View larger
AXL F PSDO8/3 1F 2701560 PHOENIX CONTACT Safety module
AXL F PSDO8/3 1F
2701560
PHOENIX CONTACT
1 Pcs.
Automation > Fieldbus, decentr. periphery - digital I/O module
Safety
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Engineered for machine safety loops, this Phoenix Contact AXL F PSDO8/3 1F safety module manages critical interlocking and emergency stop signals within industrial control systems. Such devices enforce safe operational states by reliably interrupting power to hazardous machine zones when faults or trip conditions occur.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Width: 53.6 mm
- Height: 126.1 mm
- Depth: 54 mm
- Note on dimensions: Housing dimensions
- Note on application Note on application: Only for industrial use
- Axioline F local bus Connection method: Bus base module
- Module Input address area: 5 Byte
- Output address area: 5 Byte
- Required parameter data: 22 Byte ((I-and F-parameters))
- Required configuration data: 10 Byte
- Digital: Output name: Digital outputs
- Connection method: Direct plug-in technology
- Connection technology: 2-, 3-conductor
- Number of outputs: 4 (for 2-channel assignment)
- Output voltage: 24 V DC
- Output current: max. 2 A (per channel)
More info
▲| Dimensional drawing | |
| Width | 53.6 mm |
| Height | 126.1 mm |
| Depth | 54 mm |
| Note on dimensions | Housing dimensions |
| Note on application | |
| Note on application | Only for industrial use |
| Axioline F local bus | |
| Connection method | Bus base module |
| Module | |
| Input address area | 5 Byte |
| Output address area | 5 Byte |
| Required parameter data | 22 Byte ((I-and F-parameters)) |
| Required configuration data | 10 Byte |
| Digital: | |
| Output name | Digital outputs |
| Connection method | Direct plug-in technology |
| Connection technology | 2-, 3-conductor |
| Number of outputs | 4 (for 2-channel assignment) |
| 8 (for 1-channel assignment) | |
| 8 | |
| Protective circuit | Overload protection, freewheeling circuit for inductive loads,Discharge circuit for accelerated discharge of capacitive loads |
| Output voltage | 24 V DC |
| Output current | max. 2 A (per channel) |
| max. 1.5 A (per channel according to CULUS) | |
| max. 4 A (per group) | |
| max. 3 A (per group according to CULUS) | |
| max. 8 A (Total current of all outputs; Please observe the notes in the user manual.) | |
| max. 6 A (Total current of all outputs according to CULUS) | |
| Maximum output current per channel | 2 A |
| Maximum output current per module / terminal block | 8 A |
| Permissible cable length | max. 1000 m (Forward and return line in total) |
| Behavior with overload | Affected output is disabled and a diagnostic message is generated. |
| Product type | I/O component |
| Product family | Axioline F |
| Application | Functional safety |
| PROFIsafe | |
| only for connection to Phoenix Contact or Siemens controller | |
| Type | modular |
| Data management status | |
| Article revision | 11 |
| Maximum power dissipation for nominal condition | 4 W |
| Transmission medium | Copper |
| Potentials | |
| Protective circuit | Protection against polarity reversal, EMC protective circuit, undervoltage detection |
| Potentials: Axioline F local bus supply (UBus) | |
| Supply voltage | 5 V DC (via bus base module) |
| Current draw | max. 280 mA |
| typ. 260 mA (all outputs set; supply by UOof 19.2 V DC ... 30 V DC) | |
| Potentials: Supply for digital output modules (UO) | |
| Supply voltage | 24 V DC |
| Supply voltage range | 19.2 V DC ... 30 V DC (including all tolerances, including ripple) |
| Current draw | typ. 25 mA (all outputs set; supply from UOwith 30 V DC; without supply to the actuators) |
| Connection technology | |
| Connection name | Axioline F connector |
| Conductor connection | |
| Connection method | Push-in connection |
| Conductor cross section rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Axioline F connector | |
| Connection method | Push-in connection |
| Conductor cross section, rigid | 0.2 mm² ... 1.5 mm² |
| Conductor cross section, flexible | 0.2 mm² ... 1.5 mm² |
| Conductor cross section AWG | 24 ... 16 |
| Ambient conditions | |
| Ambient temperature (operation) | -35 °C ... 60 °C (Mounting position: any) |
| Degree of protection | IP20 |
| Air pressure (operation) | 70 kPa ... 108 kPa (up to 3000 m above sea level) |
| Air pressure (storage/transport) | 66 kPa ... 108 kPa (up to 3500 m above sea level) |
| Ambient temperature (storage/transport) | -40 °C ... 85 °C |
| Permissible humidity (operation) | 10 % ... 75 % (on average, 85% infrequently, non-condensing) |
| Permissible humidity (storage/transport) | 10 % ... 75 % (non-condensing) |
| Protection class | III (IEC 61140, EN 61140, VDE 0140-1) |
| Mounting type | DIN rail mounting |