View larger
DEK-REL- 24/I/1 2940171 PHOENIX CONTACT Relay Module
DEK-REL-24/I/1
2940171
PHOENIX CONTACT
1 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
Isolate and control low-voltage instrumentation signals with the Phoenix Contact DEK-REL-24/I/1 Relay Module. Compact electromechanical and solid-state relay blocks are standard additions to control enclosures, ensuring signal integrity and preventing ground loops between PLCs and field sensors. Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage AC 50 Hz (EF003978): 19.2 V
- Rated control supply voltage AC 60 Hz (EF003979): 19.2 V
- Rated control supply voltage DC (EF003980): 19.2 V
- Voltage type for actuating (EF008242): AC/DC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as change-over contact (EF008257): 0
- Type of switch contact (EF003358): Double contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Gold
More info
▲Key Commercial Data
| Orderkey | 2940171 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 438 (C-5-2017) |
| GTIN | 4017918079895 |
| Weight per Piece (excluding packing) | 19.000 g |
| Custom tariff number | 85364190 |
| Country of origin | CN (China) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Coil side
| Nominal input voltage UN | 24 V AC/DC |
|---|---|
| Input voltage range in reference to UN | 0.8 ... 1.1 |
| Typical input current at UN | 6.5 mA |
| Typical response time | 5 ms |
| Typical release time | 15 ms |
| Protective circuit | Bridge rectifier Bridge rectifier |
| Operating voltage display | Yellow LED |
| Power dissipation for nominal condition | 0.16 W |
Contact side
| Contact type | 1 N/O contact (double contact) |
|---|---|
| Type of switch contact | Double contact |
| Contact material | AgNi, hard gold-plated |
| Maximum switching voltage | 250 V AC |
| 125 V DC | |
| Minimum switching voltage | 0.1 V |
| Min. switching current | 1 mA |
| Maximum inrush current | 5 A |
| Limiting continuous current | 3 A (5 A up to 35°C at 24 V DC) |
| Interrupting rating (ohmic load) max. | 72 W (at 24 V DC) |
| 60 W (at 48 V DC) | |
| 50 W (at 60 V DC) | |
| 50 W (at 110 V DC) | |
| 750 VA (for 250 V AC) | |
| 120 W (at 24 V DC - up to 35°) |
General
| Type of note | Note on application |
|---|---|
| Note | Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
| Test voltage relay winding/relay contact | 2 kV AC (50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Net weight (SAP) | 19 g |
Connection data input side
| Connection name | Coil side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
Connection data output side
| Connection name | Contact side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |