View larger
SAC-5P-15,0-280/M12FSL FE 1100247 PHOENIX CONTACT Power cable, 5-position, PUR halogen-free, gray RAL 7001, ..
SAC-5P-15,0-280/M12FSL FE
1100247
PHOENIX CONTACT
25 Pcs.
Automation > Sensor-actuator patch cord
Industrial Field Connectivity (IFC)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact power cable (SAC-5P-15,0-280/M12FSL FE) is designed to safely route electrical currents and control signals between industrial power supplies and field devices. Premade cable assemblies streamline installation and minimize downtime during maintenance operations.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electrical connection, box-sided (EF005524): M12
- Type of plug-in contact, box-sided (EF008386): Female (bus)
- Positioning cable feed, box-sided (EF005927): Straight
- Cable length (EF000536): 15 m
- Halogen free (EF000025): Yes
- With LED indication (EF005950): No
- Screened (EF000881): No
- Vulcanize (EF004115): No
- Rated voltage (EF000228): 63 V
- Degree of protection (IP) (EF005474): IP65
More info
▲General
| Rated current at 40°C | 16 A |
|---|---|
| Rated voltage | 63 V DC |
| Number of positions | 5 |
| Insulation resistance | ≥ 100 MΩ |
| Coding | L - Power |
| Standards/regulations | M12 connector IEC 61076-2-111 |
| Status display | No |
| Protective circuit/component | unwired |
| Overvoltage category | III |
| Degree of pollution | 3 |
| Insertion/withdrawal cycles | ≥ 100 |
| Torque | 0.4 Nm (M12 connector) |
Material
| Flammability rating according to UL 94 | V0 |
|---|---|
| Contact material | CuZn |
| Contact surface material | Ni/Au |
| Contact carrier material | PA |
| Material of grip body | PP |
| Material, knurls | Zinc die-cast, nickel-plated |
Standards and Regulations
| Standards/specifications | M12 connector IEC 61076-2-111 |
|---|---|
| Flammability rating according to UL 94 | V0 |
Cable
| Cable type | PUR halogen-free gray |
|---|---|
| Cable type (abbreviation) | 280 |
| UL AWM style | 20233 / 10493 (80°C/300 V) |
| Conductor cross section | 5x 2.5 mm² |
| AWG power supply | 14 |
| Conductor structure, voltage supply | 141x 0.15 mm |
| Core diameter including insulation | 2.85 mm ±0.1 mm |
| Thickness, insulation | ≥ 0.31 mm |
| Wire colors | Brown, white, blue, black, gray |
| External sheath, color | gray RAL 7001 |
| Outer sheath thickness | approx. 0.76 mm |
| External cable diameter D | 9.65 mm ±0.25 mm |
| Minimum bending radius, fixed installation | 5 x D |
| Minimum bending radius, flexible installation | 10 x D |
| Number of bending cycles | 4000000 |
| Minimum bending radius, drag chain applications | 10 x D |
| Traversing path | 10 m |
| Traversing rate | 3 m/s |
| Acceleration | 10 m/s² |
| Cable weight | 185 kg/km |
| Outer sheath, material | PUR |
| Material conductor insulation | PP |
| Conductor material | Bare Cu litz wires |
| Insulation resistance | ≥ 1 GΩ*km (at 20 °C) |
| Conductor resistance | ≤ 8 Ω/km (at 20 °C) |
| Nominal voltage, cable | ≤ 300 V AC |
| Test voltage, cable | ≥ 3000 V AC (Spark test) |
| Flame resistance | According to UL 758/1581 (Cable Flame) |
| according to UL 758/1581 FT1 | |
| According to DIN EN 60332-1-2 | |
| Halogen-free | in accordance with DIN VDE 0472 part 815 |
| in accordance with DIN EN 50267-2-1 | |
| Resistance to oil | according to DIN EN 60811-404, 168 h at 100 °C |
| Other resistance | Hydrolysis and microbe resistant as per VDE 0282 section 10 |
| Low adhesion | |
| abrasion-resistant | |
| Resistant to salt water | |
| Ambient temperature (operation) | -50 °C ... 80 °C (cable, fixed installation) |
| -30 °C ... 80 °C (cable, flexible installation) |