View larger
ELR W3-230AC/500AC- 9I 2297060 PHOENIX CONTACT Hybrid motor starter
ELR W3-230AC/500AC-9I
2297060
PHOENIX CONTACT
1 Pcs.
Automation > Motor starter/Motor starter combination
INTERFACE Components (IF)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A Phoenix Contact hybrid motor starter (ELR W3-230AC/500AC-9I) utilizes advanced solid-state technology combined with mechanical relays to provide wear-resistant reversing operation for industrial motors. Hybrid starters offer high switching frequency and extended operating lifespans compared to traditional electromechanical contactor assemblies.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of motor starter: Reversing starter
- With short-circuit release: No
- Rated control supply voltage AC 50 Hz: 92 V
- Rated control supply voltage AC 60 Hz: 92 V
- Voltage type for actuating: AC
- Rated operation current Ie: 9 A
- Rated operation current at AC-3, 400 V: 9 A
- Overload release current setting: 1.5 A
- Temperature compensated overload protection: No
- Release class: CLASS 10
- Type of electrical connection of main circuit: Screw connection
- Suitable for rail mounting: Yes
- Number of command positions: 1
- Suitable for emergency stop: Yes
- External reset possible: Yes
- Degree of protection (IP): IP20
More info
▲Key Commercial Data
| Orderkey | 2297060 |
|---|---|
| Packing unit | 1 pc |
| Catalog page | Page 19 (C-7-2013) |
| GTIN | 4046356170598 |
| Weight per Piece (excluding packing) | 223.150 g |
| Custom tariff number | 85371098 |
| Country of origin | DE (Germany) |
| Width | 22.5 mm |
|---|---|
| Height | 106.6 mm |
| Depth | 113.7 mm |
| Ambient temperature (operation) | -25 °C ... 70 °C (observe derating) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Degree of protection | IP20 |
Device supply
| Rated control circuit supply voltage US | 230 V AC |
|---|---|
| Control supply voltage range | 92 V AC ... 253 V AC |
| Rated control supply current IS | 4 mA |
| Mains frequency | 40/100 Hz |
| Type of protection | Surge protection |
Input data
| Input name | Control input right/left |
|---|---|
| Rated actuating voltage UC | 230 V AC |
| Triggering voltage range | 92 V AC ... 253 V AC |
| Rated actuating current IC | 7 mA |
| Switching threshold | 44 V AC (“0” signal) |
| 85 V AC (“1” signal) | |
| Switching level | < 5 V DC (For EMERGENCY STOP) |
| Typical response time | < 35 ms |
| Typical turn-off time | < 80 ms |
Output data load output
| Output name | AC output |
|---|---|
| Rated operating voltage Ue | 500 V AC |
| Operating voltage range | 42 V AC ... 550 V AC |
| Rated operating current Ie | 9 A (AC-51) |
| 6.5 A (AC-53a) | |
| Mains frequency | 50/60 Hz |
| Load current range | 1.5 A ... 9 A (see to derating) |
| Trigger characteristic in acc. with IEC 60947-4-2 | Class 10A |
| Cooling time | 20 min. (for auto reset) |
| Leakage current | 0 mA |
| Residual voltage | < 0.5 V |
| Surge current | 100 A (t = 10 ms) |
| Type of protection | Surge protection |
Output data reply output
| Output name | Acknowledge output |
|---|---|
| Note | Confirmation: floating change-over contact, signal contact |
| Contact type | 1 PDT |
| Switching capacity according to IEC 60947-5-1 | 3 A (230 V, AC15) |
| 2 A (24 V, DC13) |
General
| Switching frequency | ≤ 2 Hz (Load-dependent) |
|---|---|
| Mounting position | Vertical (horizontal DIN rail) |
| Mounting type | DIN rail mounting |
| Assembly instructions | Can be aligned with spacing = 20 mm |
| Operating mode | 100% operating factor |
| Maximum power dissipation | 16.1 W |
| Minimum power dissipation | 2.6 W |
| Operating voltage display | Green LED |
| Status display | Yellow LED |
| Indication | Red LED |
| Connection name | Control circuits |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm ... 0.6 Nm |
| Connection name | Load circuit |
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm ... 0.6 Nm |
UL data
| SCCR | 100 kA (500 V AC (fuse: 30 A class CC/30 A class J (high fault))) |
|---|---|
| 5 kA (500 V AC (fuse: 20 A RK5 (standard fault))) | |
| FLA | 6.5 A (500 V AC) |
| Group installation | 20 A (class RK5, SCCR 5kA, #24 - 14 AWG max. solid and stranded) |
| 30 A (class CC or J, SCCR 100kA, #24 - 14 AWG max, solid and stranded) | |
| Category code | NLDX |
Insulation characteristics
| Rated insulation voltage | 500 V |
|---|---|
| Rated surge voltage | 6 kV |
| Overvoltage category | III |
| Degree of pollution | 2 |
| Designation | Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit |
| Insulation | Safe isolation (IEC 60947-1/EN 50178) at operating voltage ≤ 300 V AC |
| Basic isolation (IEC 60947-1) at operating voltage 300 ... 500 V AC | |
| Safe isolation (EN 50178) at operating voltage 300 ... 500 V AC | |
| Designation | Isolation characteristics between the control input and control supply voltage to auxiliary circuit |
| Insulation | Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC |
| Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC |
Standards and Regulations
| Designation | Standards/regulations |
|---|---|
| Standards/regulations | DIN EN 50178 |
| EN 60947 | |
| IEC 61508 | |
| ISO 13849 | |
| ATEX | II (2) G [Ex e] [Ex d] [Ex px] |
| II (2) D [Ex t] [Ex p] |
Approvals/conformities
| Safety Integrity Level according to IEC 61508 | ≤ 3 (Safe shutdown) |
|---|---|
| 2 (Motor protection) | |
| Category acc. to EN ISO 13849 | ≤ 3 (Safe shutdown) |
| Performance level according to ISO 13849 | ≤ e (Safe shutdown) |
| ATEX | II (2) G [Ex e] [Ex d] [Ex px] |
| II (2) D [Ex t] [Ex p] | |
| EU-type examination certificate | PTB 07 ATEX 3145 |
| UL certificate | NLDX.E228652 |
Environmental Product Compliance
| REACh SVHC | Lead 7439-92-1 |
|---|---|
| China RoHS | Environmentally Friendly Use Period = 50 |
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |