PHOENIX CONTACT FLK 50-PA/EZ-DR/KS/1600/YUC FLK 50-PA/EZ-DR/KS/1600/YUC 2321538 PHOENIX CONTACT Front adapters View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FLK 50-PA/EZ-DR/KS/1600/YUC 2321538 PHOENIX CONTACT Front adapters

FLK 50-PA/EZ-DR/KS/1600/YUC

2321538

PHOENIX CONTACT

1 Pcs.

Front adapters Cast iron front adapter with fixed round cable and a 50-pole plug pin extruded on both sides for connecting Yokogawa control systems. Cable length: 16.0 m Cast front adapter with attached round cable and a 50-pos. socket strip injection-molded on both sides for the connection of Yokogawa controllers. Cable length: 16.0 m

Automation > Accessories/spare parts for controls
INTERFACE Components (IF)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

The Phoenix Contact FLK 50-PA/EZ-DR/KS/1600/YUC is a front adapter engineered to bridge system cabling between control hardware and specific automation I/O cards. Front adapters streamline multi-core signal routing in complex control cabinets, ensuring reliable interconnections in large-scale process automation. Pricing, availability, and lead time are confirmed per enquiry through an RFQ.

  • Product type: Front adapter
  • Data management status Article revision: 06
  • Operating voltage (DC): ≤ 30 V DC
  • Nominal operating mode: 100% operating factor
  • Current (Per path): ≤ 500 mA (uncoiled)
  • Supported controller YOKOGAWA STARDOM Suitable I/O card: NFDV151
  • Supported controller YOKOGAWA ProSafe-RS Suitable I/O card: SDV541
  • Connection 1 Connection in acc. with standard: based on IEC 60603-13
  • Connection method: Yokogawa, I/O cards compatible
  • Number of connections: 1
  • Number of positions: 50
  • Tightening torque: 0.5 Nm (Screw connection)
  • Insertion/withdrawal cycles: > 50
  • Pitch: 2.54 mm
  • Connection 2 Connection in acc. with standard: based on IEC 60603-13
  • Connection method: Yokogawa, KS compatible

More info

▲
Technical data

Product properties
Product typeFront adapter
Data management status
Article revision06

Electrical properties
Operating voltage (DC)≤ 30 V DC
Nominal operating mode100% operating factor
Current (Per path)≤ 500 mA (uncoiled)
Supported controller YOKOGAWA CS3000 CentumVP
Suitable I/O cardADV151
ADV551
Supported controller YOKOGAWA STARDOM
Suitable I/O cardNFDV151
NFDV551
Supported controller YOKOGAWA ProSafe-RS
Suitable I/O cardSDV541
SDV144
SDV521

Connection data
Connection 1
Connection in acc. with standardbased on IEC 60603-13
Connection methodYokogawa, I/O cards compatible
Number of connections1
Number of positions50
Tightening torque0.5 Nm (Screw connection)
Insertion/withdrawal cycles> 50
Pitch2.54 mm
Connection 2
Connection in acc. with standardbased on IEC 60603-13
Connection methodYokogawa, KS compatible
Number of connections1
Number of positions50
Tightening torque0.5 Nm (Screw connection)
Insertion/withdrawal cycles> 50
Pitch2.54 mm

Dimensions
Cable
Length16 m

Cable/line
50X0.14 [PVC]
UL AWM Style2464/1061
Number of positions50
Shieldedyes
Cable type50X0.14 [PVC]
Conductor typeAssembled shielded round cable
Conductor structure signal line7x 0.16 mm
AWG signal line26
Conductor cross section50x 0.14 mm²
Wire diameter incl. insulation1 mm ±0.03 mm
External cable diameter11.00 mm ±0.3 mm
Outer sheath, materialSemi-rigid PVC
External sheath, colorgray
Conductor materialTin-plated Cu litz wires
Cable resistance≤ 145 Ω/km (at 20 °C)
Insulation resistance≥ 20 MΩ*km (20 °C)
Smallest bending radius, fixed installation114 mm
Smallest bending radius, movable installation205 mm
Dynamic load capacity (bending)Max. bending cycles: 5000 (at a radius of ≥ 18x outside diameter)
Halogen-freeno
Flame resistanceIEC 60332-1-2 (raw cable)
VDE 0842, Part 332-1-2 (raw cable)
IEC 60332-3-22 (raw cable)
UL VW-1
CSA FT-1
Resistance to oilcan withstand occasional splashes (raw cable)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Degree of protection (Installation location)≥ IP54 (Installation location)
Ambient temperature (operation)-40 °C ... 70 °C (fixed installation)
-10 °C ... 70 °C (flexible installation)
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m

Approvals
UKCA
CertificateUKCA-compliant

Mounting
Mounting positionany

Notes
Notes on operationFor proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met.

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.