PHOENIX CONTACT PSR-SCP-24UC/ESAM4/2X1/1X2 PSR-SCP- 24UC/ESAM4/2X1/1X2 2900525 PHOENIX CONTACT Safety relays View larger
Images are for illustrative purposes only. Please refer to data sheet for details

PSR-SCP- 24UC/ESAM4/2X1/1X2 2900525 PHOENIX CONTACT Safety relays

PSR-SCP-24UC/ESAM4/2X1/1X2

2900525

PHOENIX CONTACT

1 Pcs.

Safety relays Safety relay for emergency stop control and safety doors up to SIL 3 or category 4, PL e according to EN ISO 13849, two-channel operation, 2 trip circuits, input voltage rated 24 V DC, plug-in screw terminal

Automation > Device for monitoring of safety-related circuits
Safety

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Phoenix Contact Safety relays unit serves as a critical logic interface in industrial automation architectures, continuously checking safety sensors and interlocking circuits to halt hazardous machinery movements safely.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Model (EF000010): Basic device
  • Suitable for rail mounting (EF003972): Yes
  • With detachable clamps (EF003340): Yes
  • Type of electric connection (EF003961): Screw connection
  • Suitable for monitoring of position switches (EF007270): Yes
  • Suitable for monitoring of valves (EF007272): No
  • Suitable for monitoring of tactile sensors (EF007271): No
  • Suitable for monitoring of magnetic switches (EF007266): Yes
  • Suitable for monitoring of proximity switches (EF007267): No
  • With start input (EF003342): No
  • With muting function (EF004057): No
  • With feedback circuit (EF003343): Yes
  • Release-delay (EF001129): 0.1 s
  • With approval for BG BIA (EF004145): No
  • With approval according to UL (EF001783): No
  • Width (EF000008): 22.5 mm

More info

▲

Key Commercial Data

Orderkey2900525
Packing unit1 pc
Catalog pagePage 260 (C-6-2017)
GTIN4046356515658
Weight per Piece (excluding packing)137.480 g
Custom tariff number85371098
Country of originDE (Germany)

Note

Utilization restrictionEMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width22.5 mm
Height99 mm
Depth114.5 mm

Ambient conditions

Ambient temperature (operation)-20 °C ... 55 °C
Ambient temperature (storage/transport)-40 °C ... 70 °C
Max. permissible relative humidity (operation)75 % (on average, 85% infrequently, non-condensing)
Max. permissible humidity (storage/transport)75 % (on average, 85% infrequently, non-condensing)
Maximum altitude≤ 2000 m (Above sea level)

Input data

Rated control circuit supply voltage US
Nominal input voltage UN24 V AC/DC
Input voltage range in reference to UN0.85 ... 1.1
Typical input current at UN140 mA AC
65 mA DC
Voltage at input/start and feedback circuitapprox. 24 V DC
Typical response time20 ms (manual start)
150 ms (automatic start)
Typical release time45 ms (single-channel)
10 ms (two-channel)
Concurrence input 1/2∞
Recovery time1 s
Operating voltage displayGreen LED
Status displayGreen LED
Protective circuitSurge protection Suppressor diode
Max. permissible overall conductor resistanceapprox. 50 Ω (Input and start circuits at UN)

Output data

Contact type2 enabling current paths
1 signaling current path
Contact materialAgSnO2, + 0.2 µm Au
Maximum switching voltage250 V AC/DC
Minimum switching voltage15 V AC/DC
Limiting continuous current6 A (N/O contact)
Maximum inrush current6 A
Inrush current, minimum25 mA
Sq. Total current72 A2(ITH2= I12+ I22)
Interrupting rating (ohmic load) max.144 W (24 V DC, τ = 0 ms)
288 W (48 V DC, τ = 0 ms)
77 W (110 V DC, τ = 0 ms)
88 W (220 V DC, τ = 0 ms)
1500 VA (250 V AC, τ = 0 ms)
Maximum interrupting rating (inductive load)48 W (24 V DC, τ = 40 ms)
40 W (48 V DC, τ = 40 ms)
35 W (110 V DC, τ = 40 ms)
35 W (220 V DC, τ = 40 ms)
Switching capacity min.0.4 W
Mechanical service lifeapprox. 107cycles
Switching capacity (360/h cycles)6 A (24 V DC)
5 A (230 V AC)
Output fuse10 A gL/gG NEOZED (N/O contact)
6 A gL/gG NEOZED (N/C contact)

General

Relay typeElectromechanical relay with forcibly guided contacts in accordance with EN 50205
Nominal operating mode100% operating factor
Net weight137.48 g
Mounting positionany
Mounting typeDIN rail mounting
Degree of protectionIP20
IP54
Min. degree of protection of inst. locationIP54
Housing coloryellow

Connection data

Connection methodScrew connection
pluggableYes
Conductor cross section solid min.0.2 mm²
Conductor cross section solid max.2.5 mm²
Conductor cross section flexible min.0.2 mm²
Conductor cross section flexible max.2.5 mm²
Conductor cross section AWG min.24
Conductor cross section AWG max.12
Stripping length7 mm
Screw threadM3

Safety-related characteristic data

Stop category0
DesignationIEC 61508 - High demand
Safety Integrity Level (SIL)3
DesignationIEC 61508 - Low demand
Safety Integrity Level (SIL)3
DesignationEN ISO 13849
Performance level (PL)e
Category4
DesignationEN 62061
Safety Integrity Level Claim Limit (SIL CL)3
DesignationEN 50156
Safety Integrity Level (SIL)3

Standards and Regulations

DesignationAir clearances and creepage distances between the power circuits
Standards/regulationsDIN EN 50178/VDE 0160
Rated insulation voltage250 V
Rated surge voltage/insulation6 kV / Safe isolation, increased insulation
Degree of pollution2
Overvoltage categoryIII
Shock15g
Vibration (operation)10 Hz ... 150 Hz, 2g

Environmental Product Compliance

China RoHSEnvironmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

Classifications


Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.