View larger
PSR-MS50-1NO-1DO-24DC-SC 2904956 PHOENIX CONTACT Safety relays
PSR-MS50-1NO-1DO-24DC-SC
2904956
PHOENIX CONTACT
1 Pcs.
Automation > Device for monitoring of safety-related circuits
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Safety relays provide essential signal isolation and logical evaluation for industrial automation circuits, ensuring that machinery halts reliably when protective barriers are breached. This Phoenix Contact PSR-MS50-1NO-1DO-24DC-SC unit integrates seamlessly into control cabinets to manage emergency shutdown sequences and interlocking devices.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Model (EF000010): Basic device
- Suitable for rail mounting (EF003972): Yes
- With detachable clamps (EF003340): No
- Type of electric connection (EF003961): Screw connection
- Suitable for monitoring of position switches (EF007270): Yes
- Suitable for monitoring of valves (EF007272): No
- Suitable for monitoring of tactile sensors (EF007271): No
- Suitable for monitoring of magnetic switches (EF007266): Yes
- Suitable for monitoring of proximity switches (EF007267): No
- With start input (EF003342): No
- With muting function (EF004057): No
- With feedback circuit (EF003343): Yes
- Release-delay (EF001129): 0.175 s
- With approval for BG BIA (EF004145): No
- With approval according to UL (EF001783): No
- Width (EF000008): 6.8 mm
More info
▲Key Commercial Data
| Orderkey | 2904956 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 250 (C-6-2017) |
| GTIN | 4046356904063 |
| Weight per Piece (excluding packing) | 69.000 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
Ambient conditions
| Ambient temperature (operation) | -40 °C ... 60 °C (observe derating) |
|---|---|
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Max. permissible relative humidity (operation) | 75 % (on average, 85% infrequently, non-condensing) |
| Max. permissible humidity (storage/transport) | 75 % (on average, 85% infrequently, non-condensing) |
| Maximum altitude | ≤ 2000 m (Above sea level) |
Power supply
| Rated control circuit supply voltage US | 24 V DC -15 % / +10 % |
|---|---|
| 20.4 V DC ... 26.4 V DC | |
| Rated control supply current IS | typ. 42 mA |
| Power consumption at US | typ. 1 W |
| Inrush current | 4.5 A (Δt s) |
| Filter time | 1 ms (at A1 in the event of voltage dips at Us) |
| Protective circuit | Surge protection Suppressor diode |
| Protection against polarity reversal for rated control circuit supply voltage |
Digital inputs
| Input voltage range "0" signal | 0 V DC ... 5 V DC (for safe Off; at S12) |
|---|---|
| Input current range "0" signal | 0 mA ... 2 mA (for safe Off; at S12) |
| Inrush current | < 20 mA (with Us/Ixto S12) |
| < 10 mA (with Us/Ixat the start circuit) | |
| < 20 mA (with Us/Ixto S13) | |
| Current consumption | < 5 mA (with Us/Ixto S12) |
| < 5 mA (with Us/Ixto S13) | |
| < 10 mA (with Us/Ixat the start circuit) | |
| Filter time | max. 1.5 ms (at S12, S13; test pulse width) |
| min. 7.5 ms (at S12, S13; test pulse rate) | |
| Test pulse rate = 5 x Test pulse width | |
| Voltage at input/start and feedback circuit | 24 V DC -15 % / +10 % |
| Max. permissible overall conductor resistance | 150 Ω |
Relay outputs: enabling current path
| Output name | Enabling current path |
|---|---|
| Output description | safety-related N/O contacts |
| Number of outputs | 1 (undelayed) |
| Contact type | 1 enabling current path |
| Contact material | AgSnO2 |
| Switching voltage | min. 12 V AC/DC |
| max. 250 V AC/DC (Observe the load curve) | |
| Limiting continuous current | 6 A (observe derating) |
| Inrush current | min. 3 mA |
| max. 6 A | |
| Sq. Total current | 36 A2(observe derating) |
| Switching capacity | min. 60 mW |
| Switching frequency | max. 0.5 Hz |
| Mechanical service life | 10x 106cycles |
| Output fuse | 6 A gL/gG (N/O contact) |
| 4 A gL/gG (for low-demand applications) |
Alarm outputs
| Output description | non-safety-related |
|---|---|
| Number of outputs | 1 (digital, PNP) |
| Voltage | 22 V DC (Us- 2 V) |
| Current | max. 100 mA |
| Maximum inrush current | 500 mA (Δt = 1 ms at Us) |
| Short-circuit protection | no |
Times
| Typical pickup time at US | < 250 ms (when controlled via A1) |
|---|---|
| Typical response time at US | < 175 ms |
| Typical release time at US | < 20 ms (when controlled via A1 or S12 and S13.) |
| Recovery time | < 500 ms |
General
| Relay type | Electromechanical relay with forcibly guided contacts in accordance with IEC/EN 61810-3 (EN 50205) |
|---|---|
| Nominal operating mode | 100% operating factor |
| Net weight | 69 g |
| Mounting position | vertical or horizontal |
| Mounting type | DIN rail mounting |
| Assembly instructions | See derating curve |
| Degree of protection | IP20 |
| Min. degree of protection of inst. location | IP54 |
| Housing material | PBT |
| Housing color | yellow |
| Operating voltage display | 1 x green LED |
| Status display | 2 x green LEDs |
Connection data
| Connection method | Screw connection |
|---|---|
| pluggable | no |
| Conductor cross section solid min. | 0.2 mm² |
| Conductor cross section solid max. | 2.5 mm² |
| Conductor cross section flexible min. | 0.2 mm² |
| Conductor cross section flexible max. | 2.5 mm² |
| Conductor cross section AWG min. | 26 |
| Conductor cross section AWG max. | 12 |
| Stripping length | 12 mm |
| Screw thread | M3 |
Safety-related characteristic data
| Stop category | 0 |
|---|---|
| Designation | IEC 61508 - High demand |
| Safety Integrity Level (SIL) | 3 |
| Designation | IEC 61508 - Low demand |
| Safety Integrity Level (SIL) | 3 |
| Designation | EN ISO 13849 |
| Performance level (PL) | e (4 A DC13; 5 A AC15; 8760 switching cycles/year) |
| Category | 4 |
| Designation | EN 62061 |
| Safety Integrity Level Claim Limit (SIL CL) | 3 |
Standards and Regulations
| Designation | Air clearances and creepage distances between the power circuits |
|---|---|
| Standards/regulations | DIN EN 50178 |
| Rated insulation voltage | 250 V AC |
| 250 V AC | |
| Rated surge voltage/insulation | Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path Basic insulation 4 kV between all current paths and housing |
| Degree of pollution | 2 |
| Overvoltage category | III |
| Shock | 15g |
| Vibration (operation) | 10 Hz ... 150 Hz, 2g |
| Conformance | CE-compliant |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |