PHOENIX CONTACT FLT-SEC-P-T1-350/25-P FLT-SEC-P-T1-350/25-P 2905422 PHOENIX CONTACT Type 1 surge protection plug View larger
Images are for illustrative purposes only. Please refer to data sheet for details

FLT-SEC-P-T1-350/25-P 2905422 PHOENIX CONTACT Type 1 surge protection plug

FLT-SEC-P-T1-350/25-P

2905422

PHOENIX CONTACT

1 Pcs.

Type 1 surge protection plug Replacement connector for lightning current arresters from the FLASHTRAB SEC PLUS 350 product series, for the L-N and L-PEN sections.

Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)

Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.

Request a Quote

Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.

Request Quote

Product Overview

A Phoenix Contact type 1 surge protection plug defends heavy industrial facilities against direct lightning strikes and high-energy grid surges. Heavy-duty arrester plugs snap into mounting rails to absorb massive transient currents before they reach critical machinery.

Pricing, availability and lead time are confirmed per enquiry through an RFQ.

  • Accessory (EF013236): Yes
  • Spare part (EF013237): No

More info

▲

Key Commercial Data

Orderkey2905422
Packing unit1 pc
NoteMade to Order (non-returnable)
Catalog pagePage 31 (C-4-2017)
GTIN4046356950107
Weight per Piece (excluding packing)262.500 g
Custom tariff number85363010
Country of originDE (Germany)

Dimensions

Height46.6 mm
Width35.5 mm
Depth59.4 mm
Horizontal pitch2 Div.

Ambient conditions

Degree of protectionIP20
Ambient temperature (operation)-40 °C ... 80 °C
Ambient temperature (storage/transport)-40 °C ... 80 °C
Altitude≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation)5 % ... 95 %
Shock (operation)30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation)5g (5 - 500 Hz/2.5 h/X, Y, Z)

General

IEC test classificationI / II
T1 / T2
T1
I
EN typeT1 / T2
T1
IEC power supply systemTT
Mode of protectionL-N
L-PEN
Mounting typeon base element
Colorlight grey RAL 7035
Housing materialPA 6.6-FR 20% GF
PBT-FR
Degree of pollution2
Flammability rating according to UL 94V-0
TypeMale
Number of positions1
Surge protection fault messageoptical

Protective circuit

Nominal voltage UN240 V AC (TN)
240 V AC (TT)
Nominal frequency fN50 Hz (60 Hz)
Maximum continuous voltage UC350 V AC
Nominal discharge current In(8/20) µs25 kA
Maximum discharge current Imax(8/20) µs50 kA
Impulse discharge current (10/350) µs, charge12.5 As
Impulse discharge current (10/350) µs, specific energy160 kJ/Ω
Impulse discharge current (10/350) µs, peak value limp25 kA
Follow current interrupt rating Ifi50 kA
Short-circuit current rating ISCCR50 kA
Voltage protection level Up≤ 1.5 kV
Residual voltage Ures≤ 1.5 kV (at In)
Front of wave sparkover voltage at 6 kV (1.2/50) µs≤ 1.5 kV
TOV behavior at UT415 V AC (5 s / withstand mode)
457 V AC (120 min / withstand mode)
Response time tA≤ 100 ns
Max. backup fuse with branch wiring315 A (gG)

Additional technical data

Follow current interrupt rating Ifi100 kA (264 V AC)
Short-circuit current rating ISCCR100 kA (264 V AC)
Maximum discharge current Imax(8/20) µs100 kA (AS NZS 1768:2007)

Connection data

Connection methodpluggable

UL specifications

SPD Type1CA
Maximum continuous operating voltage MCOV350 V AC
Nom. voltage240 V AC
Mode of protectionL-N
L-G
Power distribution systemSingle phase
Nominal frequency50/60 Hz
Voltage protection rating VPR1500 V
Nominal discharge current In20 kA
Short-circuit current rating (SCCR)50 kA

Standards and Regulations

Standards/regulationsIEC 61643-11 2011
EN 61643-11 2012

Environmental Product Compliance

REACh SVHCLead 7439-92-1

Classifications