Serving as a centralized junction node, the Phoenix Contact SACB-8/ 8-30,0PUR SCO P 1419609 PHOENIX CONTACT Sensor/actuator box SACB-8/ 8-30,0PUR SCO P 1419609 is engineered to handle multiple field connections. These distribution blocks simplify the physical wiring of automated processes by consolidating scattered input lines into a single streamlined trunk cable. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Length of the preassembled cable (EF007300): 30 m
- Cable length configurable (EF007301): No
- Number of sensor-/actuator-slots (EF006939): 8
- Number of channels per connector slot (EF006885): 1
- Number of poles sensor/actuator slots (EF007402): 4
- Rated voltage (EF000228): 120 V
- Operating voltage (EF003983): 120 V
- Max. current carrying capacity per socket (EF004038): 2 A
- Max. total current (EF004039): 12 A
- Material of contact surface (EF004020): Gold
- Material insulation body (EF007543): Polyamide (PA)
- With LED indication (EF005950): No
- With potential separation (EF003272): No
- Connection for NPN-sensors (EF006817): No
- Fix cable version suitable for cable guide chain (EF007461): No
- Degree of protection (IP) (EF005474): IP65
More info
▲Sensor/actuator box, application: Standard, number of slots: 8, number of positions: 4, coding: A - standard, slot assignment: single, status display: No; master cable connection: Fixed connection 180°, PUR/PVC, cable length: 30 m, shielding: no
Key Commercial Data
| Orderkey | 1419609 |
|---|---|
| Packing unit | 1 |
| GTIN | 4055626176765 |
| Custom tariff number | 85444290 |
General
| Rated voltage | 120 V |
|---|---|
| Current carrying capacity per I/O signal | 2 A |
| Current carrying capacity per slot | 4 A |
| Total rated current | 12 A |
| Number of positions | 4 |
| Number of slots | 8 |
| Flammability rating according to UL 94 | V0 |
Ambient conditions
| Degree of protection | IP65 |
|---|---|
| IP67 | |
| Ambient temperature (operation) | -40 °C ... 90 °C (for fixed installation) |
| -5 °C ... 80 °C (for flexible installation) |
Master cable data/connection data
| Connection method | Fixed connection |
|---|---|
| Length of cable | 30 m |
Insulation material
| Housing material | PBT |
|---|---|
| Material of the moulding mass | PUR |
| Contact material | Cu alloy |
| Contact surface material | gold-plated |
| Contact carrier material | PA |
| Material of threaded sleeve | PBT |
| O-ring material | NBR |
Pin assignment
| Slot/position = Wire color or connection | 1 / 4 (A) = WH |
|---|---|
| 2 / 4 (A) = GN | |
| 3 / 4 (A) = YE | |
| 4 / 4 (A) = GY | |
| 5 / 4 (A) = PK | |
| 6 / 4 (A) = RD | |
| 7 / 4 (A) = BK | |
| 8 / 4 (A) = VT | |
| 1-8 / 1 (+ 120 V) = BN | |
| 1-8 / 3 (0 V) = BU | |
| 1-8 / 5 (PE) = GN/YE |
Standards and Regulations
| Standard designation | M12 connector |
|---|---|
| Standards/regulations | IEC 61076-2-101 |
| Flammability rating according to UL 94 | V0 |
Classifications
eCl@ss
| eCl@ss 5.1 | 27250300 |
|---|---|
| eCl@ss 6.0 | 27279200 |
| eCl@ss 7.0 | 27279219 |
| eCl@ss 8.0 | 27279219 |
| eCl@ss 9.0 | 27440108 |
ETIM
| ETIM 5.0 | EC002585 |
|---|---|
| ETIM 6.0 | EC002585 |
| ETIM 7.0 | EC002585 |
UNSPSC
| UNSPSC 13.2 | 31251501 |
|---|