View larger
FLT-SEC-H-T1-264/25-P 2905968 PHOENIX CONTACT Type 1 surge protection plug
FLT-SEC-H-T1-264/25-P
2905968
PHOENIX CONTACT
1 Pcs.
Automation > Accessories/spare parts for surge protection power supply systems
Trabtech (TT)
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
FLT-SEC-H-T1-264/25-P 2905968 PHOENIX CONTACT Type 1 surge protection plug units deliver high-energy transient voltage suppression for industrial power distribution and automation panels. Systems engineers deploy these modular protection plugs to safely discharge severe electrical surges to ground before they damage connected assets. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Accessory (EF013236): Yes
- Spare part (EF013237): No
More info
▲Key Commercial Data
| Orderkey | 2905968 |
|---|---|
| Packing unit | 1 pc |
| Note | Made to Order (non-returnable) |
| Catalog page | Page 28 (C-4-2017) |
| GTIN | 4055626012032 |
| Weight per Piece (excluding packing) | 335.780 g |
| Custom tariff number | 85363030 |
| Country of origin | DE (Germany) |
Ambient conditions
| Degree of protection | IP20 |
|---|---|
| Ambient temperature (operation) | -40 °C ... 80 °C |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C |
| Altitude | ≤ 4000 m (amsl (above mean sea level)) |
| Permissible humidity (operation) | 5 % ... 95 % |
General
| IEC test classification | I / II |
|---|---|
| T1 / T2 | |
| EN type | T1 / T2 |
| IEC power supply system | TN-C |
| Mode of protection | L-PEN |
| Mounting type | on base element |
| Color | light grey RAL 7035 |
| Housing material | PA 6.6-FR 20% GF |
| PBT-FR | |
| Degree of pollution | 2 |
| Flammability rating according to UL 94 | V-0 |
| Type | Male |
| Number of positions | 1 |
| Surge protection fault message | optical |
Protective circuit
| Nominal voltage UN | 240 V AC (TN) |
|---|---|
| Nominal frequency fN | 50 Hz (60 Hz) |
| Maximum continuous voltage UC | 264 V AC |
| Nominal discharge current In(8/20) µs | 25 kA |
| Maximum discharge current Imax(8/20) µs | 50 kA |
| Impulse discharge current (10/350) µs, charge | 12.5 As |
| Impulse discharge current (10/350) µs, specific energy | 160 kJ/Ω |
| Impulse discharge current (10/350) µs, peak value limp | 25 kA |
| Follow current interrupt rating Ifi | 50 kA |
| Short-circuit current rating ISCCR | 50 kA |
| Voltage protection level Up | ≤ 1.5 kV |
| Residual voltage Ures | ≤ 1.5 kV (at In) |
| ≤ 2.5 kV (at 50 kA) | |
| ≤ 1.2 kV (at 12.5 kA) | |
| ≤ 1 kV (at 5 kA) | |
| ≤ 0.9 kV (at 2.5 kA) | |
| Front of wave sparkover voltage at 6 kV (1.2/50) µs | ≤ 1.5 kV |
| TOV behavior at UT | 415 V AC (5 s / withstand mode) |
| 460 V AC (120 min / withstand mode) | |
| Response time tA | ≤ 100 ns |
Additional technical data
| Follow current interrupt rating Ifi | 100 kA |
|---|---|
| Short-circuit current rating ISCCR | 100 kA |
| Maximum discharge current Imax(8/20) µs | 100 kA (AS NZS 1768:2007) |
| Maximum continuous voltage UC | 275 V AC |