PHOENIX CONTACT RFC 4072R RFC 4072R 1136419 PHOENIX CONTACT High availability PLCnext Controller with redundancy functionality View larger
Images are for illustrative purposes only. Please refer to data sheet for details

RFC 4072R 1136419 PHOENIX CONTACT High availability PLCnext Controller with redundancy functionality

RFC 4072R

1136419

PHOENIX CONTACT

1 Pcs.

High availability PLCnext Controller with redundancy functionality

Automation > PLC CPU-module
Control Systems (CST)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

Built for mission-critical applications, this Phoenix Contact High availability PLCnext Controller with redundancy functionality provides robust processing power and fault-tolerant operation for continuous industrial processes. Redundant controllers secure maximum uptime in power generation, water treatment, and large continuous manufacturing operations by seamlessly switching control tasks upon hardware failure. Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Type: Stand-Alone
  • Product type: Controller
  • Product family: PLCnext Control
  • Insulation characteristics Protection class: III (IEC 61140, EN 61140, VDE 0140-1)
  • Display Diagnostics display: yes
  • Processor: Intel ® Core™ i5-6300U 2x 2.4 GHz (Standard)
  • Flash memory: 100 Mbyte (internal flash memory)
  • Retentive data storage: 2 Mbyte
  • IEC 61131 runtime system Program memory: 16 Mbyte
  • Data storage system: 32 Mbyte
  • PROFINET Device function: PROFINET-Controller
  • Number of supported devices: max. 256
  • Vendor ID: 00B0 hex / 176 dez
  • Function Diagnostics display: yes
  • Controller redundancy: yes
  • Safety function: No

More info

▲
Technical data

Product properties
TypeStand-Alone
Product typeController
Product familyPLCnext Control
Insulation characteristics
Protection classIII (IEC 61140, EN 61140, VDE 0140-1)
Pollution degree2 (when installed in a control cabinet or housing with IP54 degree of protection or higher)
Display
Diagnostics displayyes

System properties
ProcessorIntel®Core™ i5-6300U 2x 2.4 GHz (Standard)
Flash memory100 Mbyte (internal flash memory)
SD card from Phoenix Contact (for external flash memory, see accessories)
Retentive data storage2 Mbyte
IEC 61131 runtime system
Program memory16 Mbyte
Data storage system32 Mbyte
PROFINET
Device functionPROFINET-Controller
Number of supported devicesmax. 256
Vendor ID00B0hex/ 176dez
Function
Diagnostics displayyes
Controller redundancyyes
Safety functionNo
Functionality
Programming languages supportedInstruction list (IL)
Symbolic flowchart (SFC)
Ladder diagram (LD)
Function block diagram (FBD)
Structured text (ST)
C++
C#
Java
Python
Simulink
System requirements
Engineering toolPLCnext Engineer
Eclipse
Visual Studio
MATLAB®Simulink®
Application interfaceOPC UA
OPC UA Pub/Sub

Electrical properties
Power consumptiontyp. 25 W (Without fan module)
max. 35 W (With fan module)
Transmission mediumCopper
FO
Supply
Supply voltage24 V DC
Supply voltage range19.2 V DC ... 30 V DC (including ripple (3.6 VPP))
Power supply connectionVia COMBICON, max. conductor cross section 2.5 mm²
Real-time clock
Realtime clockintegrated (capacitive buffering)
Description realtime clock1.73 s/day = 20 ppm at 25 °C
Potentials
Protective circuitSurge protection of the supply voltage; electronic
Polarity reversal protection of the supply voltage; electronic

Connection data
Cross section AWG(converted acc. to IEC)
COMBICON connector
Conductor cross section, rigid0.2 mm² ... 2.5 mm²
Conductor cross section, flexible0.2 mm² ... 2.5 mm²
Conductor cross section AWG24 ... 12

Interfaces
Web serveryes
USB
Number of interfaces1
Connection methodUSB type A, socket
Ethernet
Bus systemRJ45
Number of interfaces4
Connection methodRJ45 jack
Note on the connection methodAuto negotiation and auto crossing, auto polarity exchange
Transmission speed10/100/1000 Mbps (LAN 1/LAN 2, half duplex or full duplex)
10/100 Mbps (LAN3.1/LAN3.2 (internally switched), half duplex or full duplex)

Dimensions
External dimensions
Width / Height / Depth122 mm / 182 mm / 173 mm (without fan module)
122 mm / 220 mm / 173 mm (With fan module)

Environmental and real-life conditions
Ambient conditions
Degree of protectionIP20
Ambient temperature (operation)0 °C ... 60 °C up to 2000 m above mean sea level (recommended: above 50°C with fan module)
0 °C ... 55 °C 2000 m ... 3000 m above mean sea level (With fan module only)
0 °C ... 50 °C 3000 m ... 4000 m above mean sea level (With fan module only)
Ambient temperature (storage/transport)-25 °C ... 70 °C
Permissible humidity (operation)10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)5 % ... 95 % (non-condensing)
Shock (operation)20g (in accordance with EN 60068-2-27/IEC 60068-2-27)
Vibration (operation)1g (in accordance with EN 60068-2-6/IEC 60068-2-6)
Air pressure (operation)60 kPa ... 108 kPa (up to 4000 m above mean sea level)
Air pressure (storage/transport)58 kPa ... 108 kPa (up to 4500 m above mean sea level)
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37Use of the device in these ambient conditions is prohibited.

EMC data
Conformance with EMC directivesImmunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN 61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN 61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Fast transients (burst)EN 61000-4-4/IEC 61000-4-4 Criterion B; Supply lines: 2 kV; Signal/data lines: 2 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN 61000-4-5/IEC 61000-4-5 Criterion B, supply lines: 0.5 kV, signal/data cables: 1 kV
Immunity test in accordance with EN 61000-6-2/IEC 61000-6-2 Conducted interferenceEN 61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Noise emission test in accordance with EN 61000-6-4/IEC 61000-6-4
Electromagnetic compatibilityConformance with EMC Directive 2014/30/EU

Mounting
Mounting typeDIN rail mounting

Product Datasheet

Electrica Online Product Datasheet Prepared from the current product description, catalog data and structured technical attributes.