Safe coupling relay with forced-conduction contacts, 3 normally open contacts, 3 normally closed contacts, plug-in screw terminal, width: 22.5 mm
Safe coupling relay with force-guided contacts, 3 N/O contacts, 3 N/C contacts, plug-in screw terminal block, width: 22.5 mm
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact PSR-SCP-24UC/URM/3X1/3X2 coupling relay provides electrical isolation and signal multiplication between control systems and safety actuators in complex industrial setups.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Model (EF000010): Basic device
- Suitable for rail mounting (EF003972): Yes
- With detachable clamps (EF003340): Yes
- Type of electric connection (EF003961): Screw connection
- Suitable for monitoring of valves (EF007272): No
- Suitable for monitoring of tactile sensors (EF007271): No
- Suitable for monitoring of magnetic switches (EF007266): No
- Suitable for monitoring of proximity switches (EF007267): No
- With start input (EF003342): No
- With muting function (EF004057): No
- With feedback circuit (EF003343): No
- Release-delay (EF001129): 0.015 s
- With approval for BG BIA (EF004145): No
- With approval according to UL (EF001783): No
- Width (EF000008): 22.5 mm
- Height (EF000040): 114.5 mm
More info
▲Key Commercial Data
| Orderkey | 2981839 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 278 (C-6-2017) |
| GTIN | 4046356138604 |
| Weight per Piece (excluding packing) | 126.900 g |
| Custom tariff number | 85364900 |
| Country of origin | DE (Germany) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 55 °C |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 70 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | max. 2000 m (Above sea level) |
Input data
| Rated control circuit supply voltage US | 24 V AC/DC -15 % / +10 % |
|---|---|
| Rated control supply current IS | typ. 45 mA |
| Power consumption at US | typ. 1.08 W |
| Inrush current | typ. 350 mA DC (Δt s) |
| typ. 350 mA AC (Δt = 2 ms at Us) | |
| Typ. starting time with Us | typ. 15 ms (when controlled via A1) |
| Typical release time | typ. 15 ms (when controlled via A1) |
| Recovery time | < 500 ms |
| Operating voltage display | 1 x green LED |
| Protective circuit | Surge protection Suppressor diode |
| Maximum switching frequency | 0.5 Hz |
Output data
| Contact type | 3 enabling current paths |
|---|---|
| 3 confirmation current paths | |
| Contact material | AgSnO2 |
| Maximum switching voltage | 230 V AC/DC (Observe the load curve) |
| Minimum switching voltage | 5 V AC/DC |
| Limiting continuous current | 6 A (N/O contact) |
| 3 A (N/C contact) | |
| Maximum inrush current | 8 A |
| Inrush current, minimum | 10 mA |
| Sq. Total current | 48 A2 |
| Interrupting rating (ohmic load) max. | For additional values, see load curve |
| Maximum interrupting rating (inductive load) | 48 W (N/O contact, 24 V DC, τ = 40 ms) |
| 40 W (N/O contact, 48 V DC, τ = 40 ms) | |
| 36 W (N/O contact, 60 V DC, τ = 40 ms) | |
| 35 W (N/O contact, 110 V DC, τ = 40 ms) | |
| 33 W (N/O contact, 220 V DC, τ = 40 ms) | |
| Switching capacity | min. 50 mW |
| Mechanical service life | 10x 106cycles |
| Switching capacity according to IEC 60947-5-1 | 5 A (24 V (DC13)) |
| 5 A (250 V (AC15)) | |
| Output fuse | 10 A gL/gG (N/O contact) |
| 4 A gL/gG (N/O contact, for low-demand applications) | |
| 6 A gL/gG (N/C contact) |
General
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with EN 50205 |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 126.9 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Degree of protection | IP20 |
| IP54 | |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | yellow |
Connection data
| Connection method | Screw connection |
|---|---|
| pluggable | Yes |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 24 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 7 mm |
| Screw thread | M3 |
Safety-related characteristic data
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 - High demand |
| Safety Integrity Level (SIL) | 1 |
| Designation | IEC 61508 - Low demand |
| Safety Integrity Level (SIL) | 1 |
| Designation | EN ISO 13849 |
| Performance level (PL) | c |
| Category | 1 |
| Safety Integrity Level Claim Limit (SIL CL) | 1 |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178 |
| Rated insulation voltage | 250 V |
| 250 V | |
| Rated surge voltage/insulation | 4 kV / Basic isolation, (safe isolation, reinforced insulation and 6 kV between input circuit and enabling current paths.) |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Shock | 15g (In the event of stress caused by shock, contact reactions are possible for up to 2 ms.) |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g (In the event of stress caused by vibration, contact reactions are possible for up to 1 ms.) |
| Conformance | CE-compliant |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |