View larger
SAC-8P-45,0-28X/M12FS OD 1417918 PHOENIX CONTACT Sensor/actuator cable SAC-8P-45,0-28X/M12FS OD 1417918
SAC-8P-45,0-28X/M12FS OD
1417918
PHOENIX CONTACT
25 Pcs.
Automation > Sensor-actuator patch cord
Industrial Field Connectivity (IFC)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact SAC-8P-45,0-28X/M12FS OD sensor/actuator cable provides extended-reach connectivity for complex monitoring and control architectures. Long-run multi-core cabling allows remote sensors and actuators to communicate reliably with centralized control cabinets.
Pricing, availability, and lead time are confirmed per enquiry through an RFQ.
- Number of poles (EF001391): 8
- Cable length (EF000536): 45 m
- Halogen free (EF000025): Yes
- With LED indication (EF005950): No
- Screened (EF000881): No
- Cable type (EF000081): Multi-core
- Vulcanize (EF004115): Yes
- Rated current In (EF008250): 2 A
- Rated voltage (EF000228): 30 V
- Degree of protection (IP) (EF005474): IP65
More info
▲Sensor/actuator cable, 8-position, PE-X halogen-free, black-gray RAL 7021, cable length: 45 m, for outdoor applications, with high-grade steel knurl
Key Commercial Data
| Orderkey | 1417918 |
|---|---|
| Packing unit | 1 |
| GTIN | 4055626128689 |
| Custom tariff number | 85444290 |
Dimensions
| Length of cable | 45 m |
|---|
General
| Rated current at 40°C | 2 A |
|---|---|
| Rated voltage | 30 V AC |
| 30 V DC | |
| Number of positions | 8 |
| Standards/regulations | M12 connector IEC 61076-2-101 |
| Status display | No |
| Protective circuit/component | unwired |
| Degree of pollution | 3 |
Material
| Flammability rating according to UL 94 | V0 |
|---|
Standards and Regulations
| Standard designation | M12 connector |
|---|---|
| Standards/regulations | IEC 61076-2-101 |
| Flammability rating according to UL 94 | V0 |
Cable
| Cable type | PE-X black |
|---|---|
| Cable type (abbreviation) | 28X |
| Cable abbreviation | Li2X2X |
| Conductor cross section | 8x 0.25 mm² |
| AWG signal line | 24 |
| Conductor structure signal line | 32x 0.10 mm |
| Core diameter including insulation | 1.17 mm ±0.02 mm |
| Thickness, insulation | approx. 0.25 mm (Core insulation) |
| Wire colors | white, brown, green, yellow, gray, pink, blue, red |
| Overall twist | 8 wires around filler to the core |
| Length of twist, overall twist | 67 mm |
| External sheath, color | black-gray RAL 7021 |
| Outer sheath thickness | approx. 1.3 mm |
| External cable diameter D | 6.8 mm ±0.2 mm |
| Minimum bending radius, fixed installation | 5 x D |
| Minimum bending radius, flexible installation | 10 x D |
| Number of bending cycles | 2000000 |
| Minimum bending radius, drag chain applications | 10 x D |
| Traversing path | 10 m |
| Traversing rate | 3 m/s |
| Acceleration | 10 m/s² |
| Cable weight | 65 kg/km |
| Outer sheath, material | PE-X |
| Material, filler | PP yarn |
| Material conductor insulation | PE-X |
| Conductor material | Bare Cu litz wires |
| Insulation resistance | ≥ 100 MΩ*km (at 20 °C) |
| Conductor resistance | ≤ 78 Ω/km (at 20 °C) |
| Nominal voltage, cable | ≤ 300 V AC |
| Test voltage, cable | ≥ 3000 V AC (Spark test) |
| Special properties | Irradiated |
| Flame resistance | According to DIN EN 60332-1-2 |
| according to DIN EN 50266-2-5 | |
| Halogen-free | in accordance with DIN VDE 0472 part 815 |
| in accordance with DIN EN 50267-2-1 | |
| Resistance to oil | According to DIN EN 60811-2-1, 168 h at 100°C |
| According to DIN EN 50306 | |
| Other resistance | Resistance to fuels according to IEC 60811, 168 h at 70°C |
| UV resistant according to DIN VDE 0276-605 | |
| Ambient temperature (operation) | -40 °C ... 105 °C (cable, fixed installation) |
| -15 °C ... 105 °C (cable, flexible installation) | |
| 20 °C ±5 °C (cable, drag chain applications) |
Environmental Product Compliance
| REACh SVHC | |
|---|---|
| Lead 7439-92-1 | |
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |
Classifications
eCl@ss
| eCl@ss 5.1 | 27061801 |
|---|---|
| eCl@ss 6.0 | 27279200 |
| eCl@ss 7.0 | 27279218 |
| eCl@ss 8.0 | 27279218 |
| eCl@ss 9.0 | 27060311 |
ETIM
| ETIM 5.0 | EC001855 |
|---|---|
| ETIM 6.0 | EC001855 |
| ETIM 7.0 | EC001855 |
UNSPSC
| UNSPSC 13.2 | 31251501 |
|---|