RSCWE 6-3/9 3969925 PHOENIX CONTACT Test terminal strip
RSCWE 6-3/9
3969925
PHOENIX CONTACT
1 Pcs.
Automation > (Knife) disconnect terminal block
Enclosures connectivity
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Phoenix Contact RSCWE 6-3/9 test terminal strip facilitates organized measurement tasks and circuit monitoring within complex automation assemblies. Panel builders rely on these specialized blocks to route and test current transformers or secondary control wiring efficiently. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Accessory (EF013236): No
- Spare part (EF013237): No
More info
▲Key Commercial Data
| Orderkey | 3969925 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 614 (C-1-2017) |
| GTIN | 4055626272658 |
| Weight per Piece (excluding packing) | 402.000 g |
| Custom tariff number | 85366990 |
| Country of origin | PL (Poland) |
General
| Number of positions | 9 |
|---|---|
| Number of levels | 1 |
| Number of connections | 18 |
| Potentials | 9 |
| Nominal cross section | 6 mm² |
| Color | gray |
| Insulating material | PA |
| Flammability rating according to UL 94 | V0 |
| Rated surge voltage | 4 kV |
| Test surge voltage | 5 kV |
| Overvoltage category | III |
| Insulating material group | I |
| Maximum power dissipation for nominal condition | 1.31 W |
| Ambient temperature (operation) | -60 °C ... 100 °C |
| Maximum load current | 30 A (with 10 mm² conductor cross section) |
| Current Ith | 24 A |
| Nominal voltage UN | 400 V AC/DC |
| Open side panel | No |
| Terminal block mounting | 0.8 Nm ... 1 Nm |
| Shock protection test specification | DIN EN 50274 (VDE 0660-514):2002-11 |
| Back of the hand protection | guaranteed |
| Note regarding shock protection | |
| Result of surge voltage test | Test passed |
| Surge voltage test setpoint | 4.8 kV |
| Result of power-frequency withstand voltage test | Test passed |
| Power frequency withstand voltage setpoint | 1.89 kV |
| Result of the test for mechanical stability of terminal points (5 x conductor connection) | Test passed |
| Result of tight fit on support | Test passed |
| Setpoint | 5 N |
| Result of voltage-drop test | Test passed |
| Requirements, voltage drop | ≤ 4.8 mV |
| Result of temperature-rise test | Test passed |
| Short circuit stability result | Test passed |
| Conductor cross section short circuit testing | 4 mm² |
| Short-time current | 300 A |
| Conductor cross section short circuit testing | 4 mm² |
| Short-time current | 500 A |
| Conductor cross section short circuit testing | 4 mm² |
| Short-time current | 150 A |
| Conductor cross section short circuit testing | 4 mm² |
| Short-time current | 1250 A |
| Result of thermal test | Test passed |
| Proof of thermal characteristics (needle flame) effective duration | 30 s |
| Oscillation, broadband noise test result | Test passed |
| Test specification, oscillation, broadband noise | DIN EN 50155 (VDE 0115-200):2008-03 |
| Test spectrum | Service life test category 2, bogie-mounted |
| Test frequency | f1= 5 Hz to f2= 250 Hz |
| ASD level | 6.12 (m/s2)2/Hz |
| Acceleration | 3.12 g |
| Test duration per axis | 5 h |
| Test directions | X-, Y- and Z-axis |
| Shock test result | Test passed |
| Test specification, shock test | DIN EN 50155 (VDE 0115-200):2008-03 |
| Shock form | Half-sine |
| Acceleration | 30g |
| Shock duration | 18 ms |
| Number of shocks per direction | 3 |
| Test directions | X-, Y- and Z-axis (pos. and neg.) |
| Relative insulation material temperature index (Elec., UL 746 B) | 130 °C |
| Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) | 125 °C |
| Static insulating material application in cold | -60 °C |
| Behavior in fire for rail vehicles (DIN 5510-2) | Test passed |
| Flame test method (DIN EN 60695-11-10) | V0 |
| Oxygen index (DIN EN ISO 4589-2) | >32 % |
| NF F16-101, NF F10-102 Class I | 2 |
| NF F16-101, NF F10-102 Class F | 2 |
| Surface flammability NFPA 130 (ASTM E 162) | passed |
| Specific optical density of smoke NFPA 130 (ASTM E 662) | passed |
| Smoke gas toxicity NFPA 130 (SMP 800C) | passed |
| Calorimetric heat release NFPA 130 (ASTM E 1354) | 27,5 MJ/kg |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Connection data
| Connection method | Ring cable lug |
|---|---|
| Connection in acc. with standard | IEC 60947-7-1 |
| Conductor cross section flexible min. | 0.5 mm² |
| Conductor cross section flexible max. | 10 mm² |
| Min. AWG conductor cross section, flexible | 24 |
| Max. AWG conductor cross section, flexible | 8 |
| 2 conductors with same cross section, solid min. | 0.5 mm² |
| 2 conductors with same cross section, solid max. | 6 mm² |
| 2 conductors with same cross section, stranded min. | 0.5 mm² |
| 2 conductors with same cross section, stranded max. | 6 mm² |
| Cable lug connection according to standard | DIN 46234 |
| Min. cross section for cable lug connection | 0.5 mm² |
| Max. cross section for cable lug connection | 10 mm² |
| Hole diameter, min. | 4.3 mm |
| Cable lug width, max. | 8 mm |
| Bolt diameter | 4.1 mm |
| Cable lug connection according to standard | DIN 46237 |
| Min. cross section for cable lug connection | 0.5 mm² |
| Max. cross section for cable lug connection | 10 mm² |
| Hole diameter, min. | 4.3 mm |
| Cable lug width, max. | 8 mm |
| Bolt diameter | 4.1 mm |
| Stripping length | 12 mm |
| Internal cylindrical gage | A5 |
| Screw thread | No 8 UNC |
| Tightening torque, min | 1.5 Nm |
| Tightening torque max | 1.8 Nm |
Mounting
| Mounting type | Wall mounting |
|---|---|
| Plate thickness | 1 mm ... 4 mm |
| Min. tightening torque of the mounting screw: | 0.8 Nm |
| Max. tightening torque of the mounting screw: | 1 Nm |
Standards and Regulations
| Connection in acc. with standard | IEC 60947-7-1 |
|---|---|
| Flammability rating according to UL 94 | V0 |
| Fire protection for rail vehicles (DIN EN 45545-2) R22 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R23 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R24 | HL 1 - HL 3 |
| Fire protection for rail vehicles (DIN EN 45545-2) R26 | HL 1 - HL 3 |
Environmental Product Compliance
| China RoHS | Environmentally friendly use period: unlimited = EFUP-e |
|---|---|
| No hazardous substances above threshold values |