depending on the application) |
| Designation | IEC 61508 - Low demand |
| Safety Integrity Level (SIL) | 1 (up to SIL 3 depending on the application) |
| Designation | EN ISO 13849 |
| Performance level (PL) | c (up to PL e depending on the application) |
| Category | 1 (up to Cat. 4 depending on the application) |
| Designation | EN 62061 |
| Safety Integrity Level Claim Limit (SIL CL) | 1 (up to SILCL 3 depending on the application) |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178/VDE 0160 |
| Rated insulation voltage | 250 V AC |
| Rated surge voltage/insulation | Basic insulation 4 kV: between all current paths and housing Safe isolation, reinforced insulation 6 kV: between A1/A2 and 13/14, 23/24, 33/34, 43/44 between S11/S12/S33/S34 and 13/14, 23/24, 33/34, 43/44 between 51/52 and 13/14, 23/24, 33/34, 43/44 |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Shock | 15g |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| Conformance | CE-compliant |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |