View larger
PSR-SCP- 24UC/URM/5X1/1X2 2981952 PHOENIX CONTACT Coupling relay
PSR-SCP-24UC/URM/5X1/1X2
2981952
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Industrial coupling relays provide secure signal amplification and electrical separation between control systems and output actuators in manufacturing plants. This Phoenix Contact PSR-SCP-24UC/URM/5X1/1X2 component uses force-guided contacts to guarantee safe switching performance and reliable diagnostic feedback across process control loops.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Note on application Note on application: Only for industrial use
- Product type: Coupling relay
- Product family: PSRclassic
- Application: Safe switch off
- Mechanical service life: 10x 10 6 cycles
- Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
- Data management status Article revision: 06
- Times Restart time: < 1 s (Boot time)
- Nominal operating mode: 100% operating factor
- General Rated control circuit supply voltage U S: 24 V AC/DC -15 % / +10 %
- Power consumption at U S: typ. 1.2 W
- Rated control supply current I S: typ. 47 mA
- Input voltage range: 20.4 V AC/DC ... 26.4 V AC/DC
- Inrush current: typ. 350 mA DC (Δt s)
- Typ. starting time with U s: typ. 20 ms (when controlled via A1)
- Typical release time: typ. 20 ms (when controlled via A1)
More info
▲| Note on application | |
| Note on application | Only for industrial use |
| Product type | Coupling relay |
| Product family | PSRclassic |
| Application | Safe switch off |
| High demand | |
| Low demand | |
| Mechanical service life | 10x 106cycles |
| Relay type | Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3 |
| Data management status | |
| Article revision | 06 |
| Times | |
| Restart time | < 1 s (Boot time) |
| Maximum power dissipation for nominal condition | 8.56 W (at UB= 26.4 V DC, US= 24 V, IS= 47 mA, n = 1, IL² = 72 A², Rcontact= 0.1 ) |
| Nominal operating mode | 100% operating factor |
| Air clearances and creepage distances between the power circuits | |
| Rated insulation voltage | 250 V |
| 250 V | |
| Rated surge voltage/insulation | 4 kV / basic isolation (safe isolation, reinforced isolation and 6 kV between A1/A2, 53/54, 71/72 and 13/14, 23/24, 33/34, 43/44.) |
| General | |
| Rated control circuit supply voltage US | 24 V AC/DC -15 % / +10 % |
| Power consumption at US | typ. 1.2 W |
| Rated control supply current IS | typ. 47 mA |
| Input voltage range | 20.4 V AC/DC ... 26.4 V AC/DC |
| Inrush current | typ. 350 mA DC (Δt s) |
| typ. 350 mA AC (Δt = 2 ms at Us) | |
| Typ. starting time with Us | typ. 20 ms (when controlled via A1) |
| Typical release time | typ. 20 ms (when controlled via A1) |
| Recovery time | < 500 ms |
| Maximum switching frequency | 0.5 Hz |
| Protective circuit | Surge protection; Varistor |
| Operating voltage display | 1 x green LED |
| Contact switching type | 5 enabling current paths |
| 1 confirmation current path | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 230 V AC/DC (Observe the load curve) |
| Minimum switching voltage | 5 V AC/DC |
| Limiting continuous current | 6 A (N/O contact) |
| 6 A (N/C contact) | |
| Maximum inrush current | 6 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 72 A2 |
| Interrupting rating (ohmic load) max. | 144 W (N/O contact, 24 V DC, τ = 0 ms) |
| 288 W (N/O contact, 48 V DC, τ = 0 ms) | |
| 240 W (N/O contact, 60 V DC, τ = 0 ms) | |
| 110 W (N/O contact, 110 V DC, τ = 0 ms) | |
| 88 W (N/O contact, 220 V DC, τ = 0 ms) | |
| 1380 VA (N/O contact, 230 V AC, τ = 0 ms) | |
| Maximum interrupting rating (inductive load) | 42 W (N/O contact, 24 V DC, τ = 40 ms) |
| 42 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 42 W (N/O contact, 220 V DC, τ = 40 ms) | |
| Switching capacity | min. 50 mW |
| Switching capacity in accordance with IEC 60947-5-1 | 3 A (24 V (DC13)) |
| 3 A (230 V (AC 15)) | |
| Switching capacity (360/h cycles) | 4 A (24 V (DC13)) |
| 4 A (230 V (AC15)) | |
| Output fuse | 10 A gL/gG (N/O contact) |
| 4 A gL/gG (N/O contact, for low-demand applications) | |
| 6 A gL/gG (N/C contact) |
| Connection technology | |
| pluggable | yes |
| Conductor connection | |
| Connection method | Screw connection |
| Conductor cross section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Tightening torque | 0.6 Nm |
| Width | 22.5 mm |
| Height | 114.5 mm |
| Depth | 99 mm |
| Color (Housing) | yellow (RAL 1018) |
| Housing material | Polyamide |
| Safety data | |
| Stop category | 0 |
| Safety data: EN ISO 13849 | |
| Category | 1 |
| Performance level (PL) | c |
| Safety data: IEC 61508 - High demand | |
| Safety Integrity Level (SIL) | 1 |
| Safety data: IEC 61508 - Low demand | |
| Safety Integrity Level (SIL) | 1 |
| Safety data | |
| Safety Integrity Level (SIL) | 1 |
| Ambient conditions | |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Ambient temperature (operation) | -20 °C ... 55 °C |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Maximum altitude | max. 2000 m (Above sea level) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Shock | 15g (In the event of stress caused by shock, contact reactions are possible for up to 2 ms.) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 1 ms.) |
| CE | |
| Certificate | CE-compliant |
| Air clearances and creepage distances between the power circuits | |
| Standards/regulations | DIN EN 50178 |
| Mounting type | DIN rail mounting |
| Mounting position | vertical or horizontal |