View larger
DEK-REL- 24/1/AKT 2964063 PHOENIX CONTACT Relay Module
DEK-REL-24/1/AKT
2964063
PHOENIX CONTACT
1 Pcs.
Automation > Switching relay
Industrial Relays
Product condition, packaging, certifications and applicable manufacturer warranty terms are confirmed with the quotation.
Request a Quote
Pricing and availability are confirmed for each enquiry. Send this part and we will reply with price and lead time.
Request QuoteProduct Overview
A DEK-REL- 24/1/AKT 2964063 PHOENIX CONTACT Relay Module is an electromechanical switching assembly utilized in industrial control panels to isolate control circuits from load circuits, manage power distribution, and interface lower-voltage controllers with higher-voltage field devices. These modules provide reliable signal conversion and amplification across automated machinery and process control loops.
Pricing, availability and lead time are confirmed per enquiry through an RFQ.
- Type of electric connection (EF003961): Screw connection
- Complete with socket (EF003359): Yes
- With detachable clamps (EF003340): No
- With LED indication (EF005950): Yes
- Rated control supply voltage AC 50 Hz (EF003978): 19.2 V
- Rated control supply voltage AC 60 Hz (EF003979): 19.2 V
- Rated control supply voltage DC (EF003980): 19.2 V
- Voltage type for actuating (EF008242): AC/DC
- Drive, polarization (EF003355): Polarized
- Drive, switching attitude (EF003356): Mono stable
- Number of contacts as normally closed contact (EF008255): 0
- Number of contacts as normally open contact (EF008256): 1
- Number of contacts as change-over contact (EF008257): 0
- Type of switch contact (EF003358): Double contact
- With forced-guided contacts (EF003357): No
- Material of contact surface (EF004020): Gold
More info
▲Key Commercial Data
| Orderkey | 2964063 |
|---|---|
| Packing unit | 10 pc |
| Catalog page | Page 439 (C-5-2017) |
| GTIN | 4017918099374 |
| Weight per Piece (excluding packing) | 22.900 g |
| Custom tariff number | 85364190 |
| Country of origin | CN (China) |
Note
| Utilization restriction | EMC: class A product, see manufacturer's declaration in the download area |
|---|
Ambient conditions
| Ambient temperature (operation) | -20 °C ... 50 °C |
|---|---|
| Ambient temperature (storage/transport) | -20 °C ... 70 °C |
Coil side
| Nominal input voltage UN | 24 V AC/DC |
|---|---|
| Input voltage range in reference to UN | 0.8 ... 1.1 |
| Typical input current at UN | 6.5 mA |
| Typical response time | 5 ms |
| Typical release time | 15 ms |
| Protective circuit | Bridge rectifier Bridge rectifier |
| Operating voltage display | Yellow LED |
| Power dissipation for nominal condition | 0.16 W |
Contact side
| Contact type | 1 N/O contact |
|---|---|
| Type of switch contact | Double contact |
| Contact material | AgNi, hard gold-plated |
| Maximum switching voltage | 250 V AC |
| 125 V DC | |
| Minimum switching voltage | 0.1 V |
| Min. switching current | 1 mA |
| Maximum inrush current | 5 A |
| Limiting continuous current | 3 A (5 A up to 35°C at 24 V DC) |
| Interrupting rating (ohmic load) max. | 72 W (at 24 V DC) |
| 60 W (at 48 V DC) | |
| 50 W (at 60 V DC) | |
| 50 W (at 110 V DC) | |
| 750 VA (for 250 V AC) | |
| 120 W (at 24 V DC - up to 35°) |
General
| Type of note | Note on application |
|---|---|
| Note | Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place. |
| Test voltage relay winding/relay contact | 2 kV AC (50 Hz, 1 min.) |
| Operating mode | 100% operating factor |
| Mechanical service life | approx. 2x 107cycles |
| Mounting position | any |
| Assembly instructions | In rows with zero spacing |
| Net weight (SAP) | 22.9 g |
Connection data input side
| Connection name | Coil side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
Connection data output side
| Connection name | Contact side |
|---|---|
| Connection method | Screw connection |
| Stripping length | 8 mm |
| Screw thread | M3 |
| Conductor cross section solid | 0.2 mm² ... 2.5 mm² |
| Conductor cross section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross section AWG | 24 ... 14 |
| Torque | 0.5 Nm |
Standards and Regulations
| Connection in acc. with standard | CUL |
|---|---|
| Standards/regulations | IEC 60664 |
| EN 50178 | |
| Insulation | Basic insulation |
| Degree of pollution | 2 |
| Overvoltage category | III |
Environmental Product Compliance
| China RoHS | Environmentally Friendly Use Period = 50 |
|---|---|
| For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration” |