PSR-SPP- 24DC/ESP4/2X1/1X2 2981017 PHOENIX CONTACT Safety relays
PSR-SPP-24DC/ESP4/2X1/1X2
2981017
PHOENIX CONTACT
1 Pcs.
Safety relays
Safety relay for SIL 3 high- and low-demand applications, also approved according to EN 50156, Germanischer Lloyd and EN ISO 13849, emergency stop and safety door monitoring, single-channel, 2 trip circuits, 1 warning contact, width: 22.5 mm, plug-in push-in terminal block
Safety relay for SIL 3 high-demand and low-demand applications, also approved in accordance with EN 50156, DNV, and EN ISO 13849, emergency stop and safety door monitoring, 1-channel, 2 enabling current paths, 1 signal contact, width: 22.5 mm, pluggable Push-in terminal block
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact PSR-SPP-24DC/ESP4/2X1/1X2 safety relay processes emergency stop signals and protective device states, ensuring dependable shutdown functionality across factory automation lines.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Note on application Note on application: Only for industrial use
- Product type: Safety relays
- Product family: PSRclassic
- Application: Emergency stop
- Mechanical service life: approx. 10 7 cycles
- Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
- Data management status Article revision: 08
- Times Typical response time: typ. 60 ms (For U s manual, monitored start)
- Typ. starting time with U s: 60 ms (At Us/on demand via A1)
- Typical release time: typ. 20 ms (At Us/on demand via A1)
- Restart time: < 1 s (Boot time)
- Recovery time: ≥ 1 s (following demand of the safety function)
- Maximum power dissipation for nominal condition: 16.12 W (At U S = 26.4 V, I L ² = 72 A², P Total max = 1.72 W + 14.4 W)
- Nominal operating mode: 100% operating factor
- Rated surge voltage/insulation: See section “Insulation coordination”
- Digital: Logic (A1) Description of the input: safety-related
More info
▲Technical data
Notes
| Note on application | |
| Note on application | Only for industrial use |
Product properties
| Product type | Safety relays |
| Product family | PSRclassic |
| Application | Emergency stop |
| Process technology | |
| Safety door | |
| Mechanical service life | approx. 107cycles |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Data management status | |
| Article revision | 08 |
| Times | |
| Typical response time | typ. 60 ms (For Usmanual, monitored start) |
| 60 ms (For Usautostart) | |
| Typ. starting time with Us | 60 ms (At Us/on demand via A1) |
| Typical release time | typ. 20 ms (At Us/on demand via A1) |
| Restart time | < 1 s (Boot time) |
| Recovery time | ≥ 1 s (following demand of the safety function) |
Electrical properties
| Maximum power dissipation for nominal condition | 16.12 W (At US= 26.4 V, IL² = 72 A², PTotal max= 1.72 W + 14.4 W) |
| Nominal operating mode | 100% operating factor |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V |
| 250 V | |
| Rated surge voltage/insulation | See section “Insulation coordination” |
Input data
| Digital: Logic (A1) | |
| Description of the input | safety-related |
| Number of inputs | 1 |
| Input voltage range "1" signal | 20.4 V ... 26.4 V |
| Inrush current | max. 1 A (typ. with US, Δt = |
| Filter time | max. 3 ms (Test pulse width of low test pulses) |
| min. 200 ms (Test pulse rate for low test pulse) | |
| No brightness test pulses / high test pulses permitted. | |
| Max. permissible overall conductor resistance | 50 Ω |
| Protective circuit | Suppressor diode |
| Current consumption | 65 mA (typ. with US) |
| Digital: Start circuit (Y2) | |
| Description of the input | non-safety-related |
| Number of inputs | 1 |
| Input voltage range "1" signal | 20.4 V ... 26.4 V |
| Inrush current | < 14 mA (typically with USat Y2, Δt - 10 ms) |
| Filter time | No test pulses permitted |
| Max. permissible overall conductor resistance | 50 Ω |
| Protective circuit | Suppressor diode |
| Current consumption | 0 mA (typically with USat Y2) |
Output data
| Relay: Enabling current paths (13/14, 23/24) | |
| Output description | 2 N/O contacts each in series, safety-related, floating |
| Number of outputs | 2 |
| Contact switching type | 2 enabling current paths |
| Contact material | AgSnO2 |
| Switching voltage | min. 10 V |
| max. 250 V AC/DC | |
| Switching capacity | min. 100 mW |
| Inrush current | min. 10 mA |
| max. 6 A | |
| Switching capacity in accordance with IEC 60947-5-1 | 5 A (AC15) |
| 5 A (DC13) | |
| Limiting continuous current | 6 A (Observe derating and load limit curve) |
| Sq. Total current | 72 A2(observe derating) |
| Switching frequency | max. 0.5 Hz |
| Mechanical service life | 107cycles |
| Interrupting rating (ohmic load) max. | Observe derating and load limit curve |
| Maximum interrupting rating (inductive load) | Observe derating and load limit curve |
| Output fuse | 10 A gL/gG |
| 4 A gL/gG (for low-demand applications) | |
| Relay: Signaling current path (31/32) | |
| Output description | 2 N/C contacts parallel, non-safety-related, floating |
| Number of outputs | 1 |
| Contact switching type | 1 signaling current path |
| Contact material | AgSnO2 |
| Switching voltage | min. 10 V AC/DC |
| max. 250 V AC/DC | |
| Switching capacity | min. 100 mW |
| Inrush current | min. 10 mA |
| max. 6 A | |
| Switching capacity in accordance with IEC 60947-5-1 | 1.5 A (AC15) |
| 2 A (DC13) | |
| Limiting continuous current | 6 A |
| Sq. Total current | 36 A2(observe derating) |
| Switching frequency | max. 0.5 Hz |
| Mechanical service life | 107cycles |
| Interrupting rating (ohmic load) max. | Observe derating and load limit curve |
| Maximum interrupting rating (inductive load) | Observe derating and load limit curve |
| Output fuse | 6 A gL/gG |
Connection data
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible, with ferrule, with plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross section flexible, with ferrule without plastic sleeve | 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) |
| Conductor cross-section AWG | 24 ... 16 |
| Stripping length | 8 mm |
Signaling
| Status display | LED (green) |
| Operating voltage display | Green LED |
Dimensions
| Width | 22.5 mm |
| Height | 112 mm |
| Depth | 114.5 mm |
Material specifications
| Color (Housing) | yellow (RAL 1018) |
| Housing material | Polyamide |
Characteristics
| Safety data | |
| Stop category | 0 |
| Safety data: EN ISO 13849 | |
| Category | 4 |
| Performance level (PL) | e |
| Safety data: IEC 61508 - High demand | |
| Safety Integrity Level (SIL) | 3 |
| Safety data: IEC 61508 - Low demand | |
| Safety Integrity Level (SIL) | 3 |
| Safety data: EN IEC 62061 | |
| Safety Integrity Level (SIL) | 3 |
Environmental and real-life conditions
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -20 °C ... 55 °C (observe derating) |
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Maximum altitude | ≤ 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
Approvals
| CE | |
| Identification | CE-compliant |
Standards and regulations
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | DIN EN 60947-1 |
Mounting
| Mounting type | DIN rail mounting |
| Mounting position | On horizontal and vertical DIN rail |