View larger
SAC-3P-M12MR/ 5,0-280 VC 1080932 PHOENIX CONTACT Sensor/actuator cable SAC-3P-M12MR/ 5,0-280 VC 1080932
SAC-3P-M12MR/ 5,0-280 VC
1080932
PHOENIX CONTACT
50 Pcs.
Automation > Sensor-actuator patch cord
Industrial Field Connectivity (IFC)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
This SAC-3P-M12MR/ 5,0-280 VC 1080932 PHOENIX CONTACT Sensor/actuator cable bridges the gap between field instrumentation and control hardware. Sensor and actuator cables ensure secure electrical connections for transmitting telemetry and control signals in factory machinery. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Orderkey: 1080932
- Packing unit: 1
- GTIN: 4055626806938
- Custom tariff number: 85444290
- Length of cable: 5 m
- Degree of protection: IP65
- Rated current at 40°C: 4 A
- Rated voltage: 250 V AC
- Number of positions: 3
- Insulation resistance: ≥ 100 MΩ
- Coding: A - standard
- Overvoltage category: II
- Degree of pollution: 3
- Torque: 0.4 Nm
- Flame resistance: according to DIN VDE 0482
- Resistance to oil: largely oil-resistant
More info
▲Sensor/actuator cable, 3-position, PUR halogen-free, gray RAL 7001, Plug angled M12, A-coded, on free cable end, cable length: 5 m
Key Commercial Data
| Orderkey | 1080932 |
|---|---|
| Packing unit | 1 |
| GTIN | 4055626806938 |
| Custom tariff number | 85444290 |
Dimensions
| Length of cable | 5 m |
|---|
Ambient conditions
| Degree of protection | IP65 |
|---|---|
| IP67 |
General
| Rated current at 40°C | 4 A |
|---|---|
| Rated voltage | 250 V AC |
| 250 V DC | |
| Number of positions | 3 |
| Insulation resistance | ≥ 100 MΩ |
| Coding | A - standard |
| Overvoltage category | II |
| Degree of pollution | 3 |
| Torque | 0.4 Nm |
Standards and Regulations
| Flame resistance | according to DIN VDE 0482 |
|---|---|
| According to DIN EN 50265-2-1 | |
| Resistance to oil | largely oil-resistant |
Cable
| Cable type | PUR halogen-free gray |
|---|---|
| Cable type (abbreviation) | 280 |
| Cable abbreviation | Li9Y11Y-HF |
| UL AWM style | 20549 |
| Conductor cross section | 3x 0.5 mm² (Signal line) |
| AWG signal line | 20 |
| Conductor structure signal line | 28x 0.15 mm |
| Core diameter including insulation | 1.5 mm ±0.05 mm (Signal line) |
| Wire colors | black 1, black 2, green/yellow |
| Overall twist | Wires twisted in layers |
| External sheath, color | gray RAL 7001 |
| External cable diameter D | 4.5 mm ±0.2 mm |
| Smallest bending radius, fixed installation | 22.5 mm |
| Number of bending cycles | 15000000 |
| Bending radius | 50 mm |
| Traversing path | 0.9 m |
| Traversing rate | 5 m/s |
| Acceleration | 30 m/s² |
| Outer sheath, material | PUR |
| Material conductor insulation | PP |
| Conductor material | Bare Cu litz wires |
| Insulation resistance | ≥ 20 MΩ*km |
| Conductor resistance | 39 Ω/km (at 20 °C) |
| Nominal voltage, cable | 300 V |
| Test voltage, cable | 1200 V |
| Flame resistance | according to DIN VDE 0482 |
| According to DIN EN 50265-2-1 | |
| Resistance to oil | largely oil-resistant |
| Ambient temperature (operation) | -40 °C ... 80 °C (cable, fixed installation) |
| -20 °C ... 80 °C (cable, flexible installation) |
Classifications
eCl@ss
| eCl@ss 6.0 | 27279200 |
|---|---|
| eCl@ss 7.0 | 27279218 |
| eCl@ss 9.0 | 27060311 |
ETIM
| ETIM 6.0 | EC001855 |
|---|---|
| ETIM 7.0 | EC001855 |