PHOENIX CONTACT VAL-SEC-T2-380DC-P VAL-SEC-T2-380DC-P 2907880 PHOENIX CONTACT Type 2 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

VAL-SEC-T2-380DC-P 2907880 PHOENIX CONTACT Type 2 surge protection plug

VAL-SEC-T2-380DC-P

2907880

PHOENIX CONTACT

1 Pcs.

Type 2 surge protection plug Replacement connector for surge protection device from the VALVETRAB SEC product line for DC power sources.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Phoenix Contact VAL-SEC-T2-380DC-P Type 2 surge protection plug delivers targeted overvoltage protection for direct current industrial networks by safely diverting electrical transients to earth. This modular plug-in device is engineered to fit standard base elements inside control cabinets, ensuring uninterrupted operation of critical DC machinery. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Orderkey: 2907880
  • Packing unit: 1 pc
  • Note: Made to Order (non-returnable)
  • Catalog page: Page 51 (C-4-2017)
  • GTIN: 4055626245058
  • Weight per Piece (excluding packing): 61.600 g
  • Custom tariff number: 85363030
  • Country of origin: DE (Germany)
  • Height: 46.4 mm
  • Width: 11.7 mm
  • Depth: 59.4 mm
  • Horizontal pitch: 0.6 Div.
  • Degree of protection: IP20
  • Ambient temperature (operation): -40 °C ... 80 °C
  • Ambient temperature (storage/transport): -40 °C ... 80 °C
  • Altitude: ≤ 6000 m (amsl (above mean sea level))

More info

▲

Key Commercial Data

Orderkey2907880
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 51 (C-4-2017)
GTIN4055626245058
Weight per Piece (excluding packing)61.600 g
Custom tariff number85363030
Country of originDE (Germany)

Dimensions

Height46.4 mm
Width11.7 mm
Depth59.4 mm
Horizontal pitch0.6 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 6000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (10 ... 500 Hz / 2.5 h / X, Y, Z)

General

IEC test classificationII
T2
EN typeT2
IEC power supply systemDC
Mode of protection(DC+) - (DC-)
(DC+/DC-) - PE
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN350 V DC ... 400 V DC
Maximum continuous voltage UC450 V DC
Residual current IPE≤ 350 µA DC
Nominal discharge current In(8/20) µs20 kA
Maximum discharge current Imax(8/20) µs40 kA
Impulse discharge current (10/350) µs, charge0.5 As
Impulse discharge current (10/350) µs, specific energy0.25 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp1 kA
Short-circuit current rating ISCCR0.1 kA (without backup fuse)
6 kA (for 20 A gG/B backup fuse)
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.5 kV (at In)
≤ 1.3 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 4 kA)
≤ 1 kV (at 2 kA)
TOV behavior at UT551 V DC (5 s / withstand mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring20 A (gG / B at ISCCR> 200 A)
10 A (gG / B at ISCCR> 100 A)
Max. backup fuse with branch wiring20 A (gG / B at ISCCR> 200 A)
10 A (gG / B at ISCCR> 100 A)

Connection data

Connection methodpluggable

UL specifications

SPD Type4CA
Maximum continuous operating voltage MCOV450 V DC
Nominal voltage400 V DC
Mode of protection(DC+) - G
(DC-) - G
Power distribution systemDC
Measured limiting voltage MLV1640 V
Nominal discharge current In20 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

China RoHSEnvironmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

Classifications


Product Datasheet